Page 1 Page 2 Page 3 Page 4
62
Troubleshooting
Safety Messages
Please read the following safety messages before troubleshooting or performing
maintenance on the inverter and motor system.
WARNING: Wait at least ten (10) minutes after turning OFF the input power supply
before performing maintenance or an inspection. Otherwise, there is a danger of
electric shock.
WARNING: Make sure that only qualified personnel will perform maintenance,
inspection, and part replacement. Before starting to work, remove any metallic objects
from your person (wristwatch, bracelet, etc.). Be sure to use tools with insulated
handles. Otherwise, there is a danger of electric shock and/or injury to personnel.
WARNING: Never remove connectors by pulling on its wire leads (wires for cooling fan
and logic P.C.board). Otherwise, there is a danger of fire due to wire breakage and/or
injury to personnel.
General Precautions and Notes
Always keep the unit clean so that dust or other foreign matter does not enter the
inverter.
Take special care in regard to breaking wires or making connection mistakes.
Firmly connect terminals and connectors.
Keep electronic equipment away from moisture and oil. Dust, steel filings and other
foreign matter can damage insulation, causing unexpected accidents, so take special
care.
Inspection Items
This chapter provides instructions or checklists for these inspection items:
Daily inspection
Periodical inspection (approximately once a year)
Insulation resistance (Megger) test (approximately once two years)
63
Troubleshooting Tips
The table below lists typical symptoms and the corresponding solution(s).
1. Inverter does not power up.
Possible Cause(s) Corrective Action
Power cable is incorrectly wired. Check input wiring
Short bar or DCL between [P] and [PD]
is disconnected.
Install short bar or DCL between [P] and [PD] terminal.
Power cable is breaking. Check input wiring.
2. Motor does not start.
Possible Cause(s) Corrective Action
Incorrect RUN command source is
selected.
Check RUN command source (A002) for correct source.
Ex. Terminal (digital input) : 01
Operator (RUN key) : 02
Incorrect frequency source is selected. Check frequency source (A001) for correct source.
Ex. Terminal (analog input) : 01
Operator (F001) : 02
Frequency setting is 0Hz. If frequency source is terminal (A001=01), check analog
voltage or current signal at [O] or [OI] terminals.
If frequency source is operator (A001=02), set frequency in
F001.
Depending on frequency source, input proper frequency
reference.
If frequency source is multi-speed operation, set frequency
in A020 to A035 and A220.
RUN command is not set to input
terminal.
If RUN command source is terminal (A002=01), set
"forward" (00:FW) or "reverse" (01:RV) to any input
terminals. In case of 3-wire control, set "3-wire start"
(20:STA), "3-wire stop" (21:STP) and "3-wire FW/RV"
(22:F/R) to any input terminals.
“Multi-speed input(s) (02 to 05:CF1 to
CF4)” is (are) set to input terminal(s)
and active.
Deactivate the input(s).
Both FWD and REV input are active. If RUN command source is FWD/REV input, activate
either FWD or REV input.
Rotation direction restriction (b035) is
enabled.
Check b035.
Incorrect input wiring or short bar
position
Wire inputs correctly and/or install short bar. (ON/OFF
status of inputs are monitored in d005.)
Incorrect analog input or variable
resistor wiring
Wire correctly.
In case of analog voltage or variable resistor input, check
voltage between [O] and [L] terminal.
In case of analog current, check current between current
source and [OI] terminal.
RUN command source is operator, but
input terminal is set to "Force terminal"
and active.
Deactivate the input.
RUN command source is terminal, but
input terminal is set to "Force operator"
and active.
Deactivate the input.
Inverter is in trip status.
(With ALARM LED and "Exxx"
indication)
Reset inverter by STOP/RESET key and check error code.
64
Safety function is enabled and either
GS1 or GS2 input is inactive.
If safety function is used, activate both GS1 and GS2. If
not, disable safety function by dip switch.
Possible Cause(s) Corrective Action
"18:RS", "14:CS" or "11:FRS" is set to
input terminal and the input is active.
Deactivate the input.
"84:ROK" is set to input terminal and
the input is active.
Activate the input.
Cable between inverter and motor or
internal cable of motor is breaking.
Check the wiring.
Excess load. Remove excess load.
Motor is locked. Unlock the motor.
3. Motor does not accelerate to command speed.
Possible Cause(s) Corrective Action
Bad connection of analog wiring. Check the wiring.
In case of analog voltage or variable resistor input, check
voltage between [O] and [L] terminal.
In case of analog current, check current between current
source and [OI] terminal.
Overload restriction or OC suppression
function works.
Check the function level.
Max. frequency (A004) or upper limit
(A061/A261) is lower than as expected.
Check the value.
Acceleration time is excessive. Change acceleration time (F002/A092/A292).
“Multi-speed input(s) (02 to 05:CF1 to
CF4)” is (are) set to input terminal(s)
and active.
Deactivate the input(s).
"06:JG " is set to input terminal and the
input is active.
Deactivate the input.
Excess load. Remove excess load.
Motor is locked. Unlock the motor.
4. Inverter does not respond to changes in frequency setting from operator.
Possible Cause(s) Corrective Action
Incorrect frequency source is selected. Check frequency source (A001=02).
"51:F-TM" is set to input terminal and
the input is active.
Deactivate the input.
5. A part of function codes is not displayed.
Possible Cause(s) Corrective Action
"Function code display restriction" (b037)
is enabled.
Set 00 (all display) to b037.
"86:DISP" is set to input terminal and
the input is active.
Deactivate the input.
6. Operator (keypad) does not respond.
Possible Cause(s) Corrective Action
"86:DISP" is set to input terminal and
the input is active.
Deactivate the input.
65
7. Parameter data does not change.
Possible Cause(s) Corrective Action
Inverter is in RUN status. Stop the inverter, make sure the motor stops and try again.
If "RUN mode edit" is enabled, a part of function codes can
be changed in RUN status.
Software lock function (b031) is enabled. Disable software lock function.
8. Motor rotates reverse direction with forward command.
Possible Cause(s) Corrective Action
Incorrect power wiring. Exchange any two of U/T1, V/T2 or W/T3.
Incorrect logic of direction signal in
3-wire operation.
Check the logic of input set as "22:F/R".
9. Motor rotates reverse direction with RUN key of keypad.
Possible Cause(s) Corrective Action
Keypad RUN key routing (F004) is
incorrectly set.
Check F004.
10. .Overcurrent trip (E03)
Possible Cause(s) Corrective Action
Acceleration time is short. Change acceleration time (F002/A092/A292).
Enable "acceleration hold" function (A069,A070)
Excess load. Remove excess load.
Enable torque boost function.
Set free V/f in V/F characteristic curve selection
(A044/A244=02)
Overload restriction (b021) is disabled
(00).
Enable overload restriction (b021=01/02/03).
When the inverter trips due to Overcurrent(E03), despite overload restriction is enabled(b021=01/02/03).
Overload restriction level (b022/b025) is
high.
Set overload restriction level (b022/b025) lower.
Deceleration rate at overload restriction
(b023/b026) is too short.
Set deceleration rate at overload restriction (b023/b026)
longer.
11. STOP/RESET key does not respond.
Possible Cause(s) Corrective Action
STOP/RESET key disabled. Check "STOP key enable" function. (b087)
Deceleration overvoltage suppression
(b130) or controlled deceleration on
power loss (b050) function is enabled.
Check b130 and b050.
66
12. Sound noise of motor or machine.
Possible Cause(s) Corrective Action
Carrier frequency is low. Set carrier frequency (b083) higher. (This could cause
electric noise and leak current higher.)
Machine frequency and motor frequency
are resonated.
Change output frequency slightly. If resonating in
accel/deceleration, use jump frequency function (A063-68)
to avoid machine frequency.
Over excitation Set base frequency (A003/A203) and AVR voltage
(A082/A282) according to motor rating. If not improved,
reduce V/f gain (A045/A245) slightly or change V/f curve
(A044/A244) as free V/f.
13. Overload trip (E05).
Possible Cause(s) Corrective Action
Improper electronic thermal level Check electronic thermal setting (b012/b013)
14. Over voltage trip (E07).
Possible Cause(s) Corrective Action
Short deceleration time Change deceleration time. (F003/F203/A093/A293)
Overvoltage suppression during
deceleration (b130) is disabled (00).
Enable overvoltage suppression (b130=01/02).
When the inverter trips due to over voltage, despite over voltage suppression is enabled.
Improper overvoltage suppression
propotional gain (b134) or integral time
(135).
Check overvoltage suppression proportional gain (b134)
and integral time (b135).
Overvoltage suppression level (b131) is
high.
Set Overvoltage suppression level (b131) lower. (Lower
limit of parameter b131 must be (input voltage)×√2×
1.1.)
15. Thermistor error trip (E35).
Possible Cause(s) Corrective Action
Thermistor is set to input [5] and DC24V
is supplied.
Check setting of input terminal [5] (C005).
16. Unstable output frequency.
Possible Cause(s) Corrective Action
Improper parameters Set output frequency slightly smaller or bigger value than
power source frequency.
Change motor stabilization constant (H006/H203).
Load variation is excessive. Change motor and inverter to one size bigger.
Power voltage variation is excessive. Check power source.
17. Output torque is not sufficient.
Possible Cause(s) Corrective Action
Improper parameters [Acceleration] Increase torque boost (A042/A242-A043/A243)
Reduce carrier frequency (A083).
Change V/f curve (A044/A244) to SLV.
Change torque boost select (A041/A241) to automatic.
Improper parameters [Deceleration] Increase deceleration time (F003/F203/A093/A293).
Disable AVR function (A081/A281).
Install dynamic braking resistor or regenerative braking
unit.
67
18. If cable to operator is disconnected, inveter will trip or stop.
Possible Cause(s) Corrective Action
Improper setting of b165. Set ex.operator com loss action (b165) to 02.
19. No response over Modbus communication.
Possible Cause(s) Corrective Action
New parameter is not updated. If C071, C074 or C075 is changed, cycle power or reset
inverter by turning RS terminal ON and OFF.
Incorrect setting of RUN command
source (A002/A202).
Set RUN command source (A002/A202) to 03.
Incorrect setting of Frequency source
(A001/A201).
Set frequency source (A001/A201) to 03.
Incorrect setting of com. speed. Check communication speed (A071).
Incorrect setting or duplication of
Modbus address.
Check Modbus address (A072).
Incorrect setting of com. parity. Check communication parity (A074).
Incorrect setting of com. stop bit. Check communication stop bit (A075).
Incorrect wiring. Check communication wiring at SP,SN terminals.
20. When inverter starts, ECB (Earth leakage Circuit Breaker) trips.
Possible Cause(s) Corrective Action
Leak current of inverter is excessive. Reduce carrier frequency (A083).
Increase current sensor level of ECB or replace ECB with
another one having higher current sensor level.
21.DC braking doesn’t work
Possible Cause(s) Corrective Action
DC braking force for deceleration (A054)
isn’t set. (Defaults (0.))
Set DC braking force for deceleration (A054).
DC braking time for deceleration (A055)
isn’t set. (Defaults (0.0))
Set DC braking time for deceleration (A055).
22.Under-voltage error
Possible Cause(s) Corrective Action
Decrease in input voltage due to capacity
shortage of electric source.
Make capacity of electric source larger.
23.TV or radio near inverter receives noises
Possible Cause(s) Corrective Action
The radiation noise generated by the
inverter.
Put away those devices from the inverter as far as possible.
68
Monitoring Trip Events, History, & Conditions
Fault Detection and Clearing
RUN
STOP
STOP
RESET
STOP
RESET
Tri
p
Fault
RUN
The microprocessor in the inverter detects a
variety of fault conditions and captures the event,
recording it in a history table. The inverter output
turns OFF, or “trips” similar to the way a circuit
breaker trips due to an over-current condition.
Most faults occur when the motor is running (refer
to the diagram to the right). However, the inverter
could have an internal fault and trip in Stop Mode.
In either case, you can clear the fault by pressing
the Stop/Reset key. Additionally, you can clear the
inverter’s cumulative trip history by performing
the procedure “Restoring Factory Default Settings”
on page 6–8 (setting B084=00 will clear the trip
history but leave inverter settings intact).
Fault
Error Codes
An error code will appear on the display automatically when a fault causes the inverter
to trip. The following table lists the cause associated with the error.
Erro
r
Code
Name Cause(s)
E01
Over-current event while at
constant speed
The inverter output was short-circuited, or the
motor shaft is locked or has a heavy load. These
conditions cause excessive current for the inverter,
so the inverter output is turned OFF.
The dual-voltage motor is wired incorrectly.
E02
Over-current event during
deceleration
E03
Over-current event during
acceleration
E04
Over-current event during
other conditions
E05
Overload protection When a motor overload is detected by the
electronic thermal function, the inverter trips and
turns OFF its output.
E06
Braking resistor overload
protection
When the BRD operation rate exceeds
the setting of "b090", this protective
function shuts off the inverter output and
displays the error code.
E07
Over-voltage protection When the DC bus voltage exceeds a threshold, due
to regenerative energy from the motor.
E08
EEPROM error When the built-in EEPROM memory has problems
due to noise or excessive temperature, the inverter
trips and turns OFF its output to the motor.
E09
Under-voltage error A decrease of internal DC bus voltage below a
threshold results in a control circuit fault. This
condition can also generate excessive motor heat or
cause low torque. The inverter trips and turns OFF
its output.
E10
Current detection error If an error occurs in the internal current
detection system, the inverter will shut off its
output and display the error code.
69
Error
Code
Name Cause(s)
E11
CPU error A malfunction in the built-in CPU has occurred, so
the inverter trips and turns OFF its output to the
motor.
E12
External trip A signal on an intelligent input terminal
configured as EXT has occurred. The inverter trips
and turns OFF the output to the motor.
E13
USP When the Unattended Start Protection (USP) is
enabled, an error occurred when power is applied
while a Run signal is present. The inverter trips
and does not go into Run Mode until the error is
cleared.
E14
Ground fault The inverter is protected by the detection of ground
faults between the inverter output and the motor
upon during powerup tests. This feature protects
the inverter, and does not protect humans.
E15
Input over-voltage The inverter tests for input over-voltage after the
inverter has been in Stop Mode for 100 seconds. If
an over-voltage condition exists, the inverter
enters a fault state. After the fault is cleared, the
inverter can enter Run Mode again.
E21
Inverter thermal trip When the inverter internal temperature is above
the threshold, the thermal sensor in the inverter
module detects the excessive temperature of the
power devices and trips, turning the inverter
output OFF.
E22
CPU communication error When communication between two CPU fails,
inverter trips and displays the error code.
E25
Main circuit
error (*3)
The inverter will trip if the power supply
establishment is not recognized because of a
malfunction due to noise or damage to the main
circuit element.
E30
Driver error An internal inverter error has occurred at the
safety protection circuit between the CPU and
main driver unit. Excessive electrical noise may be
the cause. The inverter has turned OFF the IGBT
module output.
E35
Thermistor When a thermistor is connected to terminals [5]
and [L] and the inverter has sensed the
temperature is too high, the inverter trips and
turns OFF the output.
E36
Braking error When "01" has been specified for the Brake Control
Enable (b120), the inverter will trip if it cannot
receive the braking confirmation signal within the
Brake Wait Time for Confirmation (b124) after the
output of the brake release signal.
E37
Safe Stop Safe stop signal is given.
E38
Low-speed overload protection If overload occurs during the motor operation at a
very low speed, the inverter will detect the
overload and shut off the inverter output.
610
Error
Code
Name Cause(s)
E40
Operator connection When the connection between inverter and
operator keypad failed, inverter trips and displays
the error code.
E41
Modbus communication error When “trip” is selected (C076=00) as a behavior in
case of communication error, inverter trips when
timeout happens.
E43
EzSQ invalid instruction The program stored in inverter memory has been
destroyed, or the PRG terminal was turned on
without a program downloaded to the inverter.
E44
EzSQ nesting count error Subroutines, if-statement, or for-next loop are
nested in more than eight layers
E45
EzSQ instruction error Inverter found the command which cannot be
executed.
E50
to
E59
EzSQ user trip (0 to 9) When user –defined trip happens, inverter trips
and displays the error code.
E60
Option error (DeviceNet
Communications error)
If the disconnection due to the Bus-Off signal or
timeout occurs during the operation using
DeviceNet commands, the inverter will shut off its
output and display the error code shown on the
right.
(The inverter will trip according to the settings of
"p45" and "P048".)
E61
Option error (duplicated MACID) If two or more devices having the same
MAC ID are detected in the same network, the
inverter will display the error code shown on the
right.
E62
Option error (External trip) If the Force Fault/Trip bit of Attribute 17 in the
Instance 1 of the Control Supervisory object is set
to "1", the inverter will shut off its output and
display the error code shown on the right.
E63 to
E68
Option error The inverter detects errors in the option board
mounted in the optional slot. For details, refer to
the instruction manual for the mounted option
board.
E69
Option error (inverter
communication error)
If timeout occurs during the communication
between the inverter and DeviceNet option board,
the inverter will shut off its output and display the
error code shown on the right.
E80
Encoder
disconnection
If the encoder wiring is disconnected, an encoder
connection error is detected, the encoder fails, or an
encoder that does not support line driver output is
used, the inverter will shut off its output and display
the error code shown on the right.
E81
Excessive speed If the motor speed rises to "maximum frequency
(A004) x over-speed error detection level (P026)" or
more, the inverter will shut off its output and
display the error code shown on the right.
E83
Positioning range error If current position exceeds the position range
(P072-P073), the inverter will shut off its output
and display the error code.
611
Error
Code
Name Descriptions
Rotating
Reset RS input is ON or STOP/RESET key is pressed.
Undervoltage
If input voltage is under the allowed level, inverter
shuts off output and wait with this indication.
Waiting to restart
This indication is displayed after tripping before
restarting.
Restricted operation
command
Commanded RUN direction is restricted in b035.
Trip history
initializing
Trip history is being initialized.
No data
(Trip monitor)
No trip/waning data exists.
Blinking
Communication
error
Communication between inverter and digital
operator fails.
Auto-tuning
completed
Auto-tuning is completed properly.
Auto-tuning error Auto-tuning fails.
NOTE:
Reset is not allowed in 10 second after trip.
NOTE: When error E08, E14 and E30 occur, reset operation by RS terminal or STOP/RESET
key is not accepted. In this case, reset by cycling power. If still same error occurs, perform
initialization.
Warning Codes
If set parameter is conflicted to other parameters, warning code is displayed as follows.
Warning
Code
Warning condition
001
Frequency upper limit (A061)
>
Max. Frequency (A004)
002
Frequency lower limit (A062)
>
Max. Frequency (A004)
005
Output Frequency setting (F001)
Multi-speed freq. 0 (A020)
>
Max. Frequency (A004)
015
Output Frequency setting (F001)
Multi-speed freq. 0 (A020)
>
Frequency upper limit (A061)
025
Frequency lower limit (A062)
>
Output Frequency setting (F001)
Multi-speed freq. 0 (A020)
031
Start frequency (A082)
>
Frequency upper limit (A061)
032
Start frequency (A082)
>
Frequency lower limit (A062)
035
Start frequency (A082)
>
Output Frequency setting (F001)
Multi-speed freq. 0 (A020)
036
Start frequency (A082)
>
Multi-speed freq. 1-15 (A021-A035)
037
Start frequency (A082)
>
Jogging frequency (A038)
612
Warning
Code
Warning condition
085
Output Frequency setting (F001)
Multi-speed freq. 0 (A020)
=
Jump frequency
(A063/A063/A063±A064/A066/A068)
086
Multi-speed freq. 1-15 (A021-A035)
091
Free setting V/f frequency 7 >
Frequency upper limit (A061)
092
Free setting V/f frequency 7 >
Frequency lower limit (A062)
095
Free setting V/f frequency 7 >
Output Frequency setting (F001)
Multi-speed freq. 0 (A020)
201
Frequency upper limit (A261)
>
Max. Frequency (A204)
202
Frequency lower limit (A262)
>
Max. Frequency (A204)
205
Output Frequency setting (F001)
Multi-speed freq. 0 (A220)
>
Max. Frequency (A204)
215
Output Frequency setting (F001)
Multi-speed freq. 0 (A220)
>
Frequency upper limit (A261)
225
Frequency lower limit (A262)
>
Output Frequency setting (F001)
Multi-speed freq. 0 (A220)
231
Start frequency (A082)
>
Frequency upper limit (A261)
232
Start frequency (A082)
>
Frequency lower limit (A262)
235
Start frequency (A082)
>
Output Frequency setting (F001)
Multi-speed freq. 0 (A220)
285
Output Frequency setting (F001)
Multi-speed freq. 0 (A220)
=
Jump frequency
(A063/A063/A063±A064/A066/A068)
291
Free setting V/f frequency 7 >
Frequency upper limit (A261)
292
Free setting V/f frequency 7 >
Frequency lower limit (A262)
295
Free setting V/f frequency 7 >
Output Frequency setting (F001)
Multi-speed freq. 0 (A220)
613
Trip History and Inverter Status
We recommend that you first find the cause of the fault before clearing it. When a fault
occurs, the inverter stores important performance data at the moment of the fault. To
access the data, use the monitor function (dxxx) and select d081 details about the
present fault. The previous 5 faults are stored in d082 to d086. Each error shifts
d081-d085 to d082-d086, and writes the new error to d081.
The following Monitor Menu map shows how to access the error codes. When fault(s)
exist, you can review their details by first selecting the proper function: D081 is the
most recent, and D086 is the oldest.
E072
D081
U
V
SET
ESC
U
V
Trip history 1 (Latest) Trip history 6
Error code
Hz
A
Hz
A
Hz
A
Hz
A
Hz
A
Hz
A
...
d086
.
.
6000
.
U
V
400
U
V
2840
U
V
18
U
V
15
.
Output frequency
Output current
Elapsed RUN time
DC bus voltage
Elapsed power-
ON time
E072
.
Inverter status
at trip point
Trip cause
.0
Power up or initial processing
.1
Stop
.2
Deceleration
.3
Constant speed
A
cceleration
.4
.5
.6
.7
0Hz command and RUN
Starting
DC braking
.8
Overload restriction
Note: Indicated inverter status could be
different from actual inverter behavior.
e.g. When PID operation or frequency given
by analog signal, although it seems constant
speed, acceleration and deceleration could
be repeated in very short cycle.
614
Restoring Factory Default Settings
You can restore all inverter parameters to the original factory (default) settings
according to area of use. After initializing the inverter, use the powerup test in Chapter
2 to get the motor running again. If operation mode (std. or high frequency) mode is
changed, inverter must be initialized to activate new mode. To initialize the inverter,
follow the steps below.
(1) Select initialization mode in b084.
(2) If b084=02, 03 or 04, select initialization target data in b094.
(3) If b084=02, 03 or 04, select country code in b085.
(4) Set 01 in b180.
(5) The following display appears for a few seconds, and initialization is completed with
d001 displayed.
Display during initialization
Initialization of trip history
5 HC
Initialization
mode
Initialization for area A
5 00
Initialization for area B
5 01
The left digit rotates during initialization
d001
Blinking alternately
HD mode
1-C
Operation
mode after
initialization
ND mode
1-v
High frequency mode
H-1
“B” Function
Func.
Code
Name Description
B084
Initialization mode
(parameters or trip
history)
Select initialized data, five option codes:
00Initialization disabled
01Clears Trip history
02Initializes all Parameters
03Clears Trip history and initializes all parameters
04Clears Trip history and initializes all parameters and EzSQ
program
b094
Initialization target
data setting
Select initialized parameters, four option codes:
00All parameters
01All parameters except in/output terminals and communication.
02Only registered parameters in Uxxx.
03All parameters except registered parameters in Uxxx and b037.
B085
Initial value select Select default parameter values:
00area A 01area B
b180
Initialization trigger
This is to perform initialization by parameter input with b084, b085
and b094. Two option codes:
00Initialization disable
01Perform initialization
Data of b084 is not saved in EEPROM to avoid unintentional initializing.
615
Maintenance and Inspection
Daily and Yearly Inspection Chart
Item Inspected Check for…
Inspection
Cycle
Inspection
Method
Criteria
Daily Year
Overall
Ambient
environment
Extreme
temperatures &
humidity
9
Thermometer,
hygrometer
Ambient temperature
between –10 to 50°C,
Humidity 90% or less
non-condensing
Major
devices
Abnormal noise &
vib.
9
Visual and aural Stable environment for
electronic controls
Power
supply
voltage
Voltage tolerance
9
Digital volt meter,
measure between
inverter terminals
[L1], [L2], [L3]
200V class: 50/60 Hz
200 to 240V (-15/+10%)
400V class: 50/60 Hz
380 to 460V (-15/+10%)
Main
circuit
Ground
Insulation
Adequate
resistance
9
Refer to P6-16
5 MΩ or greater
Mounting No loose screws
9
Torque wrench M3.5: 1.0Nm
M4: 1.4Nm
M5: 3.0
M6: 3.9 to 5.1Nm
M8: 5.9 to 8.8Nm
Components Overheating
9
Thermal trip
events
No trip events
IGBT Resistance value
9
Refer to P6-17
Terminal
block
Secure connections
9
Visual No abnormalities
Smoothing
capacitors
Leaking, swelling
9
Visual No abnormalities
Relay(s) Chattering
9
Aural Single click when
switching ON or OFF
Resistors Cracks or
discoloring
9
Visual Check Ohms of optional
braking res.
Control
circuit
Function Voltage balance
between phases
9
Measure voltage
between U,V,W
Difference must be 2%
or less.
Protection circuit
9
e.g. Input Ex.trip
signal and check
inverter behavior
and alarm signal.
Functions properly.
Overall No odor,
discoloring,
corrosion
9
Visual No abnormalities
Capacitor Leaking, swelling
9
Visual Undistorted appearance
Cooling
Cooling fan Noise
9
Power down,
manually rotate
Rotation must be
smooth
Dust
9
Visual Vacuum to clean
Mounting
9
Visual Mounted firmly
Heat sink Dust
9
Visual Vacuum to clean
Display
LEDs Legibility
Visual All LED segments work
Note 1: The life of a capacitor is affected by the ambient temperature. See page 6–21.
Note 2: Designed life of a cooling fan is.10 years. However, it is affected by the ambient
temperature and other environmental conditions.
Note 3: The inverter must be cleaned periodically. If dust accumulates on the fan and
heat sink, it can cause overheating of the inverter.
616
Megger test
The
megger
is a piece of test equipment that uses a high voltage to determine if an
insulation degradation has occurred. For inverters, it is important that the power
terminals be isolated from the Earth GND terminal via the proper amount of
insulation.
The circuit diagram below shows the inverter wiring for performing the megger test.
Just follow the steps to perform the test:
1. Remove power from the inverter and wait at least 5 minutes before proceeding.
2. Open the front housing panel to access the power wiring.
3. Remove all wires to terminals [R, S, T, PD/+1, P/+, N/–, U, V, and W]. Most
importantly, the input power and motor wires will be disconnected from the inverter.
4. Use a bare wire and short terminals [R, S, T, PD/+1, P/+, N/–, U, V, and W] together
as shown in the diagram.
5. Connect the megger to the inverter Earth GND and to the shorted power terminals
as shown. Then perform the megger test at 500 VDC and verify 5M or greater
resistance.
6. After completing the test, disconnect the megger from the inverter.
7. Reconnect the original wires to terminals [R, S, T, PD/+1, P/+, N/–, U, V, and W].
CAUTION: Do not connect the megger to any control circuit terminals such as
intelligent I/O, analog terminals, etc. Doing so could cause damage to the inverter.
CAUTION: Never test the withstand voltage (HIPOT) on the inverter. The inverter has
a surge protector between the main circuit terminals above and the chassis ground.
CAUTION: Power terminal assignment is different compared to old models such as
L100, L200 series, etc,. Pay attention when wiring the power cable.
WJ200
617
IGBT Test Method
The following procedure will check the inverter transistors (IGBTs) and diodes:
1. Disconnect input power to terminals [R, S, and T] and motor terminals [U, V, and
W].
2. Disconnect any wires from terminals [+] and [–] for regenerative braking.
3. Use a Digital Volt Meter (DVM) and set it for 1 resistance range. You can check the
status of the charging state of terminals [R, S, T, U, V, W, +, and –] of the inverter
and the probe of the DVM by measuring the charging state.
Table Legend Almost infinite resistance: Almost zero resistance: 0
Part DVM Measured
Value
Part DVM Measured
Value
Part DVM Measured
Value
+ + +
D1 [R] [+1]
D5 [S] []
0
TR4 [U] []
0
[+1] [R]
0
[] [S]
[][U]
D2 [S] [+1]
D6 [T] []
0
TR5 [V] []
0
[+1] [S]
0
[] [T]
[][V]
D3 [T] [+1]
TR1 [U] [+]
TR6 [W] []
0
[+1] [T]
0
[+] [U]
0
[][W]
D4 [R] []
0
TR2 [V] [+]
TR7 [RB] [+]
[] [R]
[+] [V]
0
[+] [RB]
0
TR3 [W] [+]
[RB] []
[+] [W]
0
[] [RB]
NOTE: The resistance values for the diodes or the transistors will not be exactly the
same, but they will be close. If you find a significance difference, a problem may exist.
NOTE: Before measuring the voltage between [+] and [–] with the DC current range,
confirm that the smoothing capacitor is discharged fully, then execute the tests.
D1
[R/L1]
D2 D3
D4 D5 D6
[PD/+1] [P/+]
[RB]
TR1 TR2 TR3
TR4 TR5 TR6 TR7
[U/T1]
+
-
[N/ ]
[S/L2]
[T/L3]
[V/T2]
[W/T3]
618
General Inverter Electrical Measurements
The following table specifies how to measure key system electrical parameters. The
diagrams on the next page show inverter-motor systems and the location of
measurement points for these parameters.
Parameter
Circuit location of
measurement
Measuring
instrument
Notes Reference Value
Supply voltage
E
1
E
R
– across L1 and L2
E
S
– across L2 and L3
E
T
– across L3 and L1
Moving-coil type
voltmeter or
rectifier type
voltmeter
Fundamental
wave effective
value
Commercial supply
voltage
200V class:
200–240V, 50/60 Hz
400V class:
380–460V, 50/60 Hz
Single phase
E
1
– across L1 and N
Supply current
I
1
I
r
– L1
I
s
– L2
I
t
– L3
Total effective
value
Single phase
I
1
= L1
Supply power
W
1
W
11
– across L1 and L2
W
12
– across L2 and L3
Total effective
value
Single phase
W
1
– across L1 and N
Supply power
factor Pf
1
%100
3
11
1
1
×
××
=
IE
W
Pf
Output voltage
E
O
E
U
– across U and V
E
V
– across V and W
E
W
– across W and U
Rectifier type
voltmeter
Total effective
value
Output current
I
O
I
U
– U
I
V
– V
I
W
– W
Moving-coil type
ammeter
Total effective
value
Output power
W
O
W
O1
– across U and V
W
O2
– across V and W
Electronic type
wattmeter
Total effective
value
Output power
factor Pf
O
Calculate the output power factor from the output voltage E,
output current I, and output power W.
%100
3
1
×
××
=
OO
O
IE
W
Pf
Note 1: Use a meter indicating a fundamental wave effective value for voltage, and meters
indicating total effective values for current and power.
Note 2:
The inverter output has a distorted waveform, and low frequencies may cause
erroneous readings. However, the measuring instruments and methods listed above
provide comparably accurate results.
Note 3:
A general-purpose digital volt meter (DVM) is not usually suitable to measure a
distorted waveform (not pure sinusoid).
619
The figures below show measurement locations for voltage, current, and power
measurements listed in the table on the previous page. The voltage to be measured is
the fundamental wave effective voltage. The power to be measured is the total effective
power.
Single-phase Measurement Diagram
E
V
E
U
I
V
E
W
I
W
I
U
Three-phase Measurement Diagram
W
2
W
1
E
W
E
V
I
V
I
U
E
T
E
U
I
R
I
T
I
S
E
S
E
R
I
W
620
Inverter Output Voltage Measurement Techniques
Taking voltage measurements around drives equipment requires the right equipment
and a safe approach. You are working with high voltages and high-frequency switching
waveforms that are not pure sinusoids. Digital voltmeters will not usually produce
reliable readings for these waveforms. And, it is usually risky to connect high voltage
signals to oscilloscopes. The inverter output semiconductors have some leakage, and
no-load measurements produce misleading results. So, we highly recommend using the
following circuits to measure voltage for performing the equipment inspections.
T/L3
S/L2
R/L1
T/L3
S/L2
R/L1
HIGH VOLTAGE: Be careful not to touch wiring or connector terminals when working
with the inverters and taking measurements. Be sure to place the measurement
circuitry components above in an insulated housing before using them.
621
Capacitor Life Curves
The DC bus inside the inverter uses a large capacitor as shown in the diagram below.
The capacitor handles high voltage and current as it smoothes the power for use by the
inverter. So, any degradation of the capacitor will affect the performance of the
inverter.
Capacitor life is reduced in higher ambient temperatures, as the graph below
demonstrates. Under the condition of average ambient temperature 40degC, 80% load,
24 hours operation, the lifetime is 10years. Be sure to keep the ambient temperature at
acceptable levels, and perform maintenance inspections on the fan, heat sink, and
other components. If the inverter is installed on a cabinet, the ambient temperature is
the temperature inside the cabinet.
Rectifier
Motor
Inverter Converter Internal
DC Bus
Power
Input
R/L1
S/L2
Variable-frequency Drive
T/L3
U/T1
V/T2
W/T3
A
mbient
temperature, °C
50
Years
Operation 24hours/day, 100% load
40
30
20
10
1 2 3 4 5 6 7 8 9 10
Operation 24hours/day, 80% load
Capacitor Life Curve
0
622
Warranty
3. Always keep this manual handy; please do not lose it. Please contact
your Hitachi distributor to purchase replacement or additional
manuals.
2. When service is required for the product at your work site, all
expenses associated with field repair shall be charged to the
purchaser.
c. Malfunction or damage caused by fire, earthquake, flood,
lightening, abnormal input voltage, contamination, or other
natural disasters
b. Malfunction or damage caused by a drop after purchase and
transportation
1. Service in the following cases, even within the warranty period, shall
be charged to the purchaser:
a. Malfunction or damage caused by mis-operation or modification
or improper repair
Warranty Terms
The warranty period under normal installation and handling conditions
shall be two (2) years from the date of manufacture, or one (1) year from
the date of installation, whichever occurs first. The warranty shall
cover the repair or replacement, at Hitachi's sole discretion, of ONLY
the inverter that was installed.
A1
A
Glossary and
Bibliography
In This Appendix… page
- Glossary ........................................................................................... 2
- Bibliography ..................................................................................... 8
A2
Glossary
A
mbient
T
emperature
The air temperature in the chamber containing a powered electronic
unit. A unit’s heat sinks rely on a lower ambient temperature in
order to dissipate heat away from sensitive electronics.
A
rrival Frequency
The arrival frequency refers to the set output frequency of the
inverter for the constant speed setting. The arrival frequency feature
turns on an output when the inverter reaches the set constant speed.
The inverter has various arrival frequencies and pulsed or latched
logic options.
A
uto-tuning
The ability of a controller to execute a procedure that interacts with
a load to determine the proper coefficients to use in the control
algorithm. Auto-tuning is a common feature of process controllers
with PID loops. Hitachi inverters feature auto tuning to determine
motor parameters for optimal commutation. Auto-tuning is available
as a special command from a digital operator panel. See also
Digital
Operator Panel
.
B
ase Frequency
The power input frequency for which an AC induction motor is
designed to operate. Most motors will specify a 50 to 60 Hz value.
The Hitachi inverters have a programmable base frequency, so you
must ensure that parameter matches the attached motor. The term
base frequency
helps differentiate it from the carrier frequency. See
also
Carrier Frequency
and
Frequency Setting
.
B
raking Resistor
An energy-absorbing resistor that dissipates energy from a
decelerating load. Load inertia causes the motor to act as a generator
during deceleration. For the X200 inverter models, the braking unit
and braking resistor are optional (external) components. See also
Four-quadrant Operation
and
Dynamic Braking.
B
reak-away Torque
The torque a motor must produce to overcome the static friction of a
load, in order to start the load moving.
Carrier Frequency
The frequency of the constant, periodic, switching waveform that the
inverter modulates to generate the AC output to the motor. See also
PWM
.
CE
A regulatory agency for governing the performance of electronic
products in Europe. Drive installations designed to have CE
approval must have particular filter(s) installed in the application.
Choke
An inductor that is tuned to react at radio frequencies is called a
“choke,” since it attenuates (chokes) frequencies above a particular
threshold. Tuning is often accomplished by using a movable
magnetic core. In variable-frequency drive systems, a choke
positioned around high-current wiring can help attenuate harmful
harmonics and protect equipment. See also
Harmonics
.
A3
D
C Braking
The inverter DC braking feature stops the AC commutation to the
motor, and sends a DC current through the motor windings in order
to stop the motor. Also called “DC injection braking,” it has little
effect at high speed, and is used as the motor is nearing a stop.
D
eadband
In a control system, the range of input change for which there is no
perceptible change in the output. In PID loops, the error term may
have a dead band associated with it. Deadband may or may not be
desirable; it depends on the needs of the application.
D
igital Operator
P
anel
For Hitachi inverters, “digital operator panel” (DOP) refers first to
the operator keypad on the front panel of the inverter. It also
includes hand-held remote keypads, which connect to the inverter
via a cable. Finally, the DOP Professional is a PC-based software
simulation of the keypad devices.
D
iode
A semiconductor device that has a voltage-current characteristic that
allows current to flow only in one direction, with negligible leakage
current in the reverse direction. See also
Rectifier
.
D
uty Cycle
1. The percent of time a square wave of fixed frequency is ON
(high) versus OFF (low).
2. The ratio of operating time of a device such as a motor to its
resting time. This parameter usually is specified in association
with the allowable thermal rise for the device.
D
ynamic Braking
For the X2002 inverter models, the braking unit and braking resistor
are optional (external) components. The dynamic braking feature
shunts the motor-generated EMF energy into a special braking
resistor. The added dissipation (braking torque) is effective at higher
speeds, having a reduced effect as the motor nears a stop.
EDM
[
Functional Safety Related Term
] External Device Monitoring, the
output signal from inverter to external device in order to feed back
the status that the both safety path working properly. Safety
certificate is issued based on the condition that this EDM signal is
interfaced to certified external device to avoid restarting or to inform
in case of failure in safety path.
Error
In process control, the error is the difference between the desired
value or setpoint (SP) and the actual value of a the process variable
(PV). See also
Process Variable
and
PID Loop
.
EMI
Electromagnetic Interference - In motor/drive systems, the switching
of high currents and voltages creates the possibility of generating
radiated electrical noise that may interfere with the operation of
nearby sensitive electrical instruments or devices. Certain aspects of
an installation, such as long motor lead wire lengths, tend to
increase the chance of EMI. Hitachi provides accessory filter
components you can install to decrease the level of EMI.
F
our-quadrant
o
peration
Referring to a graph of torque versus direction, a four-quadrant drive
can turn the motor either forward or reverse, as well as decelerate in
either direction (see also
reverse torque
). A load that has a relatively
A4
high inertia and must move in both directions and change directions
rapidly requires four-quadrant capability from its drive.
F
ree-run Stop
A method of stopping a motor, caused when the inverter simply
turns OFF its motor output connections. This may allow the motor
and load to coast to a stop, or a mechanical brake may intervene and
shorten the deceleration time.
F
requency Setting
While frequency has a broad meaning in electronics, it typically
refers to motor speed for variable-frequency drives (inverters). This
is because the output frequency of the inverter is variable, and is
proportional to the attained motor speed. For example, a motor with
a base frequency of 60 Hz can be speed controlled with an inverter
output varying form 0 to 60 Hz. See also
Base Frequency
,
Carrier
Frequency
, and
Slip
.
H
armonics
A
harmonic
is a whole number multiple of a base of fundamental
frequency. The square waves used in inverters produce high
frequency harmonics, even though the main goal is to produce
lower-frequency sine waves. These harmonics can be harmful to
electronics (including motor windings) and cause radiated energy
that interferes with nearby electronic devices. Chokes, line reactors,
and filters are sometimes used to suppress the transmission of
harmonics in an electrical system. See also
Choke
.
H
orsepower
A unit of physical measure to quantify the amount of work done per
unit of time. You can directly convert between horsepower and Watts
as measurements of power.
I
GBT
Insulated Gate Bipolar Transistor(IGBT) – A semiconductor
transistor capable of conducting very large currents when in
saturation and capable of withstanding very high voltages when it is
OFF. This high-power bipolar transistor is the type used in Hitachi
inverters.
I
nertia
The natural resistance a stationary object to being moved by an
external force. See also
Momentum
.
I
ntelligent Terminal
A configurable input or output logic function on the Hitachi
inverters. Each terminal may be assigned one of several functions.
I
nverter
A device that electronically changes DC to AC current through an
alternating process of switching the input to the output, inverted
and non-inverted. A variable speed drive such as the Hitachi X200
2
is also called an inverter, since it contains three inverter circuits to
generate 3-phase output to the motor.
I
solation
T
ransformer
A transformer with 1:1 voltage ratio that provides electrical
isolation between its primary and secondary windings. These are
typically used on the power input side of the device to be protected.
An isolation transformer can protect equipment from a ground fault
or other malfunction of nearby equipment, as well as attenuate
harmful harmonics and transients on the input power.
A5
J
ogging Operation
Usually done manually, a jog command from an operator’s panel
requests the motor/drive system to run indefinitely in a particular
direction, until the machine operator ends the jog operation.
J
ump Frequency
A
jump frequency
is a point on the inverter output frequency range
that you want the inverter to skip around. This feature may be used
to avoid a resonant frequency, and you can program up to three jump
frequencies in the inverter.
L
ine Reactor
A three-phase inductor generally installed in the AC input circuit of
an inverter to minimize harmonics and to limit short-circuit current.
M
omentum
The physical property of a body in motion that causes it to remain in
motion. In the case of motors, the rotor and attached load are
rotating and possesses angular momentum.
M
ulti-speed
O
peration
The ability of a motor drive to store preset discrete speed levels for
the motor, and control motor speed according to the currently
selected speed preset. The Hitachi inverters have 16 preset speeds.
M
otor Load
In motor terminology, motor load consists of the inertia of the
physical mass that is moved by the motor and the related friction
from guiding mechanisms. See also
Inertia
.
N
EC
The National Electric Code is a regulatory document that governs
electrical power and device wiring and installation in the United
States.
N
EMA
The National Electric Manufacturer’s Association. NEMA Codes are
a published series of device ratings standards. Industry uses these to
evaluate or compare the performance of devices made by various
manufacturers to a known standard.
O
pen-collector
O
utputs
A common logic-type discrete output that uses an NPN transistor
that acts as a switch to a power supply common, usually ground. The
transistor’s
collector
is
open
for external connection (not connected
internally). Thus, the output
sinks
external load current to ground.
P
ower Factor
A ratio that expresses a phase difference (timing offset) between
current and voltage supplied by a power source to a load. A perfect
power factor = 1.0 (no phase offset). Power factors less than one
cause some energy loss in power transmission wiring (source to load).
P
ID Loop
Proportional - Integral-Derivative - A mathematical model used for
process control. A process controller maintains a process variable
(PV) at a setpoint (SP) by using its PID algorithm to compensate for
dynamic conditions and vary its output to drive the PV toward the
desired value. For variable-frequency drives, the process variable is
the motor speed. See also
Error
.
A6
P
rocess Variable
A physical property of a process that is of interest because it affects
the quality of the primary task accomplished by the process. For an
industrial oven, temperature is the process variable. See also
PID
Loop
and
Error
.
P
roof Test
[
Functional Safety Related Term
] The test to be carried out
periodically to confirm the proper working of safety path. Safety
certificate is issued based on the condition that this proof test is
carried out at least once a year.
P
WM
Pulse-width modulation: A type of AC adjustable frequency drive
that accomplishes frequency and voltage control at the output section
(inverter) of the drive. The drive output voltage waveform is at a
constant amplitude, and by “chopping” the waveform (pulsewidth-
modulating), the average voltage is controlled. The chopping
frequency is sometimes called the
Carrier Frequency
.
R
eactance
The impedance of inductors and capacitors has two components. The
resistive part is constant, while the reactive part changes with
applied frequency. These devices have a complex impedance
(complex number), where the resistance is the real part and the
reactance is the imaginary part.
R
ectifier
An electronic device made of one or more diodes that converts AC
power into DC power. Rectifiers are usually used in combination
with capacitors to filter (smooth) the rectified waveform to closely
approximate a pure DC voltage source.
R
egenerative
B
raking
A particular method of generating reverse torque to a motor, an
inverter will switch internally to allow the motor to become a
generator and will either store the energy internally, deliver the
braking energy back to the main power input, or dissipate it with a
resistor.
R
egulation
The quality of control applied to maintain a parameter of interest at
a desired value. Usually expressed as a percent (±) from the nominal,
motor regulation usually refers to its shaft speed.
R
everse Torque
The torque applied in the direction opposite to motor shaft rotation.
As such, reverse torque is a decelerating force on the motor and its
external load.
R
otor
The windings of a motor that rotate, being physically coupled to the
motor shaft. See also
Stator.
Saturation Voltage
For a transistor semiconductor device, it is in saturation when an
increase in input current no longer results in an increase in the
output current. The saturation voltage is the voltage drop across the
device. The ideal saturation voltage is zero.
Sensorless Vector
Control
A technique used in some variable-frequency drives (featured in
some other Hitachi inverter model families) to rotate the force vector
in the motor without the use of a shaft position sensor (angular).
Benefits include an increase in torque at the lowest speed and the
cost savings from the lack of a shaft position sensor.
A7
Setpoint (SP)
The
setpoint
is the desired value of a process variable of interest. See
also
Process Variable (PV)
and
PID Loop
.
Single-phase power
An AC power source consisting of Hot and Neutral wires. An Earth
Ground connection usually accompanies them. In theory, the voltage
potential on Neutral stays at or near Earth Ground, while Hot varies
sinusoidally above and below Neutral. This power source is named
Single Phase to differentiate it from three-phase power sources.
Some Hitachi inverters can accept single phase input power, but
they all output three-phase power to the motor. See also
T
hree-phase
.
Slip
The difference between the theoretical speed of a motor at no load
(determined by its inverter output waveforms) and the actual speed.
Some slip is essential in order to develop torque to the load, but too
much will cause excessive heat in the motor windings and/or cause
the motor to stall.
Squirrel Cage
A “nick-name” for the appearance of the rotor frame assembly for an
AC induction motor.
Stator
The windings in a motor that are stationary and coupled to the
power input of the motor. See also
Rotor
.
T
achometer
1. A signal generator usually attached to the motor shaft for the
purpose of providing feedback to the speed controlling device of
the motor.
2. A speed-monitoring test meter that may optically sense shaft
rotation speed and display it on a readout.
T
hermal Switch
An electromechanical safety device that opens to stop current flow
when the temperature at the device reaches a specific temperature
threshold. Thermal switches are sometimes installed in the motor in
order to protect the windings from heat damage. The inverter can
use thermal switch signals to trip (shut down) if the motor overheats.
See also
Trip
.
T
hermistor
A type of temperature sensor that changes its resistance according to
its temperature. The sensing range of thermistors and their
ruggedness make them ideal for motor overheating detection.
Hitachi inverters have built-in thermistor input circuits, which can
detect an overheated motor and shut off (trip) the inverter output.
T
hree-phase power
An AC power source with three Hot connections that have phase
offsets of 120 degrees is a 3-phase power source. Usually, Neutral
and Earth Ground wires accompany the three Hot connections.
Loads may be configured in a delta or Y configuration. A Y-connected
load such as an AC induction motor will be a balanced load; the
currents in all the Hot connections are the same. Therefore, the
Neutral connection is theoretically zero. This is why inverters that
generate 3-phase power for motors do not generally have a Neutral
connection to the motor. However, the Earth Ground connection is
important for safety reasons, and is provided.
A8
T
orque
The rotational force exerted by a motor shaft. The units of
measurement consist of the distance (radius from shaft center axis)
and force (weight) applied at that distance. Units are usually given
as pound-feet, ounce-inches, or Newton-meters.
T
ransistor
A solid state, three-terminal device that provides amplification of
signals and can be used for switching and control. While transistors
have a linear operating range, inverters use them as high-powered
switches. Recent developments in power semiconductors have
produced transistors capable of handling high voltages and currents,
all with high reliability. The saturation voltage has been decreasing,
resulting in less heat dissipation. Hitachi inverters use
state-of-the-art semiconductors to provide high performance and
reliability in a compact package. See also
IGBT
and
Saturation
Voltage
.
T
rip Event
An event that causes the inverter to stop operation is called a “trip”
event (as in
tripping
a circuit breaker). The inverter keeps a history
log of trip events. They also require an action to clear.
W
att Loss
A measure of the internal power loss of a component, the difference
between the power it consumes and what its output delivers. An
inverter’s watt loss is the input power minus the power delivered to
the motor. The watt loss is typically highest when an inverter is
delivering its maximum output. Therefore, watt loss is usually
specified for a particular output level. Inverter watt loss
specifications are important when designing enclosures.
Bibliography
Title Author and Publisher
Variable Speed Drive Fundamentals, 2nd Ed. Phipps, Clarence A.
The Fairmont Press, Inc. / Prentice-Hall, Inc. 1997
Electronic Variable Speed Drives Brumbach, Michael E.
Delmar Publishers 1997
ISBN 0-8273-6937-9
Hitachi Inverter Technical Guide Book Published by Hitachi, Ltd. Japan 1995
Publication SIG-E002
B1
ModBus Network
Communications
In This Appendix… page
- Introduction ...................................................................................... 2
- Connecting the Inverter to ModBus ............................................... 3
- Network Protocol Reference ........................................................... 5
- ModBus Data Listing ..................................................................... 24
B
B2
Introduction
WJ200 Series inverters have built-in RS-485 serial communications, featuring the
ModBus RTU protocol. The inverters can connect directly to existing factory networks
or work with new networked applications, without any extra interface equipment. The
specifications are in the following table.
Item Specifications User-selectable
Transmission speed
2400 / 4800 / 9600 / 19.2k / 38.4k /
57.6k / 76.8k / 115.2k bps
Communication mode Asynchronous
U
Character code Binary
U
LSB placement Transmits LSB first
U
Electrical interface RS-485 differential transceiver
U
Data bits 8-bit (ModBus RTU mode)
U
Parity None / even / odd
Stop bits 1 or 2 bits
Startup convention One-way start from host device
U
Wait time for response 0 to 1000 msec.
Connections Station address numbers from 1 to 32
Connector Terminal connector
Error check
Overrun, Framing block check code,
CRC-16, or horizontal parity
Cable length 500m maximum
The network diagram below shows a series of inverters communicating with a host
computer. Each inverter must have a unique address, from 1 to 32, on the network. In
a typical application, a host computer or controller is the master and each of the
inverter(s) or other devices is a slave.
1 2 31
B3
Connecting the Inverter to ModBus
Modbus connector is in control terminal block as below. Note that RJ45 connector
(RS-422) is used for external operator only.
Terminate Network Wiring - The RS-485 wiring must be terminated at each physical
end to suppress electrical reflections and help decrease transmission errors. WJ200 has
a built-in 200
Ω resistor activated by a dip switch. Select termination resistors that match
the characteristic impedance of the network cable. The diagram above shows a network
with the needed termination resistor at each end.
PLC
P24 1 L 3 2 5 4 6
SN
7
12 11 AM CM2
OI L H O EA
SP
EO
RS-485
(Modbus)
SP SN
SP SN SP SN SP SN
External device
(Master)
+-
WJ200
(
No.2
)
WJ200
(
No.3
)
WJ200
(
No.n
)
WJ200
(
No.1
)
200Ω
RS-422
(Operator)
USB
Dip switch for termination resistor
B4
Inverter Parameter Setup - The inverter has several settings related to ModBus
communications. The table below lists them together. The
Required
column indicates
which parameters
must
be set properly to allow communications. You may need to
refer to the host computer documentation in order to match some of its settings.
Func.
Code
Name Required Settings
A001 Frequency source
00
Keypad potentiometer
01Control terminal
02Function F001 setting
03ModBus network input
10 Calculate function output
A002 Run command source
01
Control terminal
02Run key on keypad, or digital operator
03 ModBus network input
C071 Communication speed
03 2400 bps
044800 bps
05 9600 bps
06 19.2k bps
0738.4k bps
0857.6k bps
0976.8k bps
10 115.2k bps
C072 Modbus Address
Network address, range is 1 to 247
C074 Communication parity
00
No parity
01Even parity
02Odd parity
C075 Communication stop bit
Range is 1 or 2
C076 Communication error select
00
Trip (Error code E60)
01Decelerate to a stop and trip
02Disable
03Free run stop (coasting)
04Decelerate to a stop
C077 Communication error time-out
Comm. Watchdog timer period,
range is 0.00 to 99.99 sec.
C078 Communication wait time
Time the inverter waits after receiving a
message before it transmits.
Range is 0. to 1000. ms
NOTE: When you change any of the parameters above, the inverter power must be
rebooted in order to activate new parameters. Instead of rebooting, turning ON/OFF of
reset terminal works as same.
B5
Network Protocol Reference
Transmission procedure
The transmission between the external control equipment and the inverter takes the
procedure below.
Query - A frame sent from the external control equipment to the inverter
Response - A frame returned from inverter to the external control equipment
The inverter returns the response only after the inverter receives a query from the
external control equipment and does not output the response positively. Each frame is
formatted (with commands) as follows:
Frame Format
Header (silent interval)
Slave address
Function code
Data
Error check
Trailer (silent interval)
B6
Message Configuration: Query
Slave address:
This is a number of 1 to 32 assigned to each inverter (slave). (Only the inverter
having the address given as a slave address in the query can receive the query.)
When slave address “0” is specified, the query can be addressed to all inverters
simultaneously. (Broadcasting)
In broadcasting, you cannot call and loop back data.
Slave Address 1-247 in Modbus specification. When master address the slave
250-254, broadcast toward specific slave address. Slave doesn’t answer back. And
this function is valid for the write command (05h, 06h, 0Fh, 10h)
Slave address Broadcast to
250FAh
Broadcast to Slave address 01to 09
251FBh
Broadcast to Slave address 10 to 19
252FCh
Broadcast to Slave address 20 to 29
253FDh
Broadcast to Slave address 30 to 39
254FEh
Broadcast to Slave address 40 to 247
B7
Data:
A function command is set here.
The data format used in the X200
2 series is corresponding to the Modbus data
format below.
Name of Data Description
Coil Binary data that can be referenced and changed ( 1 bit long)
Holding Register 16-bit data that can be referenced and changed
Function code:
Specify a function you want to make the inverter execute. Function codes available to
the X200
2 series are listed below.
Function
Code
Function
Maximum data size
(bytes available
per message)
Maximum number of
data elements available
per message
0 1 h Read Coil Status 4 32 coils (in bits)
0 3 h Read Holding Resistor 32 16 registers (in bytes)
0 5 h Write in Coil 2 1 coil (in bits)
0 6 h Write in Holding Register 2 1 register (in bytes)
0 8 h Loopback Test
0 F h Write in Coils 4 32 coils (in bits)
1 0 h Write in Registers 32 16 registers (in bytes)
17
Read/Write Holding Registor 32 16 registers (in bytes)
Error check:
Modbus-RTU uses CRC (Cyclic Redundancy Check) for error checking.
The CRC code is 16-bit data that is generated for 8-bit blocks of arbitrary length.
The CRC code is generated by a generator polynomial CRC-16 (X16+ X15+ X2+ 1).
Header and trailer (silent interval):
Latency is the time between the reception of a query from the master and transmission
of a response from the inverter.
3.5 characters (24 bits) are always required for latency time. If the latency time
shorter than 3.5 characters, the inverter returns no response.
The actual transmission latency time is the sum of silent interval (3.5 characters
long) + C078 (transmission latency time).
B8
Message Configuration: Response
Transmission time required:
A time period between reception of a query from the master and transmission of a
response from the inverter is the sum of the silent interval (3.5 characters long) +
C078 (transmission latency time).
The master must provide a time period of the silent interval (3.5 characters long or
longer) before sending another query to an inverter after receiving a response from
the inverter.
Normal response:
When receiving a query that contains a function code of Loopback (08h), the inverter
returns a response of the same content of the query.
When receiving a query that contains a function code of Write in Register or Coil
(05h, 06h, 0Fh, or 10h), the inverter directly returns the query as a response.
When receiving a query that contains a function code of Read Register or Coil (01h
or 03h), the inverter returns, as a response, the read data together with the same
slave address and function code as those of the query.
Response when an error occurs:
When finding any error in a query (except for a transmission error), the inverter
returns an exception response without executing anything.
You can check the error by the function code in the response. The function code of
the exception response is the sum of the function code of the query and 80h.
The content of the error is known from the exception code.
Field Configuration
Slave address
Function code
Exception code
CRC-16
Exception
Code
Description
0 1 h The specified function is not supported.
0 2 h The specified function is not found.
0 3 h The format of the specified data is not acceptable.
2 1 h The data to be written in a holding register is outside the inverter.
2 2 h
The specified functions are not available to the inverter.
Function to change the content of a register that cannot be changed while
the inverter is in service
Function to submit an ENTER command during running (UV)
Function to write in a register during tripping (UV)
Function to change the I/O terminal configuration which is not allowed.
Function to change active state of RS (reset) terminal
Function to write in a register during auto-tuning
Function to write in a register locked by password
2 3h The register (or coil) to be written in is read-only
B9
No response occurs:
In the cases below, the inverter ignores a query and returns no response.
When receiving a broadcasting query
When detecting a transmission error in reception of a query
When the slave address set in the query is not equal to the slave address of the
inverter
When a time interval between data elements constituting a message is shorter than
3.5 characters
When the data length of the query is invalid
When broadcast message received.
NOTE: Provide a timer in the master and make the master retransmit the same query
when no response is made within a preset time period after the preceding query was
sent.
B10
Explanation of function codes
Read Coil Status [01h]:
This function reads the status (ON/OFF) of selected coils. An example follows below.
Read intelligent input terminals [1] to [5] of an inverter having a slave address “8.”
This example assumes the intelligent input terminals have terminal states listed
below.
Item Data
Intelligent input
terminal
[1] [2] [3] [4] [5]
Coil number 7 8 9 10 11
Coil Status ON OFF ON OFF OFF
Query: Response:
No. Field Name
Example
(Hex)
No. Field Name
Example
(Hex)
1 Slave address *1 08 1 Slave address 08
2 Function code 01 2 Function code 01
3 Coil start address *4
(high order)
00 3 Data size (in bytes) 01
4 Coil start address *4
(low order)
06 4 Coil data *3 05
5 Number of coils
(high order *2)
00 5 CRC-16 (high order) 92
6 Number of coils
(low order *2)
05 6 CRC-16 (low order) 17
7 CRC-16 (high order) 1C
8 CRC-16 (low order) 91
Note 1: Broadcasting is disabled.
Note 2: When 0 or more than 31 is specified as a number of coils, error code “03h” is
returned.
Note 3: Data is transferred by the specified number of data bytes (data size).
Note 4: The PDU Coils are addressed starting at zero. Therefore coils numbered 1-31
are addressed as 0-30. Coil address value (transmitted on Modbus line) is 1
less than the Coil Number.
The data set in the response shows terminal state of coils 0007h000Dh.
Data “05h = 00000101b” indicates the following assuming coil 7 is the LSB.
Item Data
Coil Number 14 13 12 11 10 9 8 7
Coil Status OFF OFF OFF OFF OFF ON OFF ON
When a read coil is outside the defined coils, the final coil data to be transmitted
contains “0“as the status of the coil outside the range.
When the Read Coil Status command cannot be executed normally, see the
exception response.
B11
Read Holding Register [03h]:
This function reads the contents of the specified number of consecutive holding
registers (of specified register addresses). An example follows below.
Reading Trip monitor 1 factor and trip frequency, current, and voltage from an
inverter having a slave address “1”
This example assumes the previous three trip factors are as follows:
X2002 Command D081
(factor)
D081
(frequency)
D081
(output current)
D081
(DC-bus Voltage)
Register Number 0012h 0014h 0016h 0017h
Trip factor Over-Current
(E03)
9.9Hz 3.0A 284V
Query: Response:
No. Field Name
Example
(Hex)
No. Field Name
Example
(Hex)
1 Slave address *1 01 1 Slave address 01
2 Function code 03 2 Function code 03
3 Register start address *3
(high order)
00 3 Data size (in bytes) *2 0C
4 Register start address *3
(low order)
11 4 Register data 1 (high order) 00
5 Number of holding
registers (high order)
00 5 Register data 1 (high order) 03
6 Number of holding
registers(low order)
06 6 Register data 2 (high order) 00
7 CRC-16 (high order) 95 7 Register data 2 (low order) 00
8 CRC-16 (low order) CD 8 Register data 3 (high order) 00
9 Register data 3 (low order) 63
10 Register data 4 (high order) 00
11 Register data 4 (low order) 00
12 Register data 5 (high order) 00
13 Register data 5 (low order) 1E
14 Register data 6 (high order) 01
15 Register data 6 (low order) 1C
16 CRC-16 (high order) AF
17 CRC-16 (low order) 6D
Note 1: Broadcasting is disabled.
Note 2: Data is transferred by the specified number of data bytes (data size). In this
case, 6 bytes are used to return the content of three holding registers.
Note 3: The PDU Register Number are addressed starting at zero. Therefore register
numbered “0012h” are addressed as “0011h”. Register address value
(transmitted on Modbus line) is 1 less than the Register Number.
B12
The data set in the response is as follows:
Response Buffer 4-5 6-7 8-9
Register Number 12+0 (high
order)
12+0
(low
order)
12+1
(high
order)
12+1 (low
order)
12+2
(high
order)
12+2 (low
order)
Register Data 0003h 00h 00h 0063h
Trip data Trip factor (E03) Not used Frequency (9.9Hz)
Response Buffer 10-11 12-13 14-15
Register Number 12+3 (high
order)
12+3
(low
order)
12+4
(high
order)
12+4 (low
order)
12+5
(high
order)
12+5 (low
order)
Register Data 00h 00h 001Eh 011Ch
Trip data Not used Output current (3.0A) DC-bus voltage (284V)
When the Read Holding Register command cannot be executed normally, refer to the
exception response.
Write in Coil [05h]:
This function writes data in a single coil. Coil status changes are as follows:
Data
Coil Status
OFF to ON ON to OFF
Change data (high order) FFh 00h
Change data (low order) 00h 00h
An example follows (note that to command the inverter, set A002=03):
Sending a RUN command to an inverter having slave address “8”
This example writes in coil number “1.”
Query: Response:
No. Field Name
Example
(Hex)
No. Field Name
Example
(Hex)
1 Slave address *1 08 1 Slave address 08
2 Function code 05 2 Function code 05
3 Coil start address *2
(high order)
00 3 Coil start address *2
(high order)
00
4 Coil start address *2
(low order)
00 4 Coil start address *2
(low order)
00
5 Change data
(high order)
FF 5 Change data
(high order)
FF
6 Change data
(low order)
00 6 Change data
(low order)
00
7 CRC-16 (high order) 8C 7 CRC-16 (high order) 8C
8 CRC-16 (low order) A3 8 CRC-16 (low order) A3
Note 1: No response is made for a broadcasting query.
Note 2: The PDU Coils are addressed starting at zero. Therefore coils numbered 1-31
are addressed as 0-30. Coil address value (transmitted on Modbus line) is 1
less than the Coil Number.
When writing in a selected coil fails, see the exception response.
B13
Write in Holding Register [06h]:
This function writes data in a specified holding register. An example follows:
Write “50Hz” as the first Multi-speed 0 (A020) in an inverter having slave address
“5.”
This example uses change data “500(1F4h)” to set “50Hz” as the data resolution of
the register “1029h” holding the first Multi-speed 0 (A020) is 0.1Hz
Query: Response:
No. Field Name
Example
(Hex)
No. Field Name
Example
(Hex)
1 Slave address *1 08 1 Slave address 08
2 Function code 06 2 Function code 06
3 Register start address
*2
(high order)
10 3 Register start address
*2
(high order)
10
4 Register start address
*2
(low order)
28 4 Register start address
*2
(low order)
28
5 Change data
(high order)
01 5 Change data
(high order)
01
6 Change data
(low order)
F4 6 Change data
(low order)
F4
7 CRC-16 (high order) 0D 7 CRC-16 (high order) 0D
8 CRC-16 (low order) 8C 8 CRC-16 (low order) 8C
Note 1: No response is made for a broadcasting query.
Note 2: The PDU Register Number are addressed starting at zero. Therefore register
numbered “1029h” are addressed as “1028h”. Register address value
(transmitted on Modbus line) is 1 less than the Register Number.
When writing in a selected holding register fails, see the exception response.
B14
Loopback Test [08h]:
This function checks a master-slave transmission using any test data. An example
follows:
Send test data to an inverter having slave address “1” and receiving the test data
from the inverter (as a loopback test).
Query: Response:
No. Field Name
Example
(Hex)
No. Field Name
Example
(Hex)
1 Slave address *1 01 1 Slave address *1 01
2 Function code 08 2 Function code 08
3 Test subcode
(high order)
00 3 Test subcode
(high order)
00
4 Test subcode
(low order)
00 4 Test subcode
(low order)
00
5 Data (high order) Any 5 Data (high order) Any
6 Data (low order) Any 6 Data (low order) Any
7 CRC-16 (high order) CRC 7 CRC-16 (high order) CRC
8 CRC-16 (low order) CRC 8 CRC-16 (low order) CRC
Note 1: Broadcasting is disabled.
When test subcode is for echo (00h, 00h) only and not available to the other commands.
B15
Write in Coils [0Fh]:
This function writes data in consecutive coils. An example follows:
Change the state of intelligent input terminal [1] to [5] of an inverter having a slave
address “8.”
This example assumes the intelligent input terminals have terminal states listed
below.
Item Data
Intelligent input terminal [1] [2] [3] [4] [5]
Coil Number 7 8 9 10 11
Terminal status ON ON ON OFF ON
Query: Response:
No. Field Name
Example
(Hex)
No. Field Name
Example
(Hex)
1 Slave address *1 08 1 Slave address 08
2 Function code 0F 2 Function code 0F
3 Coil start address *3
(high order)
00 3 Coil start address *3
(high order)
00
4 Coil start address *3
(low order)
06 4 Coil start address *3
(low order)
06
5 Number of coils
(high order)
00 5 Number of coils
(high order)
00
6 Number of coils
(low order)
05 6 Number of coils
(low order)
05
7 Byte number *2 02 7 CRC-16 (high order) 75
8 Change data
(high order)
17 8 CRC-16 (low order) 50
9 Change data
(low order)
00
10 CRC-16 (high order) 83
11 CRC-16 (low order) EA
Note 1: Broadcasting is disabled.
Note 2: The change data is a set of high-order data and low-order data. So when the
size (in bytes) of data to be changed is an odd start coil number (“7”), add “1”
to the data size (in bytes) to make it an even number.
Note 3: The PDU Coils are addressed starting at zero. Therefore coils numbered 1-31
are addressed as 0-30. Coil address value (transmitted on Modbus line) is 1
less than the Coil Number.
B16
Write in Holding Registers [10h]:
This function writes data in consecutive holding registers. An example follows:
Write “3000 seconds” as the first acceleration time 1 (F002) in an inverter having a
slave address “8.”
This example uses change data “300000(493E0h)” to set “3000 seconds” as the data
resolution of the registers “1014h” and “1015h” holding the first acceleration time 1
(F002) is 0.01 second.
Query: Response:
No. Field Name
Example
(Hex)
No. Field Name
Example
(Hex)
1 Slave address *1 08 1 Slave address 08
2 Function code 10 2 Function code 10
3 Start address *3
(high order)
10 3 Start address *3
(high order)
10
4 Start address *3
(low order)
13 4 Start address *3
(low order)
13
5 Number of holding
registers (high order)
00 5 Number of holding
registers (high order)
00
6 Number of holding
registers (low order)
02 6 Number of holding
registers (low order)
02
7 Byte number *2 04 7 CRC-16 (high order) B4
8 Change data 1
(high order)
00 8 CRC-16 (low order) 54
9 Change data 1
(low order)
04
10 Change data 2
(high order)
93
11 Change data 2
(low order)
E0
12 CRC-16 (high order) 7D
13 CRC-16 (low order) 53
Note 1: Broadcasting is disabled.
Note 2: This is not the number of holding registers. Specify the number of bytes of
data to be changed.
Note 3: The PDU Register Number are addressed starting at zero. Therefore register
numbered “1014h” are addressed as “1013h”. Register address value
(transmitted on Modbus line) is 1 less than the Register Number.
When writing in selected holding registers fails, see the exception response.
B17
Write in Holding Registers [17h]:
This function is to read and write data in consecutive holding registers. An example
follows:
Write “50.0Hz” as the set frequency (F001) in an inverter having a slave address “1”
and then to read out the output frequency (d001).
Query: Response:
No. Field Name
Example
(Hex)
No. Field Name
Example
(Hex)
1 Slave address *1 01 1 Slave address 01
2 Function code 17 2 Function code 17
3 Start address to read *3
(high order)
10 3 Byte number n 04
4 Start address to read *3
(low order)
00 4 Register Data 1 (high
order)
00
5 Number of holding
registers to read (high
order)
00 5 Register Data 1 (low
order)
00
6 Number of holding
registers to read (low
order)
02 6 Register Data 2 (high
order)
13
7 Start address to write
*3
(high order)
00 7 Register Data 2 (low
order)
88
8 Start address to write
*3
(low order)
00 8 CRC-16 (high order) F4
9 Number of holding
registers to write (high
order)
00 9 CRC-16 (low order) 71
10 Number of holding
registers to write (low
order)
02
11 Byte number to write*2 04
12 Change data 1
(high order)
00
13 Change data 1
(low order)
00
14 Change data 2
(high order)
13
15 Change data 2
(low order)
88
16 CRC-16 (high order) F4
17 CRC-16 (low order) 86
Note 1: Register address value (transmitted on Modbus line) is 1 less than the
Register Number.
When writing in selected holding registers fails, see the exception response.
B18
Exception Response:
When sending a query (excluding a broadcasting query) to an inverter, the master
always requests a response from the inverter. Usually, the inverter returns a response
according to the query. However, when finding an error in the query, the inverter
returns an exception response. The exception response consists of the fields shown
below.
Field Configuration
Slave address
Function code
Exception code
CRC-16
The content of each field is explained below. The function code of the exception
response is the sum of the function code of the query and 80h. The exception code
indicates the factor of the exception response.
Function Code
Query Exception Response
0 1 h 8 1 h
0 3 h 8 3 h
0 5 h 8 5 h
0 6 h 8 6 h
0 F h 8 F h
1 0 h 9 0 h
Exception Code
Code Description
0 1 h The specified function is not supported.
0 2 h The specified function is not found.
0 3 h The format of the specified data is not acceptable.
2 1 h The data to be written in a holding register is outside the inverter.
2 2 h
The specified functions are not available to the inverter.
Function to change the content of a register that cannot be changed while
the inverter is in service
Function to submit an ENTER command during running (UV)
Function to write in a register during tripping (UV)
Function to write in a read-only register (or coil)
B19
Store New Register Data (ENTER command)
After being written in a selected holding register by the Write in Holding Register
command (06h) or in selected holding registers by the Write in Holding Registers
command (10h), new data is temporary and still outside the storage element of the
inverter. If power to the inverter is shut off, this new data is lost and the previous data
returns. The ENTER command is used to store this new data in the storage element of
the inverter. Follow the instructions below to submit the ENTER command.
Submitting an ENTER Command:
Write any data in all memory (of a holding register at 0900h) by the Write in
Holding Register command [06h].
NOTE: The ENTER command takes much time to run. You can check its progress by
monitoring the Data Writing signal (of a coil at 001Ah).
NOTE: The service life of the storage element of the inverter is limited (to about
100,000 write operations). Frequent use of the ENTER command may shorten its
service life.
B20
EzCOM (Peer-to-Peer communication)
Besides standard Modbus-RTU communication (slave), WJ200 supports
Peer-to-Peer communication between multiple inverters.
The max. number of inverter in the network is up to 247 (32 without repeater).
One administrator inverter is necessary in the network, and the other inverters
behave as master or slave.
Be sure to set station No.1 as an administrator inverter, which controls master
inverter according to user setting. The others will be slave inverters. An admin.
inverter is fixed, but a master inverter always turns by rotation. For this reason, an
admin. inverter can be a master or a slave.
A master inverter is able to write data to any holding register of designated slave
inverter. The max. number of holding register is up to 5. After writing data
completed, a master inverter will be shift to the next inverter.
The max. number of master inverter is 8.
Note 1: The command to change a master is issued by an admin. inverter automatically, which
users do not have to take care.
Admin. inverter
(1)
Writing data to slaves by a
master (1).
: Master inverte
r
Inverter
(2)
Inverter
(3)
Inverter
(4)
Command to change
a master inverter. (Note 1)
Command to change
a master inverter.
Command to change
a master inverter.
Writing data to slaves by a
master (2).
Writing data to slaves by a
master (3).
Writing data to slaves by a
master (4).
B21
Note2: The command to change a master from 01 to 02 is issued after the data is sent from
master inverter 01 to slave and silent interval plus communication wait time (C078) passed.
Note 3: Administrative inverter issues the next command to change a master after the data
from master inverters is sent and silent interval plus communication wait time (C078)
passed. In case the data from master inverter cannot be received within the communication
timeout (C077), then the inverter timeouts and the behaves according to the communication
error selection.
Note 4: Please set the communication timeout as it is valid (C077=0.0199.99). If it is
disabled (C077=0.0), EzCOM function is interrupted in case the data from master inverter
was not received. In case it is interrupted, please turn on/off the power or reset (reset terminal
on/off).
B22
Func.
code
Name Data/Range For Description
C072 Modbus address 1 to 247 ALL Network address
C076
Selection of the operation after
communication error
00 ALL tripping
01
ALL tripping after decelerating
and stopping the motor
02 ALL ignoring errors
03
ALL stopping the motor after
free-running
04
ALL decelerating and stopping
the motor
C077 Communication timeout limit
0.00 ALL Disabled
0.0199.99
ALL [sec.]
C078 Communication wait time
0.1000.
ALL [ms]
C096 Communication selection
00
-
Modbus-RTU
01 B EzCOM
02 A
EzCOM
< Admin. inverter >
C098 EzCOM start adr. of master 01 to 08 A
C099 EzCOM end adr. of master 01 to 08 A
C100 EzCOM starting trigger
00 A Input terminal (Note 2)
01 A Always
P140 EzCOM the number of data 1 to 5 M
P141 EzCOM destination 1 adderss 1 to 247 M (Note 3)
P142 EzCOM destination 1 register 0000 to FFFF M
P143 EzCOM source 1 register 0000 to FFFF M
P144 EzCOM destination 2 adderss 1 to 247 M
P145 EzCOM destination 2 register 0000 to FFFF M
P146 EzCOM source 2 register 0000 to FFFF M
P147 EzCOM destination 3 adderss 1 to 247 M
P148 EzCOM destination 3 register 0000 to FFFF M
P149 EzCOM source 3 register 0000 to FFFF M
P150 EzCOM destination 4 adderss 1 to 247 M
P151 EzCOM destination 4 register 0000 to FFFF M
P152 EzCOM source 4 register 0000 to FFFF M
P153 EzCOM destination 5 adderss 1 to 247 M
P154 EzCOM destination 5 register 0000 to FFFF M
P155 EzCOM source 5 register 0000 to FFFF M
C001~
C007
Input terminal function 81 A 485: start EzCOM
Which parameters to be set?
ALL : Set all inverters in the network.
A : Set admin. inverter (address=1) only.
B : Set all inverters except admin. inverter.
M : Set master inverters configured in C098 to C099 of admin. inverter.
Note 5: Address of Administrative inverter is to be set 01 (C072=01).
Note 6: When selection of operation after communication error is set other than “ignoring errors
(C076=02)”, EzCOM function is interrupted in case of communication timeout on administrative inverter.
In this case, please power off/on or reset (on/off RES terminal) to recover.
Note 7:.If EzCOM starting trigger is set as input terminal (C100=00), be sure to configure 81 in one of
input terminals.
Note 8: If EzCOM starting trigger is set as always (C100=01), administrative inverter starts to send the
B23
data immediately after power on. In case the establishment of the inverter to be assigned as
master of delays and fail to receive the command to change the master, the data cannot be sent
from master and administrative inverter time-outs. When C100=01 selected, please be sure to
power up the administrative inverter at last after reconfirming the establishment of inverters
other than administrative inverters.
Note 9: Although slave addresses are set in a master inverter, data is sent as broadcast address (00). If a
slave inverter receives data to another slave, it will be ignored.
Note 10:As EzCOM source and destination register, please set the number minus one from the value
listed in the table in “modbus data listing”.
Note 11: Be sure to avoid to set “08FFh(EEPROM writing)” and “0901h(EEPROM
Note 12: If above parameter is changed, the inverter power must be rebooted in order to activate new
parameters. Instead of rebooting, turning ON/OFF of reset terminal works as same.
Basic function (in case the number of data is 1 (P140=1))
A master inverter sends data in holding register P143 of the master to a slave
inverter of address P141 and overwrites on holding register P142.
A master inverter is changed to the next inverter, and repeats same procedure
according to setting of new master inverter.
B24
ModBus Data Listing
ModBus Coil List
The following tables list the primary coils for the inverter interface to the network. The
table legend is given below.
Coil Number - The network
register address offset
for the coil. The coil data is a
single bit (binary) value.
Name - The functional name of the coil
R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data
Description - The meaning of each of the states of the coils
Coil
No.
Item R/W Setting
0000h unused - (Inaccessible)
0001h Operation command R/W 1: Run, 0: Stop (valid when A002 = 03)
0002h Rotation direction command R/W 1: Reverse rotation, 0: Forward rotation (valid when A002 = 03)
0003h External trip (EXT) R/W 1: Trip
0004h Trip reset (RS) R/W 1: Reset
0005h (Reserved) - -
0006h (Reserved) - -
0007h Intelligent input terminal [1] R/W 1: ON, 0: OFF (*1)
0008h Intelligent input terminal [2] R/W 1: ON, 0: OFF (*1)
0009h Intelligent input terminal [3] R/W 1: ON, 0: OFF (*1)
000Ah Intelligent input terminal [4] R/W 1: ON, 0: OFF (*1)
000Bh Intelligent input terminal [5] R/W 1: ON, 0: OFF (*1)
000Ch Intelligent input terminal [6] R/W 1: ON, 0: OFF (*1)
000Dh Intelligent input terminal [7] R/W 1: ON, 0: OFF (*1)
000Eh (Reserved) - -
000Fh Operation status R 1: Run, 0: Stop (interlocked to "d003")
0010h Rotation direction R 1: Reverse rotation, 0: Forward rotation (interlocked to "d003")
0011h Inverter ready R 1: Ready, 0: Not ready
0012h (Reserved) - -
0013h RUN (running) R 1: Tripping, 0: Normal
0014h FA1 (constant-speed reached) R 1: ON, 0: OFF
0015h FA2 (set frequency overreached) R 1: ON, 0: OFF
0016h OL (overload advance notice (1)) R 1: ON, 0: OFF
0017h
OD (output deviation for PID
control)
R 1: ON, 0: OFF
0018h AL (alarm signal) R 1: ON, 0: OFF
0019h FA3 (set frequency reached) R 1: ON, 0: OFF
001Ah OTQ (over-torque) R 1: ON, 0: OFF
001Bh (Reserved) - -
001Ch UV (undervoltage) R 1: ON, 0: OFF
001Dh TRQ (torque limited) R 1: ON, 0: OFF
001Eh RNT (operation time over) R 1: ON, 0: OFF
001Fh ONT (plug-in time over) R 1: ON, 0: OFF
0020h THM (thermal alarm signal) R 1: ON, 0: OFF
0021h (Reserved) - -
0022h (Reserved) - -
0023h (Reserved) - -
0024h (Reserved) - -
0025h (Reserved) - -
0026h BRK (brake release) R 1: ON, 0: OFF
0027h BER (brake error) R 1: ON, 0: OFF
0028h ZS (0 Hz detection signal) R 1: ON, 0: OFF
0029h DSE (speed deviation maximum) R 1: ON, 0: OFF
002Ah POK (positioning completed) R 1: ON, 0: OFF
002Bh FA4 (set frequency overreached 2) R 1: ON, 0: OFF
002Ch FA5 (set frequency reached 2) R 1: ON, 0: OFF
B25
Coil No. Item R/W Setting
002Dh OL2 (overload notice advance (2)) R 1: ON, 0: OFF
002Eh
Odc: Analog O disconnection
detection
- 1: ON, 0: OFF
002Fh
OIDc: Analog OI disconnection
detection
- 1: ON, 0: OFF
0030h (Reserved) - -
0031h (Reserved) - -
0032h FBV (PID feedback comparison) R 1: ON, 0: OFF
0033h
NDc (communication train
disconnection)
R 1: ON, 0: OFF
0034h LOG1 (logical operation result 1) R 1: ON, 0: OFF
0035h LOG2 (logical operation result 2) R 1: ON, 0: OFF
0036h LOG3 (logical operation result 3) R 1: ON, 0: OFF
0037h (Reserved) - -
0038h (Reserved) - -
0039h (Reserved) - -
003Ah WAC (capacitor life warning) R 1: ON, 0: OFF
003Bh WAF (cooling-fan speed drop) R 1: ON, 0: OFF
003Ch FR (starting contact signal) R 1: ON, 0: OFF
003Dh OHF (heat sink overheat warning) R 1: ON, 0: OFF
003Eh LOC (low-current indication signal) R 1: ON, 0: OFF
003Fh M01 (general output 1) R 1: ON, 0: OFF
0040h M02 (general output 2) R 1: ON, 0: OFF
0041h M03 (general output 3) R 1: ON, 0: OFF
0042h (Reserved) - -
0043h (Reserved) - -
0044h (Reserved) - -
0045h IRDY (inverter ready) R 1: ON, 0: OFF
0046h FWR (forward rotation) R 1: ON, 0: OFF
0047h RVR (reverse rotation) R 1: ON, 0: OFF
0048h MJA (major failure) R 1: ON, 0: OFF
0049h Data writing in progress R 1: Writing in progress, 0: Normal status
004Ah CRC error R 1: Error detected, 0: No error (*2)
004Bh Overrun R 1: Error detected, 0: No error (*2)
004Ch Framing error R 1: Error detected, 0: No error (*2)
004Dh Parity error R 1: Error detected, 0: No error (*2)
004Eh Sum check error R 1: Error detected, 0: No error (*2)
004Fh (Reserved) - -
0050h WCO (window comparator O) R 1: ON, 0: OFF
0051h WCOI (window comparator OI) R 1: ON, 0: OFF
0052h (Reserved) - -
0053h OPDc (option disconnection) R 1: ON, 0: OFF
0054h FREF (FQ command source) R 1: Operator, 0: Others
0055h REF (RUN command source) R 1: Operator, 0: Others
0056h SETM (2nd motor selected) R 1: 2nd motor selected, 0: 1st motor selected
0057h (Reserved) - -
0058h EDM (Gate suppress monitor) R 1: ON, 0: OFF
0059h- unused R inaccessible
*1 Normally, this coil is turned on when the corresponding intelligent input terminal on the control
circuit terminal block is turned on or the coil itself is set to on. In this regard, the operation of
the intelligent input terminal has priority over the operation of the coil. If disconnection of the
communication train has disabled the master system from turning off the coil, turn the
corresponding intelligent input terminal on the control circuit block on and off. This operation
turns off the coil.
*2 Communication error data is retained until an error reset command is input. (The data can be
reset during the inverter operation.)
B26
ModBus Holding Registers
The following tables list the holding registers for the inverter interface to the network.
The table legend is given below.
Function Code - The inverter’s reference code for the parameter or function (same as
inverter keypad display)
Name - The standard functional name of the parameter or function for the inverter
R/W - The read-only(R) or read-write access(R/W) permitted to the data in the
inverter
Description - How the parameter or setting works (same as Chapter 3 description).
Reg. - The network
register address offset
for the value. Some values have a
high-byte and low-byte address.
Range - The numerical range for the network value that is sent and/or received
TIP: The network values are binary integers. Since these values cannot have an
embedded decimal point, for many parameters it represents the actual value (in
engineering units) multiplied by a factor of 10 or 100. Network communications must
use the listed range for network data. The inverter automatically divides received
values by the appropriate factor in order to establish the decimal point for internal use.
Likewise, the network host computer must apply the same factor when it needs to work
in engineering units. However, when sending data to the inverter, the network host
computer must scale values to the integer range listed for network communications.
Resolution - This is the quantity represented by the LSB of the network value, in
engineering units. When the network data range is greater than the inverter’s
internal data range, this 1-bit resolution will be fractional.
Register No. Function name Function code R/W Monitoring and setting items
Data
resolution
0000h unused - - Inaccessible
0001h
Frequency source
F001 (high) R/W 0 to 40000 (valid when A001 = 03)
0.01 [Hz]
0002h F001 (low) R/W
0003h Inverter status A - R
0: Initial status
2: Stopping
3: Running
4: Free-run stop
5: Jogging
6: DC braking
7: Retrying
8: Tripping
9: Undervoltage
(UV),
-
0004h Inverter status B - R 0: Stopping, 1: Running, 2: Tripping -
0005h Inverter status C - R
0: ---
1: Stopping
2: Decelerating
3: Constant-speed
operation
4: Accelerating
5: Forward rotation
6: Reverse rotation
7: Switching from
fwd.
to rev. rotation,
8: Switching from
rev.
to fwd. rotation,
9: Starting fwd.
10: Starting rev.
-
0006h PID feedback - R/W 0 to 10000 0.01 [%]
0007h
to
0010h
(Reserved) - R - -
B27
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
0011h Trip Counter d080 R 0 to 65530 1 [time]
0012h Trip info. 1 (factor)
d081 R
See the list of inverter trip factors below -
0013h Trip info. 1 (inverter status) See the list of inverter trip factors below -
0014h Trip info. 1 (frequency) (high)
0 to 100000 0.01[Hz]
0015h Trip info. 1 (frequency (low)
0016h Trip info. 1 (current) Output current at tripping 0.01[A]
0017h Trip info. 1 (voltage) DC input voltage at tripping 1[V]
0018h Trip info. 1 (running time) (high)
Cumulative running time at tripping 1[h]
0019h Trip info. 1 (running time) (low)
001Ah Trip info. 1 (power-on time) (high)
Cumulative power-on time at tripping 1[h]
001Bh Trip info. 1 (power-on time) (low)
001Ch Trip info. 2 (factor)
d082 R
See the list of inverter trip factors below -
001Dh Trip info. 2 (inverter status) See the list of inverter trip factors below -
001Eh Trip info. 2 (frequency) (high)
0 to 100000 0.01[Hz]
001Fh Trip info. 2 (frequency (low)
0020h Trip info. 2 (current) Output current at tripping 0.01[A]
0021h Trip info. 2 (voltage) DC input voltage at tripping 1[V]
0022h Trip info. 2 (running time) (high)
Cumulative running time at tripping 1[h]
0023h Trip info. 2 (running time) (low)
0024h Trip info. 2 (power-on time) (high)
Cumulative power-on time at tripping 1[h]
0025h Trip info. 2 (power-on time) (low)
0026h Trip info. 3 (factor)
d083 R
See the list of inverter trip factors below -
0027h Trip info. 3 (inverter status) See the list of inverter trip factors below -
0028h Trip info. 3 (frequency) (high)
0 to 100000 0.01[Hz]
0029h Trip info. 3 (frequency (low)
002Ah Trip info. 3 (current) Output current at tripping 0.01[A]
002Bh Trip info. 3 (voltage) DC input voltage at tripping 1[V]
002Ch Trip info. 3 (running time) (high)
Cumulative running time at tripping 1[h]
002Dh Trip info. 3 (running time) (low)
002Eh Trip info. 3 (power-on time) (high)
Cumulative power-on time at tripping 1[h]
002Fh Trip info. 3 (power-on time) (low)
0030h Trip info. 4 (factor)
d084 R
See the list of inverter trip factors below -
0031h Trip info. 4 (inverter status) See the list of inverter trip factors below -
0032h Trip info. 4 (frequency) (high)
0 to 100000 0.01[Hz]
0033h Trip info. 4 (frequency (low)
0034h Trip info. 4 (current) Output current at tripping 0.01[A]
0035h Trip info. 4 (voltage) DC input voltage at tripping 1[V]
0036h Trip info. 4 (running time) (high)
Cumulative running time at tripping 1[h]
0037h Trip info. 4 (running time) (low)
0038h Trip info. 4 (power-on time) (high)
Cumulative power-on time at tripping 1[h]
0039h Trip info. 4 (power-on time) (low)
003Ah Trip info. 5 (factor)
d085 R
See the list of inverter trip factors below -
003Bh Trip info. 5 (inverter status) See the list of inverter trip factors below -
003Ch Trip info. 5 (frequency) (high)
0 to 100000 0.01[Hz]
003Dh Trip info. 5 (frequency (low)
003Eh Trip info. 5 (current) Output current at tripping 0.01[A]
003Fh Trip info. 5 (voltage) DC input voltage at tripping 1[V]
0040h Trip info. 5 (running time) (high)
Cumulative running time at tripping 1[h]
0041h Trip info. 5 (running time) (low)
0042h Trip info. 5 (power-on time) (high)
Cumulative power-on time at tripping 1[h]
0043h Trip info. 5 (power-on time) (low)
0044h Trip info. 6 (factor)
d086 R
See the list of inverter trip factors below -
0045h Trip info. 6 (inverter status) See the list of inverter trip factors below -
0046h Trip info. 6 (frequency) (high)
0 to 100000 0.01[Hz]
0047h Trip info. 6 (frequency (low)
0048h Trip info. 6 (current) Output current at tripping 0.01[A]
0049h Trip info. 6 (voltage) DC input voltage at tripping 1[V]
004Ah Trip info. 6 (running time) (high)
Cumulative running time at tripping 1[h]
004Bh Trip info. 6 (running time) (low)
004Ch Trip info. 6 (power-on time) (high)
Cumulative power-on time at tripping 1[h]
004Dh Trip info. 6 (power-on time) (low)
B28
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
004Eh Programming error monitoring d090 R Warning code -
004Fh to
006Ch
(reserved) - - - -
006Dh to
08Efh
(reserved) - - - -
0900h Writing to EEPROM - W
0: Motor constant recalculation
1: Save all data in EEPROM
Other: Motor constant recalculation and
save all data in EEPROM
-
0901h Unused - - Inaccessible -
0902h EEPROM write mode - W 0 (invalid) / 1 (valid)
0903h to
1000h
Unused - - Inaccessible -
Note 1: Assume that the rated current of the inverter is "1000".
Note 2: If a number not less than "1000" (100.0 seconds) is specified, the second value after the
decimal point will be ignored.
Note 3: 0902h setting is referred for one time when following 06H command is executed.
B29
List of inverter trip factors
Upper part of trip factor code
(indicating the factor)
Lower part of trip factor code
(indicating the inverter status)
Name Code Name Code
No trip factor 0 Resetting 0
Over-current event while at constant speed
1 Stopping 1
Over-current event during deceleration
2 Decelerating 2
Over-current event during acceleration 3 Constant-speed operation 3
Over-current event during other conditions 4 Accelerating 4
Overload protection 5 Operating at zero frequency 5
Braking resistor overload protection 6 Starting 6
Overvoltage protection 7 DC braking 7
EEPROM error 8 Overload restricted 8
Undervoltage protection 9
Current detection error 10
CPU error 11
External trip 12
USP error 13
Ground-fault protection 14
Input overvoltage protection 15
Inverter thermal trip 21
CPU error 22
Main circuit error 25
Driver error 30
Thermistor error 35
Braking error 36
Safe Stop 37
Low-speed overload protection 38
Operator connection 40
Modbus communication error 41
Easy sequence error (invalid instruction) 43
Easy sequence error (invalid nesting count) 44
Easy sequence execution error 1 45
Easy sequence user trip 0 to 9 50 to 59
Option error 0 to 9 60 to 69
Encoder disconnection 80
Excessive speed 81
Position control range trip 83
B30
(iii) List of registers (monitoring)
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1001h
Output frequency monitor
d001 (high)
R 0 to 40000(100000) 0.01 [Hz]
1002h d001 (low)
1003h Output current monitor d002 R 0 to 65530 0.1 [A]
1004h Rotation direction minitoring d003 R
0: Stopping, 1: Forward rotation, 2:
Reverse rotation
0.1 [Hz]
1005h
Process variable (PV), PID
feedback monitoring
d004 (high)
R 0 to 1000000 0.1
1006h d004 (low)
1007h Intelligent input terminal status d005 R 2^0: Terminal 1 to 2^6: Terminal 7 1 bit
1008h Intelligent output terminal status d006 R
2^0: Terminal 11 to 2^1: Terminal 12/
2^2: Relay Terminal
1 bit
1009h
Scaled output frequency monitor
d007 (high)
R 0 to 4000000(10000000) 0.01
100Ah d007 (low)
100Bh
Actual-frequency monitor
d008 (high) R
-100000 to +100000 0.01 [Hz]
100Ch d008 (low) R
100Dh Torque command monitor d009 R -200 to +200 1 [%]
100Eh Torque bias monitor d010 R -200 to +200 1 [%]
100Fh (Reserved) - - - -
1010h Torque monitor d012 R -200 to +200 1 [%]
1011h Output voltage monitor d013 R 0 to 6000 0.1 [V]
1012h Power monitor d014 R 0 to 1000 0.1 [kW]
1013h
Watt-hour monitor
d015 (high)
R 0 to 9999000 0.1
1014h d015 (low)
1015h
Elapsed RUN time monitor
d016 (high)
R 0 to 999900 1 [h]
1016h d016 (low)
1017h
Elapsed power-on time monitor
d017 (high)
R 0 to 999900 1 [h]
1018h d017 (low)
1019h Heat sink temperature monitor d018 R -200 to 1500 0.1 []
101Ah to
(Reserved) - - - -
101Ch
101Dh Life-check monitor d022 R
2^0: Capacitor on main circuit board
2^1: cooling-fan
1 bit
101Eh
EzSQ program counter
d023
R
01024
101Fh
EzSQ program number
d024
R
09999
1020h
1025h
(Reserved) - - - -
1026h
DC voltage monitoring
(across P and N)
d102 R 0 to 10000 0.1 [V]
1027h BRD load factor monitoring d103 R 0 to 1000 0.1 [%]
1028h
Electronic thermal overload
monitoring
d104 R 0 to 1000 0.1 [%]
1029h to
102Dh
(Reserved) - - - -
102Eh
User monitor 1
d025(HIGH) R
-2147483647 to 2147483647 1
102Fh d025(LOW) R
1030h
User monitor 2
d026(HIGH) R
-2147483647 to 2147483647 1
1031h d026(LOW) R
1032h
User monitor 3
d027(HIGH) R
-2147483647 to 2147483647 1
1033h d027(LOW) R
1034h to
1035h
(Reserved) - - - -
1036h
Position setting monitor
d029(HIGH) R
-268435455 to 268435455 1
1037h d029(LOW) R
1038h
Position feedback monitor
d030(HIGH) R
-268435455 to 268435455 1
1039h d030(LOW) R
103Ah to
1056h
(reserved) - - - -
1057h Inverter mode monitor d060 R
0(IM CT)
1(IM VT)
2(IM High Freq
mode)
1058h to
1102h
unused - - Inaccessible -
B31
(iv) List of registers
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1103h
Acceleration time (1)
F002 (high)
R/W 1 to 360000 0.01 [sec.]
1104h F002 (low)
1105h
Deceleration time (1)
F003 (high)
R/W 1 to 360000 0.01 [sec.]
1106h F003 (low)
1107h Keypad Run key routing F004 R/W 0 (forward rotation), 1 (reverse rotation) -
1108h to
1200h
Unused - - Inaccessible -
(v) List of registers (function modes)
Parameter group A
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1201h Frequency source A001 R/W
0 (keypad potentiometer), 1 (control circuit
terminal block), 2 (digital operator), 3
(Modbus), 4 (option ), 6 (pulse train input), 7
(easy sequence), 10 (operation function result)
-
1202h Run command source (*) A002 R/W
1 (control circuit terminal block), 2 (digital
operator), 3 (Modbus), 4 (option)
-
1203h Base frequency A003 R/W 300 to "maximum frequency" 0.1 [Hz]
1204h Maximum frequency A004 R/W 300 to 4000(10000) 0.1 [Hz]
1205h [AT] selection A005 R/W
0 (switching between O and OI terminals),
2 (switching between O terminal and keypad
potentiometer),
3 (switching between OI terminal and keypad
potentiometer)
-
1206h to
120Ah
(Reserved) - - - -
120Bh
[O] input active range
start frequency
A011 (high)
R/W 0 to 40000(100000) 0.01 [Hz]
120Ch A011 (low)
120Dh
[O] input active range end
frequency
A012 (high)
R/W 0 to 40000(100000) 0.01 [Hz]
120Eh A012 (low)
120Fh
[O] input active range
start voltage
A013 R/W 0 to "[O]-[L] input active range end voltage" 1 [%]
1210h
[O] input active range end
voltage
A014 R/W "[O]-[L] input active range start voltage" to 100 1 [%]
1211h
[O] input start frequency
select
A015 R/W 0 (external start frequency), 1 (0 Hz) -
1212h Analog input filter. A016 R/W
1 to 30 or 31 (500 ms filter ±0.1 Hz with
hysteresis)
1
1213h EzSQ selection A017 R/W 0 (disabling), 1 (PRG terminal) , 2 (Always) -
1214h (Reserved) - - - -
1215h
Multi speed operation
selection
A019 R/W 0 (binary), 1 (bit) -
1216h
Multi-speed freq. 0
A020 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1217h A020 (low) R/W
1218h
Multi-speed freq. 1
A021 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1219h A021 (low) R/W
121Ah
Multi-speed freq. 2
A022 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
121Bh A022 (low) R/W
121Ch
Multi-speed freq. 3
A023 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
121Dh A023 (low) R/W
121Eh
Multi-speed freq. 4
A024 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
121Fh A024 (low) R/W
1220h
Multi-speed freq. 5
A025 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1221h A025 (low) R/W
1222h
Multi-speed freq. 6
A026 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1223h A026 (low) R/W
1224h
Multi-speed freq. 7
A027 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1225h A027 (low) R/W
After changing the setting, keep the time 40ms or longer before actually give run command
B32
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1226h
Multi-speed freq. 8
A028 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1227h A028 (low) R/W
1228h
Multi-speed freq. 9
A029 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1229h A029 (low) R/W
122Ah
Multi-speed freq. 10
A030 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
122Bh A030 (low) R/W
122Ch
Multi-speed freq. 11
A031 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
122Dh A031 (low) R/W
122Eh
Multi-speed freq. 12
A032 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
122Fh A032 (low) R/W
1230h
Multi-speed freq. 13
A033 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1231h A033 (low) R/W
1232h
Multi-speed freq. 14
A034 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1233h A034 (low) R/W
1234h
Multi-speed freq. 15
A035 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1235h A035 (low) R/W
1236h (Reserved) - - - -
1237h (Reserved) - - - -
1238h Jog frequency A038 R/W 0.0, "Start frequency" to 999(10000) 0.01 [Hz]
1239h Jog stop mode A039 R/W
0 (free-running after jogging stops [disabled
during operation])
1 (deceleration and stop after jogging stops
[disabled during operation])
2 (DC braking after jogging stops [disabled
during operation])
3 (free-running after jogging stops [enabled
during operation])
4 (deceleration and stop after jogging stops
[enabled during operation])
5 (DC braking after jogging stops [enabled
during operation])
-
123Ah (Reserved) - - - -
123Bh
Torque boost method
selection
A041 R/W
0 (manual torque boost), 1 (automatic torque
boost)
-
123Ch Manual torque boost value A042 R/W 0 to 200 0.1 [%]
123Dh
Manual torque boost
frequency
A043 R/W 0 to 500 0.1 [%]
123Eh
V/F characteristic curve
selection, 1st motor
A044 R/W
0 (VC), 1 (VP), 2 (free V/f), 3 (sensorless
vector control),
-
123Fh V/f gain A045 R/W 20 to 100 1 [%]
1240h
Voltage compensation gain
setting for automatic torque
boost, 1st motor
A046 R/W 0 to 255 1 [%]
1241h
Slippage compensation gain
setting for automatic torque
boost, 1st motor
A047 R/W 0 to 255 1 [%]
1242h
to1244h
(Reserved) - - - -
1245h DC braking enable A051 R/W
0 (disabling), 1 (enabling), 2 (output freq <
[A052])
-
1246h DC braking frequency A052 R/W 0 to 6000 0.01 [Hz]
1247h DC braking wait time A053 R/W 0 to 50 0.1 [sec.]
1248h
DC braking force during
deceleration
A054 R/W 0 to 100 1 [%]
1249h
DC braking time for
deceleration
A055 R/W 0 to 600 0.1 [sec.]
124Ah
DC braking/edge or level
detection for [DB] input
A056 R/W 0 (edge operation), 1 (level operation) -
124Bh DC braking force for starting A057 R/W 0 to 100 1 [%]
124Ch DC braking time for starting A058 R/W 0 to 600 0.1 [sec.]
124Dh
DC braking carrier frequency
setting
A059 R/W 20 to 150 0.1 [kHz]
124Eh (Reserved) - - - -
B33
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
124Fh
Frequency upper limit
A061 (high) R/W
0 or "maximum frequency limit" to
"maximum frequency"
0.01 [Hz]
1250h A061 (low) R/W
1251h
Frequency lower limit
A062 (high) R/W
0 or "maximum frequency limit" to
"maximum frequency"
0.01 [Hz]
1252h A062 (low) R/W
1253h
Jump freq. (center) 1
A063 (high) R/W
0 to 40000(100000) 0.01 [Hz]
1254h A063 (low) R/W
1255h
Jump freq. width
(hysteresis) 1
A064 R/W 0 to 1000(10000) 0.01 [Hz]
1256h
Jump freq. (center) 2
A065 (high) R/W
0 to 40000(100000) 0.01 [Hz]
1257h A065 (low) R/W
1258h
Jump freq. width
(hysteresis) 2
A066 R/W 0 to 1000(10000) 0.01 [Hz]
1259h
Jump freq. (center) 3
A067 (high) R/W
0 to 40000(100000) 0.01 [Hz]
125Ah A067 (low) R/W
125Bh
Jump freq. width
(hysteresis) 3
A068 R/W 0 to 1000(10000) 0.01 [Hz]
125Ch
Acceleration hold frequency
A069 (high) R/W
0 to 40000 0.01 [Hz]
125Dh A069 (low) R/W
125Eh Acceleration hold time A070 R/W 0 to 600 0.1 [sec.]
125Fh PID Function Enable A071 R/W
0 (disabling), 1 (enabling), 2 (enabling
inverted-data output)
-
1260h PID proportional gain A072 R/W 0 to 2500 0.10
1261h PID integral time constant A073 R/W 0 to 36000 0.1 [sec.]
1262h PID derivative gain A074 R/W 0 to 10000 0.01 [sec.]
1263h PV scale conversion A075 R/W 1 to 9999 0.01
1264h PV source A076 R/W
0 (input via OI), 1 (input via O), 2 (external
communication), 3 (pulse train frequency
input), 10 (operation result output)
-
1265h Reverse PID A077 R/W 00 (disabling), 01 (enabling) -
1266h PID output limite
r
A078 R/W 0 to 1000 0.1 [%]
1267h PID feed forward selection A079 R/W 0 (disabled), 1(O input), 2 (OI input) -
1268h (Reserved) - R/W - -
1269h AVR function select A081 R/W
0 (always on), 1 (always off), 2 (off during
deceleration)
-
126Ah AVR voltage select A082 R/W
200 V class: 0 (200)/1 (215)/2 (220)/3
(230)/4 (240)
400 V class: 5 (380)/6 (400)/7 (415)/8
(440)/9 (460)/ 10 (480)
-
126Bh AVR filter time constant A083
R/W
0.000 to 10.00 0.001[sec]
126Ch AVR deceleration gain A084
R/W
50 to 200 1[%]
126Dh
Energy-saving operation
mode
A085 R/W
0 (normal operation), 1 (energy-saving
operation)
-
126Eh Energy-saving mode tuning A086 R/W 0 to 1000 0.1 [%]
B34
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
126Fh to
1273h
(Reserved) - - -
1274h
Acceleration time (2)
A092 (high) R/W
1 to 360000 0.01 [sec.]
1275h A092 (low) R/W
1276h
Deceleration time (2)
A093 (high) R/W
1 to 360000 0.01 [sec.]
1277h A093 (low) R/W
1278h
Select method to switch to
Acc2/Dec2 profile
A094 R/W
0 (switching by 2CH terminal), 1 (switching by
setting)
2 (Forward and reverse)
-
1279h
Acc1 to Acc2 frequency
transition point
A095 (high) R/W
0 to 40000(100000) 0.01 [Hz]
127Ah A095 (low) R/W
127Bh
Dec1 to Dec2 frequency
transition point
A096 (high) R/W
0 to 40000(100000) 0.01 [Hz]
127Ch A096 (low) R/W
127Dh
Acceleration curve
selection
A097 R/W
0 (linear), 1 (S curve), 2 (U curve), 3
(inverted-U curve), 4 (EL-S curve)
-
127Eh Deceleration curve setting A098 R/W
0 (linear), 1 (S curve), 2 (U curve), 3
(inverted-U curve), 4 (EL-S curve)
-
127Fh (Reserved) - - - -
1280h (Reserved) - - - -
1281h
[OI] input active range start
frequency
A101 (high) R/W
0 to 40000(100000) 0.01 [Hz]
1282h A101 (low) R/W
1283h
[OI] input active range end
frequency
A102 (high) R/W
0 to 40000(100000) 0.01 [Hz]
1284h A102 (low) R/W
1285h
[OI] input active range start
current
A103 R/W 0 to "[OI]-[L] input active range end current" 1 [%]
1286h
[OI] input active range end
current
A104 R/W
"[OI]-[L] input active range start current" to
100
1 [%]
1287h
[OI] input start frequency
select
A105 R/W 0 (external start frequency), 1 (0 Hz) -
1288h to
12A4h
(Reserved) - - - -
12A5h Acceleration curve constant A131 R/W 1 (smallest swelling) to 10 (largest swelling) -
12A6h
Deceleration curve
constant
A132 R/W 1 (smallest swelling) to 10 (largest swelling) -
12A7h to
12AEh
(Reserved) - - - -
12AFh
Operation-target frequency
selection 1
A141 R/W
0 (digital operator), 1 (keypad potentiometer),
2 (input via O), 3 (input via OI), 4 (external
communication), 5 (option ), 7 (pulse train
frequency input)
-
B35
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
12B0h
Operation-target frequency
selection 2
A142 R/W
0 (digital operator), 1 (keypad potentiometer),
2 (input via O), 3 (input via OI), 4 (external
communication), 5 (option ), 7 (pulse train
frequency input)
-
12B1h Operator selection A143 R/W
0 (addition: A141 + A142), 1 (subtraction:
A141 - A142), 2 (multiplication: A141 x A142)
-
12B2h (Reserved) - - - -
12B3h
Frequency to be added
A145 (high) R/W
0 to 40000(100000) 0.01 [Hz]
12B4h A145 (low) R/W
12B5h
Sign of the frequency to be
added
A146 R/W
00 (frequency command + A145), 01
(frequency command - A145)
-
12B6h to
12B8h
(Reserved) - - - -
12B9h
EL-S-curve
acceleration/deceleration
ratio 1
A150 R/W 0 to 50 1 [%]
12BAh
EL-S-curve
acceleration/deceleration
ratio 2
A151 R/W 0 to 50 1 [%]
12BBh
EL-S-curve
deceleration/deceleration
ratio 1
A152 R/W 0 to 50 1 [%]
12BCh
EL-S-curve
deceleration/deceleration
ratio 2
A153 R/W 0 to 50 1 [%]
12BDh
Deceleration hold
frequency
A154 (high)
R/W 040000(100000) 0.01 [Hz]
12BEh A154 (low)
12BFh Deceleration hold time A155 R/W 0600 0.1 [sec.]
12C0h
PID sleep function
triggering level
A156 (high)
R/W 040000(100000) 0.01 [Hz]
12C1h A156 (low)
12C2h
PID sleep function action
delay time
A157 R/W 0255 0.1 [sec.]
12C3h to
12C5h
(Reserved) - - - -
12C6h
[VR] input active range start
frequency
A161 (high)
R/W 040000(100000) 0.01 [Hz]
12C7h A161 (low)
12C8h
[VR] input active range end
frequency
A162 (high)
R/W 040000(100000) 0.01 [Hz]
12C9h A162 (low)
12CAh
[VR] input active range
start %
A163 R/W 0100 1 [%]
12CBh
[VR] input active range
end %
A164 R/W 0100 1 [%]
12CCh
[VR] input start frequency
select
A165 R/W 0(start frequency A161) / 1(0Hz) -
12CDh to
1300h
unused - - Inaccessible -
B36
Parameter group B
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1301h
Restart mode on power
failure / under-voltage trip
b001 R/W
0 (tripping), 1 (starting with 0 Hz), 2 (starting
with matching frequency), 3 (tripping after
deceleration and stopping with matching
frequency), 4 (restarting with active matching
frequency)
-
1302h
Allowable unde
r
-voltage
power failure time
b002 R/W 3 to 250 0.1 [sec.]
1303h
Retry wait time before
motor restart
b003 R/W 3 to 1000 0.1 [sec.]
1304h
Instantaneous power
failure/under-voltage trip
alarm enable
b004 R/W
0 (disabling), 1 (enabling), 2 (disabling during
stopping and decelerating to stop)
-
1305h
Number of restarts on
power failure/under-voltage
trip events
b005 R/W 0 (16 times), 1 (unlimited) -
1306h
(Reserved) - - -
-
1307h
Restart frequency threshold
b007 (high) R/W
0 to 40000
0.01 [Hz]
1308h b007 (low) R/W
1309h
Restart mode on over
voltage / over current
b008 R/W
0 (tripping), 1 (starting with 0 Hz), 2 (starting
with matching frequency), 3 (tripping after
deceleration and stopping with matching
frequency), 4 (restarting with active matching
frequency)
-
130Ah
(Reserved) - - -
-
130Bh
Number of retry on over
voltage / over current
b010 R/W 1 to 3 1 [time]
130Ch
Retry wait time on over
voltage / over current
b011 R/W 3 to 1000 0.1 [sec.]
130Dh Level of electronic thermal b012 R/W 200 to 1000 0.1 [%]
130Eh
Electronic thermal
characteristic
b013 R/W
0 (reduced-torque characteristic), 1
(constant-torque characteristic), 2 (free
setting)
-
130Fh (Reserved) - - Inaccessible -
1310h
Free setting, electronic
thermal frequency (1)
b015 R/W 0 to 400 1 [Hz]
1311h
Free setting, electronic
thermal current (1)
b016 R/W 0 to Rated current 0.1 [A]
1312h
Free setting, electronic
thermal frequency (2)
b017 R/W 0 to 400 1 [Hz]
1313h
Free setting, electronic
thermal current (2)
b018 R/W 0 to Rated current 0.1 [A]
1314h
Free setting, electronic
thermal frequency (3)
b019 R/W 0 to 400 1 [Hz]
1315h
Free setting, electronic
thermal current (3)
b020 R/W 0 to Rated current 0.1 [A]
1316h
Overload restriction
operation mode
b021 R/W
0 (disabling), 1 (enabling during acceleration
and constant-speed operation), 2 (enabling
during constant-speed operation), 3 (enabling
during acceleration and constant-speed
operation [speed increase at regeneration])
-
1317h Overload restriction level b022 R/W 200 to 2000 0.1 [%]
1318h
Deceleration rate at
overload restriction
b023 R/W 1 to 30000 0.1 [sec.]
1319h
Overload restriction
operation mode (2)
b024 R/W
0 (disabling), 1 (enabling during acceleration
and constant-speed operation), 2 (enabling
during constant-speed operation), 3 (enabling
during acceleration and constant-speed
operation [speed increase at regeneration])
-
131Ah Overload restriction level 2 b025 R/W 200 to 2000 0.1 [%]
131Bh
Deceleration rate at
overload restriction (2)
b026 R/W 1 to 30000 0.1 [sec.]
131Ch
Overcurrent suppression
enable
b027 R/W 0 (disabling), 1 (enabling) -
131Dh
Current level of active freq.
matching
b028 R/W 100 to 2000 0.1 [%]
131Eh
Deceleration rate of active
freq. matching
b029 R/W 1 to 30000 0.1 [sec.]
B37
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
131Fh
Start freq. of active
frequency matching
b030 R/W
0 (frequency at the last shutoff), 1 (maximum
frequency), 2 (set frequency)
-
1320h
Software lock mode
selection
b031 R/W
0 (disabling change of data other than "b031"
when SFT is on), 1 (disabling change of data
other than "b031" and frequency settings
when SFT is on), 2 (disabling change of data
other than "b031"), 3 (disabling change of data
other than "b031" and frequency settings), 10
(enabling data changes during operation)
-
1321h (Reserved) - - - -
1322h
Motor cable length
parameter
b033
R/W
5 to 20 -
1323h
Run/power-on warning time
b034 (high) R/W
0 to 65535 1 [10h]
1324h b034 (low) R/W
1325h
Rotation direction
restriction
b035 R/W
0( Enable for both dir)/ 1 (Enable for
forward only)/ 2 (Enable for reverse only)
-
1326h
Reduced voltage start
selection
b036 R/W
0 (minimum reduced voltage start time) to 255
(maximum reduced voltage start time)
-
1327h
Function code display
restriction
b037 R/W
0 (full display), 1 (function-specific display), 2
(user setting), 3 (data comparison display), 4
(basicdisplay), 5(monitor display)
-
1328h Initial displa
y
selection b038 R/W 001-060 -
1329h
Automatic use
r
parameter
registration
b039 R/W 0 (disabling), 1 (enabling) -
132Ah Torque limit selection b040 R/W
00 (quadrant-specific setting), 01 (switching by
terminal), 02 (analog input)
-
132Bh
Torque limit 1 (fwd-powe
r
in
4-quadrant mode)
b041 R/W 0 to 200/255 (no) 1 [%]
132Ch
Torque limit 2 (rev
/r
egen. in
4-quadrant mode)
b042 R/W 0 to 200/255 (no) 1 [%]
132Dh
Torque limit 3 (rev
/
powe
r
in
4-quadrant mode)
b043 R/W 0 to 200/255 (no) 1 [%]
132Eh
Torque limit 4 (fwd/regen. in
4-quadrant mode)
b044 R/W 0 to 200/255 (no) 1 [%]
132Fh
Torque limit LADSTOP
enable
b045 R/W 0 (disabling), 1 (enabling) -
1330h
Reverse Run protection
enable
b046 R/W 0 (disabling), 1 (enabling) -
1331h to
1332h
(Reserved) - - - -
1333h Dual Rating Selection b049 R/W 0(CT mode)/1(VT mode)
-
1334h
Controlled deceleration on
power loss
b050 R/W
0 (disabling), 1 (enabling), 2, (nonstop
operation at momentary power failure (no
restoration))
3, (nonstop operation at momentary power
failure (restoration to be done))
-
1335h
DC bus voltage trigger level
of ctrl. decel.
b051 R/W 0 to 10000 0.1 [V]
1336h
Ove
r
-voltage threshold of
ctrl. decel.
b052 R/W 0 to 10000 0.1 [V]
1337h
Deceleration time of ctrl.
decel.
b053 (high) R/W
0.01 to 36000
0.01
[sec.]
1338h b053 (low) R/W
1339h
Initial freq. drop of ctrl.
decel.
b054 R/W 0 to 1000 0.01 [Hz]
133Ah to
133Eh
(Reserved) - - - -
133Fh
Maximum-limit level of
window comparators O
b060 R/W
0. to 100. (lower limit : b061 + b062 *2) (%)
1 [%]
1340h
Minimum-limit level of
window comparators O
b061 R/W
0. to 100. (lower limit : b060 - b062*2) (%)
1 [%]
1341h
Hysteresis width of window
comparators O
b062 R/W
0. to 10. (lower limit : b061 - b062 / 2) (%)
1 [%]
1342h
Maximum-limit level of
window comparators OI
b063 R/W
0. to 100. (lower limit : b064 + b066 *2) (%)
1 [%]
1343h
Minimum-limit level of
window comparators OI
b064 R/W
0. to 100. (lower limit : b063 - b066 *2) (%)
1 [%]
1344h
Hysteresis width of window
comparators OI
b065 R/W
0. to 10. (lower limit : b063 - b064 / 2) (%)
1 [%]
B38
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
1345h to
1348h
(Reserved) - - -
1349h Operation level at O disconnection b070 R/W
0. to 100. (%) or "no" (ignore)
1 [%]
134Ah Operation level at OI disconnection b071 R/W
0. to 100. (%) or "no" (ignore)
1 [%]
134Bh to
134Dh
(reserved) - - - -
134Eh Ambient temperature b075 R/W -10 to 50
1 []
134Fh to
1350
(reserved) - - - -
1351h
Cumulative input power data
clearance
b078 R/W Clearance by setting "1" -
1352h Watt-hou
r
display gain b079 R/W 1 to 1000 1
1353h to
1354h
(Reserved) - - - -
1355h Start frequency b082 R/W 10 to 999 0.01 [Hz]
1356h Carrier frequency b083 R/W 20 to 150 0.1 [kHz]
1357h
Initialization mode (parameters or
trip history)
b084 R/W
0,1 (clearing the trip history), 2 (initializing
the data), 3 (clearing the trip history and
initializing the data), 4 (clearing the trip
history and initializing the data and EzSQ
program)
-
1358h Country code for initialization b085 R/W 0 (area A), 1 (area B) -
1359h
Frequency scaling conversion
facto
r
b086 R/W 1 to 9999 0.01
135Ah STOP key enable b087 R/W
0 (enabling), 1 (disabling), 2 (disabling only
stop)
-
135Bh Restart mode after FRS b088 R/W
0 (starting with 0 Hz), 1 (starting with
matching frequency), 2 (starting with active
matching frequency)
-
135Ch
Automatic carrier frequency
reduction
b089 R/W
0(disabling)/1(enabling( output current
controlled))/
2(enabling( fin temperature controlled))
-
135Dh Dynamic braking usage ratio b090 R/W 0 to 1000 0.1 [%]
135Eh Stop mode selection b091 R/W 0 (deceleration until stop), 1 (free-run stop) -
135Fh Cooling fan control b092 R/W
0 (always operating the fan), 1 (operating the
fan only during inverter operation [including 5
minutes after powe
r
-on and powe
r
-off]) ,2
-
1360h Clear elapsed time of cooling fan b093 R/W 0(count)/1(clear)
-
1361h Initialization target data b094 R/W 0 to 3
-
1362h Dynamic braking control b095 R/W
0 (disabling), 1 (enabling [disabling while the
motor is stopped]), 2 (enabling [enabling also
while the motor is stopped])
1363h Dynamic braking activation level b096 R/W 330 to 380, 660 to 760 1. [V]
1364h to
1366h
(Reserved) - - - -
1367h Free-setting V/f frequenc
y
(1) b100 R/W 0. to "free-setting V/f frequency (2)" 1 [Hz]
1368h Free-setting V/f voltage (1) b101 R/W 0. to 8000 0.1 [V]
1369h Free-setting V/f frequency (2) b102 R/W 0. to "free-setting V/f frequency (3)" 1 [Hz]
136Ah Free-setting V/f voltage (2) b103 R/W 0. to 8000 0.1 [V]
136Bh Free-setting V/f frequency (3) b104 R/W 0. to "free-setting V/f frequency (4)" 1 [Hz]
136Ch Free-setting V/f voltage (3) b105 R/W 0. to 8000 0.1 [V]
136Dh Free-setting V/f frequency (4) b106 R/W 0. to "free-setting V/f frequency (5)" 1 [Hz]
136Eh Free-setting V/f voltage (4) b107 R/W 0. to 8000 0.1 [V]
136Fh Free-setting V/f frequency (5) b108 R/W 0. to "free-setting V/f frequency (6)" 1 [Hz]
1370h Free-setting V/f voltage (5) b109 R/W 0. to 8000 0.1 [V]
1371h Free-setting V/f frequency (6) b110 R/W 0. to "free-setting V/f frequency (7)" 1 [Hz]
1372h Free-setting V/f voltage (6) b111 R/W 0. to 8000 0.1 [V]
1373h Free-setting V/f frequency (7) b112 R/W 0. to 400. 1 [Hz]
1374h Free-setting V/f voltage (7) b113 R/W 0. to 8000 0.1 [V]
B39
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
1375h to
137Ah
(Reserved) - - - -
137Bh Brake Control Enable b120 R/W 0 (disabling), 1 (enabling) -
137Ch Brake Wait Time for Release b121 R/W 0 to 500
0.01
[sec.]
137Dh Brake Wait Time for Acceleration b122 R/W 0 to 500
0.01
[sec.]
137Eh Brake Wait Time for Stopping b123 R/W 0 to 500
0.01
[sec.]
137Fh Brake Wait Time for Confirmation b124 R/W 0 to 500
0.01
[sec.]
1380h Brake Release Frequency b125 R/W 0 to 40000 0.01 [Hz]
1381h Brake Release Current b126 R/W 0 to 2000 0.1 [%]
1382h Braking frequency b127 R/W 0 to 40000 0.01 [Hz]
1383h (Reserved) - - - -
1384h (Reserved) - - - -
1385h
Deceleration overvoltage
suppression enable
b130 R/W
0 (disabling), 1 (enabling), 2 (enabling with
acceleration)
-
1386h Decel. overvolt. suppress level b131 R/W
200 V class: 330 to 390 (V)
400 V class: 660 to 780 (V)
1 [V]
1387h Decel. overvolt. suppress const. b132 R/W 10 to 3000
0.01
[sec.]
1388h
Decel. overvolt. suppress
propotional gain
b133 R/W 0 to 500 0.01
1389h
Decel. overvolt. suppress Integral
time
b134 R/W 0 to 1500 0.1 [sec.]
138Ah to
1393h
(Reserved) - - - -
1394h
GS input mode
b145 R/W 0(non Trip) /1(Trip)
1395h
1399h
(Reserved) - - -
139Ah Display ex.operator connected b150 R/W 001 to 060
139Bh
13A2h
(Reserved) - - -
13A3h
1st parameter of Dual
Monitor
b160 R/W 001 to 030
13A4h
2nd parameter of Dual
Monitor
b161 R/W 001 to 030
13A5h
(Reserved) - - -
13A6h
Freq. set in monitoring
b163 R/W 0 (disabling), 1 (enabling),
13A7h
Automatic return to the initial
display
b164 R/W 0 (disabling), 1 (enabling),
13A8h Ex. operator com. loss action b165 R/W
0 (tripping), 1 (tripping after decelerating and
stopping the motor), 2 (ignoring errors),
3 (stopping the motor after free-running),
4 (decelerating and stopping the motor)
13A9h
13ADh
(Reserved) - - -
13AEh
Inverter mode selection
b171 R/W
0 (disabling), 1 (IM mode), 2 (High Freq.
mode)
13AFh
13B6h
(Reserved) - - -
13B7h
Initialization trigger
b180 R/W 0 (disabling), 1 (enabling),
13B8h
1400h
unused - - Inaccessible -
B40
Parameter group C
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1401h Input [1] function C001 R/W
1 (RV: Reverse RUN), 2 (CF1: Multispeed 1 setting),
3 (CF2: Multispeed 2 setting), 4 (CF3: Multispeed 3
setting), 5 (CF4: Multispeed 4 setting), 6 (JG:
Jogging), 7 (DB: external DC braking), 8 (SET: Set
2nd motor data), 9 (2CH: 2-stage
acceleration/deceleration), 11 (FRS: free-run stop), 12
(EXT: external trip), 13 (USP: unattended start
protection), 14: (CS: commercial power source
enable), 15 (SFT: software lock), 16 (AT: analog input
voltage/current select), 18 (RS: reset), 20 (STA:
starting by 3-wire input), 21 (STP: stopping by 3-wire
input), 22 (F/R: forward/reverse switching by 3-wire
input), 23 (PID: PID disable), 24 (PIDC: PID reset, 27
(UP: remote control UP function), 28 (DWN: remote
control DOWN function), 29 (UDC: remote control
data clearing), 31 (OPE: forcible operation), 32 (SF1:
multispeed bit 1), 33 (SF2: multispeed bit 2), 34 (SF3:
multispeed bit 3), 35 (SF4: multispeed bit 4), 36 (SF5:
multispeed bit 5), 37 (SF6: multispeed bit 6), 38 (SF7:
multispeed bit 7), 39 (OLR: overload restriction
selection), 40 (TL: torque limit enable), 41 (TRQ1:
torque limit selection bit 1), 42 (TRQ2: torque limit
selection bit 2), 44 (BOK: braking confirmation), 46
(LAC: LAD cancellation), 47 (PCLR: clearance of
position deviation), 50 (ADD: trigger for frequency
addition [A145]), 51 (F-TM: forcible-terminal
operation), 52 (ATR: permission of torque command
input), 53 (KHC: cumulative power clearance), 56
(MI1: general-purpose input 1), 57 (MI2:
general-purpose input 2), 58 (MI3: general-purpose
input 3), 59 (MI4: general-purpose input 4), 60 (MI5:
general-purpose input 5), 61 (MI6: general-purpose
input 6), 62 (MI7: general-purpose input 7), 65 (AHD:
analog command holding), 66 (CP1: multistage
position settings selection 1 ), 67 (CP2: multistage
position settings selection 2), 68 (CP3: multistage
position settings selection 3), 69 (ORL: Zero-return
limit function), 70 (ORG: Zero-return trigger function),
73 (SPD: speed / position switching), 77 (GS1: safety
input 1), 78 (GS2: safety input 2), 81 (485: EzCOM),
82 (PRG: executing EzSQ program), 83 (HLD: retain
output frequency), 84 (ROK: permission of run
command), 85 (EB: Rotation direction detection(for V/f
with ENC), 86 (DISP: Display limitation),
255 (no: no assignment),
-
1402h Input [2] function C002 R/W -
1403h Input [3] function C003 R/W -
1404h Input [4] function C004 R/W -
1405h Input [5] function C005 R/W -
1406h Input [6] function C006 R/W -
1407h Input [7] function C007 R/W -
1408h to
140Ah
(Reserved) - - Inaccessible -
140Bh
Input [1] active
state
C011 R/W 0 (NO), 1 (NC) -
140Ch
Input [2] active
state
C012 R/W 0 (NO), 1 (NC) -
140Dh
Input [3] active
state
C013 R/W 0 (NO), 1 (NC) -
140Eh
Input [4] active
state
C014 R/W 0 (NO), 1 (NC) -
140Fh
Input [5] active
state
C015 R/W 0 (NO), 1 (NC) -
1410h
Input [6] active
state
C016 R/W 0 (NO), 1 (NC) -
1411h
Input [7] active
state
C017 R/W 0 (NO), 1 (NC) -
1412h to
1414h
(Reserved) - - Inaccessible -
B41
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1415h
Output [11]
function
C021 R/W
0 (RUN: running), 1 (FA1: constant-speed reached), 2
(FA2: set frequency overreached), 3 (OL: overload
notice advance signal (1)), 4 (OD: output deviation for
PID control), 5 (AL: alarm signal), 6 (FA3: set
frequency reached), 7 (OTQ: over-torque), 9 (UV:
undervoltage), 10 (TRQ: torque limited), 11 (RNT:
operation time over), 12 (ONT: plug-in time over), 13
(THM: thermal alarm signal), 19 (BRK: brake release),
20 (BER: braking error), 21 (ZS: 0 Hz detection
signal), 22 (DSE: speed deviation maximum), 23
(POK: positioning completed), 24 (FA4: set frequency
overreached 2), 25 (FA5: set frequency reached 2), 26
(OL2: overload notice advance signal (2)), 31 (FBV:
PID feedback comparison), 32 (NDc: communication
line disconnection), 33 (LOG1: logical operation result
1), 34 (LOG2: logical operation result 2), 35 (LOG3:
logical operation result 3), 39 (WAC: capacitor life
warning), 40 (WAF: cooling-fan), 41 (FR: starting
contact signal), 42 (OHF: heat sink overheat warning),
43 (LOC: low-current indication signal), 44 (M01:
general-purpose output 1), 45 (M02: general-purpose
output 2), 46 (M03: general-purpose output 3), 50
(IRDY: inverter ready), 51 (FWR: forward rotation), 52
(RVR: reverse rotation), 53 (MJA: major failur)
54 (WCO: window comparator O), 55 (WCO: window
comparator OI),
58(FREF),59(REF),60(SETM),62(EDM),63(OPO:Opti
on)
-
1416h
Output [12]
function
C022 R/W -
1421h to
1423h
(Reserved) - - -
141Ah
Alarm relay
function
C026 R/W -
141Bh
[EO] terminal
selection
C027 R/W
0 (output frequency), 1 (output current), 2 (output
torque), 3 (digital output frequency), 4 (output
voltage), 5 (input power), 6 (electronic thermal
overload), 7 (LAD frequency), 8 (digital current
monitoring), 10 (heat sink temperature), 12
(general-purpose output YA0),15 ,16(option)
-
141Ch
[AM] terminal
selection
C028 R/W
0 (output frequency), 1 (output current), 2 (output
torque), 4 (output voltage), 5 (input power), 6
(electronic thermal overload), 7 (LAD frequency), 10
(heat sink temperature), 11 (output torque [signed
value]), 13 (general-purpose output YA1),16(option)
-
141Dh (reserved) - - - -
141Eh
Digital current
monitor reference
value
C030 R/W 200 to 2000 0.1 [%]
141Fh
Output [11] active
state
C031 R/W 0 (NO), 1 (NC) -
1420h
Output [12] active
state
C032 R/W 0 (NO), 1 (NC) -
1421h to
1423h
(Reserved) - - - -
1424h
Alarm relay active
state
C036 R/W 0 (NO), 1 (NC) -
1425h (Reserved) - - - -
1426h
Output mode of
low current
detection
C038 R/W
0 (output during acceleration/deceleration and
constant-speed operation), 1 (output only during
constant-speed operation)
-
1427h
Low current
detection level
C039 R/W 0 to 2000 0.1 [%]
1428h
Overload signal
output mode
C040 R/W
00 (output during acceleration/deceleration and
constant-speed operation), 01 (output only during
constant-speed operation)
-
1429h
Overload warning
level
C041 R/W 0 to 2000 0.1 [%]
B42
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
142Ah
Frequency arrival setting for accel.
C042 (high) R/W
0 to 40000 0.01 [Hz]
142Bh C042 (low) R/W
142Ch
Frequency arrival setting for decel.
C043 (high) R/W
0 to 40000 0.01 [Hz]
142Dh C043 (low) R/W
142Eh PID deviation level C044 R/W 0 to 1000 0.1 [%]
142Fh
Frequency arrival setting 2 for
accel.
C045 (high) R/W
0 to 40000 0.01 [Hz]
1430h C045 (low) R/W
1431h
Frequency arrival setting 2 for
decel.
C046 (high) R/W
0 to 40000 0.01 [Hz]
1432h C046 (low) R/W
1433h
Pulse train input scale conversion
for EO output
C047 R/W 0.01 – 99.99
1434h to
1437h
(Reserved) - - - -
1438h Maximum PID feedback data C052 R/W 0 to 1000 0.1 [%]
1439h Minimum PID feedback data C053 R/W 0 to 1000 0.1 [%]
143Ah
Over-torque/under-torqueselection
C054 R/W 0(Over torque)/1(under torque)
143Bh
Over-torque (forward-driving) level
setting
C055 R/W 0 to 200 1 [%]
143Ch
Over-torque (reverse
regenerating) level setting
C056 R/W 0 to 200 1 [%]
143Dh
Over-torque (reverse driving) level
setting
C057 R/W 0 to 200 1 [%]
143Eh
Over-torque (forward
regenerating) level setting
C058 R/W 0 to 200 1 [%]
143Fh
Signal output mode of Over/under
torque
C059 R/W
00 (output during
acceleration/deceleration and
constant-speed operation), 01 (output
only during constant-speed operation)
1440h (Reserved) - - - -
1441h Electronic thermal warning level C061 R/W 0 to 100 1 [%]
1442h
(Reserved) - - -
1443h Zero speed detection level C063 R/W 0 to 10000 0.01 [Hz]
1444h Heat sink overheat warning level C064 R/W 0 to 110 1 []
1445h to
144Ah
(Reserved) - - - -
144Bh Communication speed C071 R/W
03(2400bps), 04(4800bps),
05(9600bps) 06(19.2kbps),
07(38.4kbps),,08(57.6kbps),
09(76.8kbps), 10(115.2kbps)
-
144Ch Modbus address C072 R/W 1. to 247. -
144Dh (Reserved) - - - -
144Eh Communication parity C074 R/W
00 (no parity), 01 (even parity), 02 (odd
parity)
-
144Fh Communication stop bit C075 R/W 1 (1 bit), 2 (2 bits) -
1450h
Selection of the operation after
communication error
C076 R/W
0 (tripping), 1 (tripping after decelerating
and stopping the motor), 2 (ignoring
errors), 3 (stopping the motor after
free-running), 4 (decelerating and
stopping the motor)
-
1451h Communication timeout limit C077 R/W 0 to 9999 0.01 [sec.]
1452h Communication wait time C078 R/W 0 to 1000 1 [msec.]
1453h to
1454h
(Reserved) - - - -
1455h [O] input span calibration C081 R/W 0 to 2000 0.1
1456h [OI] input span calibration C082 R/W 0 to 2000 0.1
1457h to
1458h
(Reserved) - - - -
1459h Thermistor input tuning C085 R/W 0 to 2000 0.1
145Ah to
145Eh
(Reserved) - - - -
145Fh Debug mode enable C091 R 0/1 -
1460h to
1463h
(Reserved) - - - -
1464h Communication selection C096 R/W 0(Modbus-RTU) 1(EzCOM)
B43
2(EzCOM<administrator>)
1465h (Reserved) - - - -
1466h EzCOM start adr. of master C098 R/W 18
1467h EzCOM end adr. of master C099 R/W 18
1468h EzCOM starting trigger C100 R/W 00(Input terminal), 01(Always)
1469h Up/Down memory mode selection C101 R/W
0 (not storing the frequency data), 1
(storing the frequency data)
-
146Ah Reset mode selection C102 R/W
0 (resetting the trip when RS is on), 1
(resetting the trip when RS is off), 2
(enabling resetting only upon tripping
[resetting when RS is on]), 3(resetting
only trip)
-
146Bh Restart mode after reset C103 R/W
0 (starting with 0 Hz), 1 (starting with
matching frequency), 2 (restarting with
active matching frequency)
-
146Ch
UP/DWN clear mode
C104 R/W
0 (0Hz)/1 (EEPROM data)
-
146Dh FM gain adjustment C105 R/W 50 to 200 1 [%]
146Eh AM gain adjustment C106 R/W 50 to 200 1 [%]
146Fh
(Reserved) - - Inaccessible
1 [%]
1471h AM bias adjustment C109 R/W 0 to 100 1 [%]
1472h (Reserved) - - - 1 [%]
1473h Overload warning level 2 C111 R/W 0 to 2000 0.1 [%]
1474h to
1485h
(Reserved) - - - -
1486h Output [11] on-delay time C130 R/W 0 to 1000 0.1 [sec.]
1487h Output [11] off-delay time C131 R/W 0 to 1000 0.1 [sec.]
1488h Output [12] on-delay time C132 R/W 0 to 1000 0.1 [sec.]
1489h Output [12] off-delay time C133 R/W 0 to 1000 0.1 [sec.]
148Ah to
148F
(Reserved) - - - -
1490h Output RY on-delay time C140 R/W 0 to 1000 0.1 [sec.]
1491h Output RY off-delay time C141 R/W 0 to 1000 0.1 [sec.]
1492h Logic output 1 operand A C142 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
1493h Logic output 1 operand B C143 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
1494h Logical output 1 operato
r
C144 R/W 0 (AND), 1 (OR), 2 (XOR) -
1495h Logic output 2 operand A C145 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
1496h Logic output 2 operand B C146 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
1497h Logical output 2 operato
r
C147 R/W 0 (AND), 1 (OR), 2 (XOR) -
1498h Logic output 3 operand A C148 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
1499h Logic output 3 operand B C149 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
149Ah Logical output 3 operato
r
C150 R/W 0 (AND), 1 (OR), 2 (XOR) -
149Bh to
14A3h
(Reserved) - - -
-
14A4h Input [1] response time C160 R/W 0 to 200
14A5h Input [2] response time C161 R/W 0 to 200
14A6h Input [3] response time C162 R/W 0 to 200
14A7h Input [4] response time C163 R/W 0 to 200
14A8h Input [5] response time C164 R/W 0 to 200
14A9h Input [6] response time C165 R/W 0 to 200
14AAh Input [7] response time C166 R/W 0 to 200
14ABh to
14ACh
(Reserved) - - -
14ADh Multistage speed/position determination time C169 R/W 0 to 200
14A4h to
1500h
unused - - Inaccessible -
B44
Parameter group H
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1501h Auto-tuning Setting H001 R/W
0 (disabling auto-tuning), 1
(auto-tuning without rotation), 2
(auto-tuning with rotation)
-
1502h Motor data selection, 1st motor H002 R/W
0 (Hitachi standard data), 2
(auto-tuned data)
-
1503h Motor capacity, 1st motor H003 R/W 00(0.1kW)- 15 (18.5kW) -
1504h Motor poles setting, 1st motor H004 R/W
0 (2 poles), 1 (4 poles), 2 (6
poles),
3 (8 poles), 4 (10 poles)
-
1505h (Reserved) - - - -
1506h Motor speed constant, 1st motor H005 R/W 0 to 1000 1[%]
1508h
1514h
(Reserved) - - - -
1516h
Motor stabilization constant, 1st
motor
H006 R/W 0 to 255 1
1517h (Reserved) - - - -
1516h Motor constant R1, 1st motor H020 R/W 1 to 65530 0.001 [Ω]
1517h (Reserved) - - - -
1518h Motor constant R2, 1st motor H021 R/W 1 to 65530 0.001 [Ω]
1519h (Reserved) - - - -
151Ah Motor constant L, 1st motor H022 R/W 1 to 65530 0.01 [mH]
151Bh (Reserved) - - - -
151Ch Motor constant Io H023 R/W 1 to 65530 0.01 [A]
151Dh
Motor constant J
H024 (high) R/W
1 to 9999000 0.001
151Eh H024 (low) R/W
151Hf
1524h
(Reserved) - - - -
1525h Auto constant R1, 1st motor H030 R/W 1 to 65530 0.001 [Ω]
1526h (Reserved) - - Inaccessible -
1527h Auto constant R2, 1st motor H031 R/W 1 to 65530 0.001 [Ω]
1528h (Reserved) - - - -
1529h Auto constant L, 1st motor H032 R/W 1 to 65530 0.01 [mH]
152Ah (Reserved) - - Inaccessible -
152Bh Auto constant Io, 1st motor H033 R/W 1 to 65530 0.01 [A]
152Ch
Auto constant J, 1st motor
H034 (high) R/W
1 to 9999000 0.001
152Dh H034 (low) R/W
152Eh
153Ch
(Reserved) - - - -
153Dh
Slip compensation P gain for V/f
control with FB
H050 R/W 0 to 10000 0.1
153Eh
Slip compensation P gain for V/f
control with FB
H051 R/W 0 to 10000 1
153Fh
1600h
unused - - Inaccessible 2
B45
Parameter group P
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
1601h
Operation mode on expansion card
1 error
P001 R/W 0 (tripping), 1 (continuing operation) -
1602h (Reserved) - - - -
1603h [EA] terminal selection P003 R/W
00 (Speed reference, incl. PID)
01 (Encoder feedback)
02 (Extended terminal for EzSQ)
1604h
Pulse train input mode for
feedback
P004 R/W
00 (Single-phase pulse [EA])
01 (2-phase pulse [90° difference] 1
([EA] and [EB]))
02 (2-phase pulse [90° difference] 2
([EA] and [EB]))
03 (Single-phase pulse [EA] and
direction signal [EB])
1605h to
160Ah
(Reserved) - - - -
160Bh
Encoder pulse-per-revolution
(PPR) setting
P011 R/W 32 to 1024 1
160Ch Simple positioning selection P012 R/W
00 (simple positioning deactivated)
02 (simple positioning activated)
-
160Dh to
160Eh
(Reserved) - - - -
160Fh Creep speed P015 R/W "start frequency" to 1000 0.01 [Hz]
1610h to
1619h
(Reserved) - - - -
161Ah Over-speed error detection level P026 R/W 0 to 1500 0.1 [%]
161Bh
Speed deviation error detection
level
P027 R/W 0 to 12000 0.01 [Hz]
161Ch to
161Eh
(Reserved) - - - -
161Fh Accel/decel time input selection P031 R/W 0 (digital operator), 3 (easy sequence) -
1620h (Reserved) - - - -
1621h Torque command input selection P033 R/W
0 (O terminal), 1 (OI terminal),
3 (digital operator), 06 (Option)
-
1622h Torque command setting P034 R/W 0 to 200 1 [%]
1623h (Reserved) - - - -
1624h Torque bias mode P036 R/W
0 (disabling the mode),1 (digital
operator),
-
1625h Torque bias value P037 R/W -200 to +200 1 [%]
1626h Torque bias polarity selection P038 R/W
0 (as indicated by the sign), 1
(depending on the operation direction),
05(Option)
-
1627h
Speed limit for torque-controlled
operation (forward rotation)
P039 (high) R/W
0 to 12000 0.01 [Hz]
1628h P039 (low) R/W
1629h
Speed limit for torque-controlled
operation (reverse rotation)
P040 (high) R/W
0 to 12000 0.01 [Hz]
162Ah P040 (low) R/W
162Bh
Speed / torque control switching
time
P041 R/W 0 to 1000 -
162Ch to
162Dh
(Reserved) - - - -
162Eh
Communication watchdog timer
P044 R/W 0 to 9999 0.01 [sec.]
162Fh
Inverter action on communication
error
P045 R/W
0 (tripping), 1 (tripping after decelerating
and stopping the motor), 2 (ignoring
errors),
3 (stopping the motor after free-running),
4 (decelerating and stopping the motor)
-
1630h
DeviceNet polled I/O: Output
instance number
P046 R/W 0-20 -
1631h (Reserved) - - - -
1632h
Inverter action on communication
idle mode
P048 R/W
0 (tripping), 1 (tripping after decelerating
and stopping the motor), 2 (ignoring
errors),
3 (stopping the motor after free-running),
4 (decelerating and stopping the motor)
-
B46
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1633h Motor poles setting for RPM P049 R/W
0 (0 pole), 1 (2 poles), 2 (4 poles),
3 (6 poles),4 (8 poles),5 (10 poles),
6 (12 poles),7 (14 poles),8 (16 poles),
9 (18 poles), 10 (20 poles),11 (22
poles), 12 (24 poles),13 (26 poles),14
(28 poles), 15 (30 poles), 16 (32
poles),17 (34 poles),
18 (36 poles), 19 (38 poles)
-
1634h to
1638h
(Reserved) - - - -
1639h Pulse train frequency scale P055 R/W
10 to 320 (input frequency
corresponding to the allowable
maximum frequency)
0.1 [kHz]
163Ah
Time constant of pulse train
frequency filter
P056 R/W 1 to 200 0.01 [sec.]
163Bh Pulse train frequency bias P057 R/W -100 to +100 1 [%]
163Ch Pulse train frequency limit P058 R/W 0 to 100 1 [%]
163Dh (Reserved) - - - -
163Eh
Multistage position 0
P060(HIGH) R/W
1
163Fh P060(LOW) R/W
1640h
Multistage position 1
P061(HIGH) R/W
1
1641h P061(LOW) R/W
1642h
Multistage position 2
P062(HIGH) R/W
1
1643h P062(LOW) R/W
1644h
Multistage position 3
P063(HIGH) R/W
1
1645h P063(LOW) R/W
1646h
Multistage position 4
P064(HIGH) R/W
1
1647h P064(LOW) R/W
1648h
Multistage position 5
P065(HIGH) R/W
1
1649h P065(LOW) R/W
164Ah
Multistage position 6
P066(HIGH) R/W
1
164Bh P066(LOW) R/W
164Ch
Multistage position 7
P067(HIGH) R/W
1
164Dh P067(LOW) R/W
164Eh Homing mode selection P068 R/W 0(Low) / 1(High)
164Fh Homing direction P069 R/W 0(FW) / 1(RV)
1650h Low-speed homing frequency P070 R/W 0 to 1000
1651h High-speed homing frequency P071 R/W 0 to 40000
1652h
Position range (forward)
P072(HIGH) R/W
0 to 268435455 1
1653h P072(LOW) R/W
1654h
Position range (reverse)
P073(HIGH) R/W
-268435455 to 0 1
1655h P073(LOW) R/W
1656h (Reserved), - - - -
1657h Positioning mode P075 R/W
00…With limitation
01…No limitation (fastest control)
1658h (Reserved), - - - -
1659h Encoder disconnection timeout P077 R/W 0 to 100 0.1[sec.]
165Ah to
1665h
(Reserved), - - - -
1656h to
1665h
(Reserved) - - - -
B47
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1666h EzSQ user parameter U (00) P100 R/W 0 to 65530 1
1667h EzSQ user parameter U (01) P101 R/W 0 to65530 1
1668h EzSQ user parameter U (02) P102 R/W 0 to 65530 1
1669h EzSQ user parameter U (03) P103 R/W 0 to 65530 1
166Ah EzSQ user parameter U (04) P104 R/W 0 to 65530 1
166Bh EzSQ user parameter U (05) P105 R/W 0 to 65530 1
166Ch EzSQ user parameter U (06) P106 R/W 0 to 65530 1
166Dh EzSQ user parameter U (07) P107 R/W 0 to 65530 1
166Eh EzSQ user parameter U (08) P108 R/W 0 to 65530 1
166Fh EzSQ user parameter U (09) P109 R/W 0 to 65530 1
1670h EzSQ user parameter U (10) P110 R/W 0 to 65530 1
1671h EzSQ user parameter U (11) P111 R/W 0 to 65530 1
1672h EzSQ user parameter U (12) P112 R/W 0 to 65530 1
1673h EzSQ user parameter U (13) P113 R/W 0 to 65530 1
1674h EzSQ user parameter U (14) P114 R/W 0 to 65530 1
1675h EzSQ user parameter U (15) P115 R/W 0 to 65530 1
1676h EzSQ user parameter U (16) P116 R/W 0 to 65530 1
1677h EzSQ user parameter U (17) P117 R/W 0 to 65530 1
1678h EzSQ user parameter U (18) P118 R/W 0 to 65530 1
1679h EzSQ user parameter U (19) P119 R/W 0 to 65530 1
167Ah EzSQ user parameter U (20) P120 R/W 0 to 65530 1
167Bh EzSQ user parameter U (21) P121 R/W 0 to 65530 1
167Ch EzSQ user parameter U (22) P122 R/W 0 to 65530 1
167Dh EzSQ user parameter U (23) P123 R/W 0 to 65530 1
167Eh EzSQ user parameter U (24) P124 R/W 0 to 65530 1
167Fh EzSQ user parameter U (25) P125 R/W 0 to 65530 1
1680h EzSQ user parameter U (26) P126 R/W 0 to 65530
1681h EzSQ user parameter U (27) P127 R/W 0 to 65530
1682h EzSQ user parameter U (28) P128 R/W 0 to 65530 1
1683h EzSQ user parameter U (29) P129 R/W 0 to 65530 1
1684h EzSQ user parameter U (30) P130 R/W 0 to 65530 1
1685h EzSQ user parameter U (31) P131 R/W 0 to 65530 1
1686h to
168Dh
(Reserved), - - - -
168Eh EzCOM number of data P140 R/W 1 to 5
168Fh EzCOM destination 1 adderss P141 R/W 1 to 247
1690h EzCOM destination 1 register P142 R/W 0000 to FFFF
1691h EzCOM source 1 register P143 R/W 0000 to FFFF
1692h EzCOM destination 2 adderss P144 R/W 1 to 247
1693h EzCOM destination 2 register P145 R/W 0000 to FFFF
1694h EzCOM source 2 register P146 R/W 0000 to FFFF
1695h EzCOM destination 3 adderss P147 R/W 1 to 247
1696h EzCOM destination 3 register P148 R/W 0000 to FFFF
1697h EzCOM source 3 register P149 R/W 0000 to FFFF
1698h EzCOM destination 4 adderss P150 R/W 1 to 247
1699h EzCOM destination 4 register P151 R/W 0000 to FFFF
169Ah EzCOM source 4 register P152 R/W 0000 to FFFF
169Bh EzCOM destination 5 adderss P153 R/W 1 to 247
169Ch EzCOM destination 5 register P154 R/W 0000 to FFFF
169Dh EzCOM source 5 register P155 R/W 0000 to FFFF
169Eh
16A1h
(Reserved), - - - -
B48
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
16A2h
Option I/F command register to write 1
P160 R/W 0000 to FFFF
16A3h
Option I/F command register to write 2
P161 R/W 0000 to FFFF
16A4h
Option I/F command register to write 3
P162 R/W 0000 to FFFF
16A5h
Option I/F command register to write 4
P163 R/W 0000 to FFFF
16A6h
Option I/F command register to write 5
P164 R/W 0000 to FFFF
16A7h
Option I/F command register to write 6
P165 R/W 0000 to FFFF
16A8h
Option I/F command register to write 7
P166 R/W 0000 to FFFF
16A9h
Option I/F command register to write 8
P167 R/W 0000 to FFFF
16AAh
Option I/F command register to write 9
P168 R/W 0000 to FFFF
16ABh
Option I/F command register to write
10
P169 R/W 0000 to FFFF
16ACh
Option I/F command register to read 1
P170 R/W 0000 to FFFF
16ADh
Option I/F command register to read 2
P171 R/W 0000 to FFFF
16AEh
Option I/F command register to read 3
P172 R/W 0000 to FFFF
16AFh
Option I/F command register to read 4
P173 R/W 0000 to FFFF
16B0h
Option I/F command register to read 5
P174 R/W 0000 to FFFF
16B1h
Option I/F command register to read 6
P175 R/W 0000 to FFFF
16B2h
Option I/F command register to read 7
P176 R/W 0000 to FFFF
16B3h
Option I/F command register to read 8
P177 R/W 0000 to FFFF
16B4h
Option I/F command register to read 9
P178 R/W 0000 to FFFF
16B5h
Option I/F command register to read
10
P179 R/W 0000 to FFFF
16B6h
Profibus Node address
P180 R/W 0 to 125
16B7h
Profibus Clear Node address
P181 R/W 0(clear)/1(not clear)
16B8h
Profibus Map selection
P182 R/W 0(PPO)/1(Comvertional)
16B9h to
16BAh
(Reserved), - - - -
16BBh
CANopen Node address P185 R/W 0 to 127
16BCh
CAN open communication speed P186 R/W
0 (automatic) 5 (250kbps)
1 (10kbps) 6 (500kbps)
2 (20kbps) 7 (800kbps)
3 (50kbps) 8 (1Mbps)
4 (125kbps)
16BDh to
1E00h
Unused - - - -
1E01h
Coil data 1 - R/W
2
1
: coil number 0010h –
2
15
: coil number 001Fh -
-
1E02h
Coil data 2 - R/W
2
1
: coil number 0020h –
2
15
: coil number 002Fh -
-
1E03h
Coil data 3 - R/W
2
1
: coil number 0001h –
2
15
: coil number 000Fh -
-
1E04h
Coil data 4 - R/W
2
1
: coil number 0030h –
2
15
: coil number 003Fh -
-
1E05h
Coil data 5 - R/W
2
1
: coil number 0040h –
2
15
: coil number 004Fh -
-
1E06h to
1F18h
(reserved) - - - -
1E19h to
1F00h
Unused - - - -
1F01h
Coil data 0 - R/W
2
1
: coil number 0001h –
2
15
: coil number 000Fh -
-
1F02h to
1F1Dh
(reserved) - - (note: 2) -
1F1Eh to
2102h
Unused - - Inaccessible -
Note 1: above register (coil data 0 to 5) is consisted with 16 coil data. EzCOM communication
(inverter to inverter) doesn’t support coil, but only register is supporte, in case of need to access
coil, please use above registers.
B49
Note 2: Be sure not to write into above 1F02h to 1F1Dh.
B50
(vi) List of registers (2nd control settings)
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
2103h
Acceleration time (1),
2nd motor
F202 (high) R/W
1 to 360000
0.01 [sec.]
2104h F202 (low) R/W
2105h
Deceleration time (1),
2nd motor
F203 (high) R/W
1 to 360000
0.01 [sec.]
2106h F203 (low) R/W
2107h to
2200h
unused - - Inaccessible -
(vii) List of registers (function modes for the 2nd control settings)
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
2201h Frequency source, 2nd motor A201 R/W
0 (keypad potentiometer), 1 (control
circuit terminal block), 2 (digital
operator), 3 (Modbus), 4 (option ), 6
(pulse train input), 7 (easy sequence),
10 (operation function result)
-
2202h Frequency source, 2nd motor A202 R/W
1 (control circuit terminal block), 2
(digital operator), 3 (Modbus), 4
(option)
-
2203h Base frequency, 2nd motor A203 R/W
300 to "maximum frequency, 2nd
motor"
0.1 [Hz]
2204h
Maximum frequency,
2nd motor
A204 R/W 300 to 4000 0.1 [Hz]
2205h to
2215h
(Reserved) - - Inaccessible -
2216h
Multispeed frequency setting,
2nd motor
A220 (high) R/W
0 or "start frequency" to "maximum
frequency, 2nd motor"
0.01 [Hz]
2217h A220 (low) R/W
2218h to
223Ah
(Reserved) - - Inaccessible -
223Bh
Torque boost method
selection, 2nd motor
A241 R/W
0 (manual torque boost), 1 (automatic
torque boost)
-
223Ch
Manual torque boost value,
2nd motor
A242 R/W 20 to 200 1 [%]
223Dh
Manual torque boost
frequency, 2nd motor
A243 R/W 0 to 255 1 [%]
223Eh
V/F characteristic curve
selection, 2nd motor
A244 R/W
0 (VC), 1 (VP), 2 (free V/f), 3
(sensorless vector control)
-
223Fh
V/f gain, 2nd motor
A245 R/W 20 to 100
1 [%]
2240h
Voltage compensation gain
setting for automatic torque
boost, 2nd motor
A246 R/W 0 to 255 1
2241h
Slippage compensation gain
setting for automatic torque
boost, 2nd motor
A247 R/W 0 to 255 1
2242h to
224Eh
(Reserved) - - Inaccessible -
224Fh
Frequency upper limit,
2nd motor
A261 (high) R/W
00 or "2nd minimum frequency limit"
to "maximum frequency, 2nd motor"
0.01 [Hz]
2250h A261 (low) R/W
2251h
Frequency lower limit,
2nd motor
A262 (high) R/W
00 or "start frequency" to "maximum
frequency, 2nd motor limit"
0.01 [Hz]
2252h A262 (low) R/W
2253h to
2268h
(Reserved) - - Inaccessible -
2269h AVR function select, 2nd motor A281 R/W
0 (always on), 1 (always off), 2 (off
during deceleration)
-
226Ah AVR voltage select, 2nd motor A282 R/W
200 V class: 0 (200)/1 (215)/2 (220)/3
(230)/4 (240)
400 V class: 5 (380)/6 (400)/7 (415)/8
(440)/9 (460)/ 10 (480)
226Bh to
226Eh
(Reserved) - - Inaccessible -
B51
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resoluti
on
226Fh
Acceleration time (2),
2nd motor
A292 (high) R/W
1 to 360000
0.01
[sec.]
2270h A292 (low) R/W
2271h
Deceleration time (2),
2nd motor
A293 (high) R/W
1 to 360000
0.01
[sec.]
2272h A293 (low) R/W
2273h
Select method to switch to
Acc2/Dec2, 2nd motor
A294 R/W
0 (switching by 2CH terminal), 1
(switching by setting), 2 (switching only
when the rotation is reversed)
-
2274h
Acc1 to Acc2 frequency
transition point, 2nd motor
A295 (high) R/W
0 to 40000 (100000)
0.01
[Hz]
2275h A295 (low) R/W
2276h
Dec1 to Dec2 frequency
transition point, 2nd motor
A296 (high) R/W
0 to 40000 (100000)
0.01
[Hz]
2277h A296 (low) R/W
2278h to
230Bh
(Reserved) - - - -
230Ch
Level of electronic thermal,
2nd motor
b212 R/W
200 to 1000
0.1 [%]
230Dh
Electronic thermal
characteristic, 2nd motor
b213 R/W
0 (reduced-torque characteristic), 1
(constant-torque characteristic), 2 (free
setting)
-
230Eh to
2315h
(Reserved) - - - -
2316h
Overload restriction operation
mode, 2nd motor
b221 R/W
0 (disabling), 1 (enabling during
acceleration and constant-speed
operation), 2 (enabling during
constant-speed operation), 3 (enabling
during acceleration and constant-speed
operation [speed increase at
regeneration])
2317h
Overload restriction level, 2nd
moto
r
b222 R/W
100 to 2000
0.1[%]
2318h
Deceleration rate at overload
restriction, 2nd moto
r
b223 R/W
1 to 30000
0.1[]
2319h to
2428h
unused - - Inaccessible -
2429h
Overload warning level 2,
2nd moto
r
C241 R/W
0 to 2000
0.1[%]
242Ah to
2501h
Unused - - Inaccessible -
2502h
Motor data selection, 2nd
motor
H202 R/W
0 (Hitachi standard data), 2 (auto-tuned
data),
2503h Motor capacity, 2nd motor H203 R/W 00(0.1kW)- 15 (18.5kW) -
B52
Register
No.
Function name Function code R/W Monitoring and setting items Data resolution
2504h
Motor poles setting, 2nd
motor
H204 R/W
0 (2 poles), 1 (4 poles), 2 (6 poles),
3 (8 poles), 4 (10 poles)
-
2505h
Motor speed constant,
2nd motor
H205 (high) R/W
1 to 1000 0.001
2506h H205 (low) R/W
2507h
Motor stabilization
constant, 2nd motor
H206 R/W
0 to 255
1
2508h to
2515h
(Reserved) - - - -
2516h
Motor constant R1, 2nd
motor
H220 (high) R/W 1 to 65535 0.001 [Ω]
2517h (Reserved) - - - -
2518h
Motor constant R2, 2nd
motor
H221 (high) R/W 1 to 65535 0.001 [Ω]
2519h (Reserved) - - - -
251Ah
Motor constant L, 2nd
motor
H222 (high) R/W 1 to 65535 0.01 [mH]
251Bh (Reserved) - - - -
251Ch
Motor constant Io, 2nd
motor
H223 (high) R/W 1 to 65535 0.01 [A]
251Dh
Motor constant J, 2nd
motor
H224 (high) R/W
1 to 9999000 0.001
251Eh H224 (low) R/W
251Fh to
2524h
(Reserved) - - - -
2525h
Auto constant R1, 2nd
motor
H230 (high) R/W 1 to 65530 0.001 [Ω]
2526h (Reserved) - - - -
2527h
Auto constant R2, 2nd
motor
H231 (high) R/W 1 to 65530 0.001 [Ω]
2528h (Reserved) - - - -
2529h
Auto constant L, 2nd
motor
H232 (high) R/W 1 to 65530 0.01 [mH]
252Ah (Reserved) - - - -
252Bh
Auto constant Io, 2nd
motor
H233 (high) R/W 1 to 65530 0.01 [A]
252Ch
Auto constant J, 2nd
motor
H234 (high) R/W
1 to 9999000 0.001
252Dh H234 (low) R/W
252Eh Unused - - Inaccessible -
C1
Drive Parameter
Setting Tables
In This Appendix… page
- Introduction ...................................................................................... 2
- Parameter Settings for Keypad Entry ............................................ 2
C
C2
Introduction
This appendix lists the user-programmable parameters for the WJ200 series inverters
and the default values for European and U.S. product types. The right-most column of
the tables is blank, so you can record values you have changed from the default. This
involves just a few parameters for most applications. This appendix presents the
parameters in a format oriented toward the keypad on the inverter.
Parameter Settings for Keypad Entry
WJ200 series inverters provide many functions and parameters that can be configured
by the user. We recommend that you record all parameters that have been edited, in
order to help in troubleshooting or recovery from a loss of parameter data.
Main Profile Parameters
NOTE:. Mark “9” in B031=10 shows the accessible parameters when B031 is set “10”,
high level access.
“F” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
F001
Output frequency setting Standard default target
frequency that determines
constant motor speed, range is
0.0 / start frequency to
maximum frequency (A004)
9
0.0 Hz
F002
Acceleration time (1) Standard default acceleration,
range is 0.01 to 3600 sec.
9
10.0 sec.
F202
Acceleration time (1),
2
nd
motor
9
10.0 sec.
F003
Deceleration time (1) Standard default deceleration,
range is 0.01 to 3600 sec.
9
10.0 sec.
F203
Deceleration time (1),
2
nd
motor
9
10.0 sec.
F004
Keypad RUN key routing Two options; select codes:
00 Forward
01 Reverse
U
00
Inverter model
WJ200
MFG. No.
This information is printed
on the specification label
located on the right side
of the inverter
C3
Standard Functions
NOTE:. Mark “9” in B031=10 shows the accessible parameters when B031 is set “10”,
high level access.
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A001
Frequency source Eight options; select codes:
00 POT on ext. operator
01 Control terminal
02 Function F001 setting
03 ModBus network input
04 Option
06 Pulse train input
07 via EzSQ
10 Calculate function output
U
02
A201
Frequency source,
2
nd
motor
U
02
A002
Run command source Five options; select codes:
01 Control terminal
02 Run key on keypad,
or digital operator
03 ModBus network input
04 Option
U
02
A202
Run command source,
2
nd
motor
U
02
A003
Base frequency Settable from 30 Hz to the
maximum frequency(A004)
U
60.0 Hz
A203
Base frequency,
2
nd
motor
Settable from 30 Hz to the 2
nd
maximum frequency(A204)
U
60.0 Hz
A004
Maximum frequency Settable from the base
frequency to 400 Hz
U
60.0 Hz
A204
Maximum frequency,
2
nd
motor
Settable from the 2
nd
base
frequency to 400 Hz
U
60.0 Hz
A005
[AT] selection Three options; select codes:
00...Select between [O] and [OI]
at [AT] (ON=OI, OFF=O)
02...Select between [O] and
external POT at [AT]
(ON=POT, OFF=O)
03...Select between [OI] and
external POT at [AT]
(ON=POT, OFF=OI)
U
00
A011
[O] input active range start
frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.00 to 400.0
U
0.00 Hz
A012
[O] input active range end
frequency
The output frequency
corresponding to the analog
input range ending point,
range is 0.0 to 400.0
U
0.00 Hz
A013
[O] input active range start
voltage
The starting point (offset) for
the active analog input range,
range is 0. to 100.
U
0. %
C4
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A014
[O] input active range end
voltage
The ending point (offset) for the
active analog input range,
range is 0. to 100.
U
100. %
A015
[O] input start frequency
enable
Two options; select codes:
00Use offset (A011 value)
01Use 0Hz
U
01
A016
Analog input filter Range n = 1 to 31,
1 to 30 : ×2ms filter
31: 500ms fixed filter with ±
0.1kHz hys.
U
8. Spl.
A017
9
00 -
a019
Multi-speed operation
selection
Select codes:
00...Binary operation (16 speeds
selectable with 4 terminals)
01...Bit operation (8 speeds
selectable with 7
terminals)
U
00 -
A020
Multi-speed freq. 0 Defines the first speed of a
multi-speed profile, range is 0.0
/ start frequency to 400Hz
A020 = Speed 0 (1st motor)
9
0.0 Hz
A220
Multi-speed freq. 0,
2
nd
motor
Defines the first speed of a
multi-speed profile or a 2nd
motor, range is 0.0 / start
frequency to 400Hz
A220 = Speed 0 (2nd motor)
9
0.0 Hz
A021
to
A035
Multi-speed freq. 1 to 15
(for both motors)
Defines 15 more speeds,
range is 0.0 / start frequency to
400 Hz.
A021=Speed 1 ~ A035=Speed15
9
See next
row
Hz
A021 ~ A035
9
0.0 Hz
A038
Jog frequency Defines limited speed for jog,
range is from start frequency to
9.99 Hz
9
6.00 Hz
A039
Jog stop mode Define how end of jog stops the
motor; six options:
00Free-run stop (invalid
during run)
01Controlled deceleration
(invalid during run)
02DC braking to stop(invalid
during run)
03Free-run stop (valid during
run)
04Controlled deceleration
(valid during run)
05DC braking to stop(valid
during run)
U
04
A041
Torque boost select Two options:
00Manual torque boost
U
00
C5
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A241
Torque boost select, 2
nd
motor
01Automatic torque boost
U
00
A042
Manual torque boost value Can boost starting torque
between 0 and 20% above
normal V/f curve,
range is 0.0 to 20.0%
9
1.0 %
A242
Manual torque boost value,
2
nd
motor
9
1.0 %
A043
Manual torque boost
frequency
Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque boost,
range is 0.0 to 50.0%
9
5.0 %
A243
Manual torque boost
frequency,
2
nd
motor
9
5.0 %
A044
V/f characteristic curve Six available V/f curves;
00Constant torque
01Reduced torque (1.7)
02Free V/F
03Sensorless vector (SLV)
U
00
A244
V/f characteristic curve,
2
nd
motor
U
00
A045
V/f gain Sets voltage gain of the
inverter, range is 20. to 100.%
9
100. %
A245
V/f gain, 2
nd
motor
9
100. %
a046
Voltage compensation gain
for automatic torque boost
Sets voltage compensation gain
under automatic torque boost,
range is 0. to 255.
9
100.
a246
Voltage compensation gain
for automatic torque boost,
2
nd
motor
9
100.
a047
Slip compensation gain for
automatic torque boost
Sets slip compensation gain
under automatic torque boost,
range is 0. to 255.
9
100.
a247
Slip compensation gain for
automatic torque boost, 2
nd
motor
9
100.
A051
DC braking enable Three options; select codes:
00Disable
01Enable during stop
02Frequency detection
U
00
A052
DC braking frequency The frequency at which DC
braking begins,
range is from the start
frequency (B082) to 60Hz
U
0.5 Hz
A053
DC braking wait time The delay from the end of
controlled deceleration to start
of DC braking (motor free runs
until DC braking begins),
range is 0.0 to 5.0 sec.
U
0.0 sec.
A054
DC braking force for
deceleration
Level of DC braking force,
settable from 0 to 100%
U
50. %
C6
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A055
DC braking time for
deceleration
Sets the duration for DC
braking, range is from 0.0 to
60.0 seconds
U
0.5 sec.
A056
DC braking / edge or level
detection for [DB] input
Two options; select codes:
00Edge detection
01Level detection
U
01
a057
DC braking force at start Level of DC braking force at
start, settable from 0 to 100%
U
0. %
a058
DC braking time at start Sets the duration for DC
braking, range is from 0.0 to
60.0 seconds
U
0.0 sec.
a059
Carrier frequency during DC
braking
Carrier frequency of DC
braking performance, range is
from 2.0 to 15.0kHz
U
5.0 sec.
A061
Frequency upper limit Sets a limit on output
frequency less than the
maximum frequency (A004).
Range is from frequency lower
limit (A062) to maximum
frequency (A004).
0.0 setting is disabled
>0.0 setting is enabled
U
0.00 Hz
A261
Frequency upper limit,
2nd motor
Sets a limit on output
frequency less than the
maximum frequency (A204).
Range is from frequency lower
limit (A262) to maximum
frequency (A204).
0.0 setting is disabled
>0.0 setting is enabled
U
0.00 Hz
A062
Frequency lower limit Sets a limit on output
frequency greater than zero.
Range is start frequency (B082)
to frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled
U
0.00 Hz
A262
Frequency lower limit,
2nd motor
Sets a limit on output
frequency greater than zero.
Range is start frequency (B082)
to frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled
U
0.00 Hz
A063
A065
A067
Jump freq. (center) 1 to 3 Up to 3 output frequencies can
be defined for the output to
jump past to avoid motor
resonances (center frequency)
Range is 0.0 to 400.0 Hz
U
0.0
0.0
0.0
Hz
A064
A066
A068
Jump freq. width (hysteresis)
1 to 3
Defines the distance from the
center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz
U
0.5
0.5
0.5
Hz
A069
Acceleration hold frequency Sets the frequency to hold
acceleration, range is 0.0 to
400.0Hz
U
0.00 Hz
C7
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A070
Acceleration hold time Sets the duration of
acceleration hold, range is 0.0
to 60.0 seconds
U
0.0 sec.
A071
PID enable Enables PID function,
three option codes:
00PID Disable
01PID Enable
02PID Enable with reverse
output
U
00
A072
PID proportional gain Proportional gain has a range
of 0.00 to 25.00
9
1.0
A073
PID integral time constant Integral time constant has a
range of 0.0 to 3600 seconds
9
1.0 sec
A074
PID derivative time constant Derivative time constant has a
range of 0.0 to 100 seconds
9
0.00 sec
A075
PV scale conversion Process Variable (PV), scale
factor (multiplier), range of 0.01
to 99.99
U
1.00
A076
PV source Selects source of Process
Variable (PV), option codes:
00[OI] terminal (current in)
01[O] terminal (voltage in)
02ModBus network
03Pulse train input
10Calculate function output
U
00
A077
Reverse PID action Two option codes:
00PID input = SP-PV
01PID input = -(SP-PV)
U
00
A078
PID output limit Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0%
U
0.0 %
a079
PID feed forward selection Selects source of feed forward
gain, option codes:
00Disabled
01[O] terminal (voltage in)
02[OI] terminal (current in)
U
00
A081
AVR function select Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
00AVR enabled
01AVR disabled
02AVR enabled except during
deceleration
U
02
a281
AVR function select,
2
nd
motor
U
02
A082
AVR voltage select 200V class inverter settings:
……200/215/220/230/240
400V class inverter settings:
……380/400/415/440/460/480
U
200/
400
V
a282
AVR voltage select,
2
nd
motor
U
200/
400
V
a083
AVR filter time constant Define the time constant of the
AVR filter, range is 0 to 10 sec.
U
0.300 sec
C8
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
a084
AVR deceleration gain Gain adjustment of the braking
performance, range is 50 to
200%
U
100. %
A085
Energy-saving operation
mode
Two option codes:
00Normal operation
01Energy-saving operation
U
00
A086
Energy-saving mode tuning Range is 0.0 to 100 %.
U
50.0 %
A092
Acceleration time (2) Duration of 2
nd
segment of
acceleration, range is:
0.01 to 3600 sec.
9
10.00 sec
A292
Acceleration time (2),
2
nd
motor
9
10.00 sec
A093
Deceleration time (2) Duration of 2
nd
segment of
deceleration, range is:
0.01 to 3600 sec.
9
10.00 sec
A293
Deceleration time (2),
2
nd
motor
9
10.00 sec
A094
Select method to switch to
Acc2/Dec2 profile
Three options for switching
from 1st to 2nd accel/decel:
002CH input from terminal
01Transition frequency
02Forward and reverse
U
00
A294
Select method to switch to
Acc2/Dec2 profile, 2
nd
motor
U
00
A095
Acc1 to Acc2 frequency
transition point
Output frequency at which
Accel1 switches to Accel2, range
is 0.0 to 400.0 Hz
U
0.0 Hz
A295
Acc1 to Acc2 frequency
transition point, 2
nd
motor
U
0.0 Hz
A096
Dec1 to Dec2 frequency
transition point
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 400.0 Hz
U
0.0 Hz
A296
Dec1 to Dec2 frequency
transition point, 2
nd
motor
U
0.0 Hz
A097
Acceleration curve selection Set the characteristic curve of
Acc1 and Acc2, five options:
00linear
01S-curve
02U-curve
03Inverse U-curve
04EL S-curve
U
00
A098
Deceleration curve selection Set the characteristic curve of
Dec1 and Dec2, options are
same as above (a097)
U
00
A101
[OI] input active range start
frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
U
0.00 Hz
A102
[OI] input active range end
frequency
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
U
0.0 Hz
C9
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A103
[OI] input active range start
current
The starting point (offset) for
the current input range,
range is 0. to 100.%
U
20. %
A104
[OI] input active range end
current
The ending point (offset) for the
current input range,
range is 0. to 100.%
U
100. %
A105
[OI] input start frequency
select
Two options; select codes:
00Use offset (A101 value)
01Use 0Hz
U
00
a131
Acceleration curve constant Range is 01 to 10.
U
02
a132
Deceleration curve constant Range is 01 to 10.
U
02
A141
A input select for calculate
function
Seven options:
00Operator
01VR
02Terminal [O] input
03Terminal [OI] input
04RS485
05Option
07Pulse train input
U
02
A142
B input select for calculate
function
Seven options:
00Operator
01VR
02Terminal [O] input
03Terminal [OI] input
04RS485
05Option
07Pulse train input
U
03
A143
Calculation symbol Calculates a value based on the
A input source (A141 selects)
and B input source (A142
selects).
Three options:
00ADD (A input + B input)
01SUB (A input - B input)
02MUL (A input * B input)
U
00
A145
ADD frequency An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
9
0.00 Hz
A146
ADD direction select Two options:
00Plus (adds A145 value to
the output frequency
setting)
01Minus (subtracts A145
value from the output
frequency setting)
U
00
a150
Curvature of EL-S-curve at
the start of acceleration
Range is 0 to 50%
U
10. %
C10
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
a151
Curvature of EL-S-curve at
the end of acceleration
Range is 0 to 50%
U
10. %
a152
Curvature of EL-S-curve at
the start of deceleration
Range is 0 to 50%
U
10. %
a153
Curvature of EL-S-curve at
the end of deceleration
Range is 0 to 50%
U
10. %
a154
Deceleration hold frequency Sets the frequency to hold
deceleration, range is 0.0 to
400.0Hz
U
0.0 Hz
a155
Deceleration hold time Sets the duration of
deceleration hold, range is 0.0
to 60.0 seconds
U
0.0 sec.
a156
PID sleep function action
threshold
Sets the threshold for the
action, set range 0.0~400.0 Hz
U
0.00 Hz
a157
PID sleep function action
delay time
Sets the delay time for the
action, set range 0.0~25.5 sec
U
0.0 sec
A161
[VR] input active range start
frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
U
0.00 Hz
A162
[VR] input active range end
frequency
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
U
0.00 Hz
A163
[VR] input active range
start %
The starting point (offset) for
the current input range,
range is 0. to 100.%
U
0. %
A164
[VR] input active range
end %
The ending point (offset) for the
current input range,
range is 0. to 100.%
U
100. %
A165
[VR] input start frequency
select
Two options; select codes:
00Use offset (A161 value)
01Use 0Hz
U
01
C11
Fine Tuning Functions
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B001
Restart mode on power
failure / under-voltage trip
Select inverter restart method,
Five option codes:
00Alarm output after trip, no
automatic restart
01Restart at 0Hz
02Resume operation after
frequency matching
03Resume previous freq. after
freq. matching, then
decelerate to stop and display
trip info
04Resume operation after active
freq. matching
U
00
B002
Allowable under-voltage
power failure time
The amount of time a power input
under-voltage can occur without
tripping the power failure alarm.
Range is 0.3 to 25 sec. If
under-voltage exists longer than
this time, the inverter trips, even
if the restart mode is selected.
U
1.0 sec.
B003
Retry wait time before motor
restart
Time delay after under-voltage
condition goes away, before the
inverter runs motor again.
Range is 0.3 to 100 seconds.
U
1.0 sec.
B004
Instantaneous power failure /
under-voltage trip alarm
enable
Three option codes:
00Disable
01Enable
02Disable during stop and
decelerates to a stop
U
00
B005
Number of restarts on power
failure / under-voltage trip
events
Two option codes:
00Restart 16 times
01Always restart
U
00
b007
Restart frequency threshold Restart the motor from 0Hz if the
frequency becomes less than this
set value during the motor is
coasting, range is 0 to 400Hz
U
0.00 Hz
b008
Restart mode on over voltage
/ over current trip
Select inverter restart method,
Five option codes:
00Alarm output after trip, no
automatic restart
01Restart at 0Hz
02Resume operation after
frequency matching
03Resume previous freq. after
active freq. matching, then
decelerate to stop and display
trip info
04Resume operation after active
freq. matching
U
00
b010
Number of retry on over
voltage / over current trip
Range is 1 to 3 times
U
3
times
C12
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
b011
Retry wait time on over
voltage / over current trip
Range is 0.3 to 100 sec.
U
1.0 sec
B012
Level of electronic thermal Set a level between 20% and 100%
for the rated inverter current.
U
Rated
current for
each
inverter
model *1
A
B212
Level of electronic thermal,
2
nd
motor
U
A
B013
Electronic thermal
characteristic
Select from three curves, option
codes:
00Reduced torque
01Constant torque
02Free setting
U
01
B213
Electronic thermal
characteristic, 2
nd
motor
U
01
b015
Free setting electronic
thermal ~freq.1
Range is 0 to 400Hz
U
0.0 Hz
b016
Free setting electronic
thermal ~current1
Range is 0 to inverter rated
current Amps
U
0.00
Amps
b017
Free setting electronic
thermal ~freq.2
Range is 0 to 400Hz
U
0.0 Hz
b018
Free setting electronic
thermal ~current2
Range is 0 to inverter rated
current Amps
U
0.00
Amps
b019
Free setting electronic
thermal ~freq.3
Range is 0 to 400Hz
U
0.0 Hz
b020
Free setting electronic
thermal ~current3
Range is 0 to inverter rated
current Amps
U
0.00
Amps
B021
Overload restriction
operation mode
Select the operation mode during
overload conditions, four options,
option codes:
00Disabled
01Enabled for acceleration and
constant speed
02Enabled for constant speed
only
03Enabled for acceleration and
constant speed, increase speed
at regen.
U
01
B221
Overload restriction
operation mode, 2
nd
motor
U
01
B022
Overload restriction level Sets the level of overload
restriction, between 20% and 200%
of the rated current of the inverter,
setting resolution is 1% of rated
current
U
Rated
current
x 1.5
Amps
B222
Overload restriction level,
2
nd
motor
U
Rated
current
x 1.5
Amps
B023
Deceleration rate at overload
restriction
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
U
1.0 sec.
B223
Deceleration rate at overload
restriction, 2
nd
motor
U
1.0 sec.
C13
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
b024
Overload restriction
operation mode 2
Select the operation mode during
overload conditions, four options,
option codes:
00Disabled
01Enabled for acceleration and
constant speed
02Enabled for constant speed
only
03Enabled for acceleration and
constant speed, increase speed
at regen.
U
01
b025
Overload restriction level 2 Sets the level of overload
restriction, between 20% and 200%
of the rated current of the inverter,
setting resolution is 1% of rated
current
U
Rated
current
x 1.5
b026
Deceleration rate 2 at
overload restriction
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
U
1.0 sec.
b027
OC suppression selection * Two option codes:
00Disabled
01Enabled
U
01
B028
Current level of active freq.
matching
Sets the current level of active
freq. matching restart, range is
0.1*inverter rated current to
2.0*inverter rated current,
resolution 0.1
U
Rated
current
A
B029
Deceleration rate of active
freq. matching
Sets the deceleration rate when
active freq. matching restart,
range is 0.1 to 3000.0, resolution
0.1
U
0.5 sec.
B030
Start freq. of active freq.
matching
Three option codes:
00freq at previous shutoff
01start from max. Hz
02start from set frequency
U
00
B031
Software lock mode selection Prevents parameter changes, in
five options, option codes:
00all parameters except B031 are
locked when [SFT] terminal is
ON
01all parameters except B031
and output frequency F001 are
locked when [SFT] terminal is
ON
02all parameters except B031 are
locked
03all parameters except B031
and output frequency F001 are
locked
10High level access including
B031
See appendix C for the accessible
parameters in this mode.
U
01
B033
Motor cable length
parameter
Set range is 5 to 20.
U
10.
C14
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
b034
Run/power ON warning time Range is,
0.:Warning disabled
1. to 9999.:
10~99,990 hrs (unit: 10)
1000 to 6553:
100,000~655,350 hrs (unit: 100)
U
0.
Hrs.
B035
Rotation direction restriction Three option codes:
00No restriction
01Reverse rotation is restricted
02Forward rotation is restricted
U
00
b036
Reduced voltage start
selection
Set range, 0 (disabling the
function), 1 (approx. 6ms) to 255
(approx. 1.5s)
U
2
b037
Function code display
restriction
Seven option codes:
00Full display
01Function-specific display
02User setting (and b037)
03Data comparison display
04Basic display
05Monitor display only
U
04
b038
Initial display selection
000Func. code that SET key
pressed last displayed.(*)
001~030d001~d030 displayed
201F001 displayed
202B display of LCD operator
U
001
B039
Automatic user parameter
registration
Two option codes:
00Disable
01Enable
U
00
B040
Torque limit selection Four option codes:
00Quadrant-specific setting
mode
01Terminal-switching mode
02Analog voltage input mode(O)
U
00
B041
Torque limit 1 (fwd/power) Torque limit level in forward
powering quadrant, range is 0 to
200%/no(disabled)
U
200 %
b042
B043
Torque limit 3 (rev/power) Torque limit level in reverse
powering quadrant, range is 0 to
200%/no(disabled)
U
200 %
B044
Torque limit 4 (fwd/regen.) Torque limit level in forward
regen. quadrant, range is 0 to
200%/no(disabled)
U
200 %
b045
Torque LAD STOP selection Two option codes:
00Disable
01Enable
U
00
b046
Reverse run protection Two option codes:
00No protection
01Reverse rotation is protected
U
01
b049
Dual Rating Selection
00 (CT mode) / 01 (VT mode)
U
00
C15
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B050
Controlled deceleration on
power loss
Four option codes:
00Trips
01Decelerates to a stop
02Decelerates to a stop with DC
bus voltage controlled
03Decelerates to a stop with DC
bus voltage controlled, then
restart
U
00
B051
DC bus voltage trigger level
of ctrl. decel.
Setting of DC bus voltage to start
controlled decel. operation. Range
is 0.0 to 1000.0
U
220.0/
440.0
V
B052
Over-voltage threshold of
ctrl. decel.
Setting the OV-LAD stop level of
controlled decel. operation. Range
is 0.0 to 1000.0
U
360.0/
720.0
V
B053
Deceleration time of ctrl.
decel.
Range is 0.01 to 3600.0
U
1.0 sec
B054
Initial freq. drop of ctrl.
decel.
Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
U
0.0 Hz
B060
Maximum-limit level of
window comparator (O)
Set range, {Min.-limit level (b061)
+ hysteresis width (b062)x2} to
100 %
(Minimum of 0%)
U
100. %
B061
Minimum-limit level of
window comparator (O)
Set range, 0 to {Max.-limit level
(b060) - hysteresis width
(b062)x2} % (Maximum of 0%)
9
0. %
B062
Hysteresis width of window
comparator (O)
Set range, 0 to {Max.-limit level
(b060) - Min.-limit level (b061)}/2 %
(Maximum of 10%)
9
0. %
B063
Maximum-limit level of
window comparator (OI)
Set range, {Min.-limit level (b064 +
hysteresis width (b065)x2} to
100 %
(Minimum of 0%)
9
100. %
B064
Minimum-limit level of
window comparator (OI)
Set range, 0 to {Max.-limit level
(b063) - hysteresis width
(b065)x2} % (Maximum of 0%)
9
0. %
b065
Hysteresis width of window
comparator (OI)
Set range, 0 to {Max.-limit level
(b063) - Min.-limit level (b064)}/2 %
(Maximum of 10%)
9
0. %
b070
Operation level at O
disconnection
Set range, 0 to 100%, or “no”
(ignore)
U
no -
b071
Operation level at OI
disconnection
Set range, 0 to 100%, or “no”
(ignore)
U
no -
b075
Ambient temperature setting Set range is,
-10~50 °C
9
40
°C
B078
Watt-hour clearance Two option codes:
00OFF
01ON (press STR then clear)
9
00 -
b079
Watt-hour display gain Set range is,
1.~1000.
9
1.
B082
Start frequency Sets the starting frequency for the
inverter output, range is 0.10 to
9.99 Hz
U
0.50 Hz
B083
Carrier frequency Sets the PWM carrier (internal
switching frequency), range is 2.0
to 15.0 kHz
U
2.0 kHz
C16
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B084
Initialization mode
(parameters or trip history)
Select initialized data, five option
codes:
00Initialization disabled
01Clears Trip history
02Initializes all Parameters
03Clears Trip history and
initializes all parameters
04Clears Trip history and
initializes all parameters and
EzSQ program
U
00
B085
Country for initialization Select default parameter values
for country on initialization, two
option codes:
00area A 01area B
U
00
B086
Frequency scaling conversion
factor
Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.01 to 99.99
U
1.00
B087
STOP key enable Select whether the STOP key on
the keypad is enabled, three option
codes:
00Enabled
01Disabled always
02 Disabled for stop
U
00
B088
Restart mode after FRS Selects how the inverter resumes
operation when free-run stop
(FRS) is cancelled, three options:
00Restart from 0Hz
01Restart from frequency
detected from real speed of
motor (freq. matching)
02Restart from frequency
detected from real speed of
motor (active freq. matching)
U
00
b089
Automatic carrier frequency
reduction
Three option codes:
00Disabled
01Enabled, depending on the
output current
02Enabled, depending on the
heat-sink temperature
U
01 -
b090
Dynamic braking usage ratio Selects the rate of use (in %) of the
regenerative braking resistor per
100 sec. intervals, range is 0.0 to
100%.
0%: Function disabled
>0%: Enabled, per value
U
0.0 %
B091
Stop mode selection Select how the inverter stops the
motor, two option codes:
00DEC (decelerate to stop)
01FRS (free-run to stop)
U
00
C17
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B092
Cooling fan control Selects when the fan is ON during
inverter operation, four options:
00Fan is always ON
01Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
02Fan is temperature controlled
U
01 -
B093
Clear elapsed time of cooling
fan
Two option codes:
00Count
01Clear
U
00 -
b094
Initialization target data Select initialized parameters, four
option codes:
00All parameters
01All parameters except
in/output terminals and
communication.
02Only registered parameters in
Uxxx.
03All parameters except
registered parameters in Uxxx
and b037.
U
00 -
b095
Dynamic braking control
(BRD) selection
Three option codes:
00Disable
01Enable during run only
02Enable always
U
01 -
b096
BRD activation level Range is:
330 to 380V (200V class)
660 to 760V (400V class)
U
360/
720
V
B100
Free V/F setting, freq.1 Set range, 0 ~ value of b102
U
0. Hz
b101
Free V/F setting, voltage.1 Set range, 0 ~ 800V
U
0.0 V
b102
Free V/F setting, freq.2 Set range, value of b100 ~b104
U
0. Hz
b103
Free V/F setting, voltage.2 Set range, 0 ~ 800V
U
0.0 V
b104
Free V/F setting, freq.3 Set range, value of b102 ~b106
U
0. Hz
b105
Free V/F setting, voltage.3 Set range, 0 ~ 800V
U
0.0 V
b106
Free V/F setting, freq.4 Set range, value of b104 ~b108
U
0. Hz
b107
Free V/F setting, voltage.4 Set range, 0 ~ 800V
U
0.0 V
b108
Free V/F setting, freq.5 Set range, value of b108 ~b110
U
0. Hz
b109
Free V/F setting, voltage.5 Set range, 0 ~ 800V
U
0.0 V
b110
Free V/F setting, freq.6 Set range, value of b108 ~b112
U
0. Hz
b111
Free V/F setting, voltage.6 Set range, 0 ~ 800V
U
0.0 V
b112
Free V/F setting, freq.7 Set range, b110 ~ 400
U
0. Hz
b113
Free V/F setting, voltage.7 Set range, 0 ~ 800V
U
0.0 V
C18
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B120
Brake control enable Two option codes:
00Disable
01Enable
U
00 -
b121
Brake Wait Time for Release Set range: 0.00 to 5.00 sec
U
0.00 Sec
b122
Brake Wait Time for
Acceleration
Set range: 0.00 to 5.00 sec
U
0.00 Sec
b123
Brake Wait Time for
Stopping
Set range: 0.00 to 5.00 sec
U
0.00 Sec
b124
Brake Wait Time for
Confirmation
Set range: 0.00 to 5.00 sec
U
0.00 Sec
b125
Brake release freq. Set range: 0 to 400Hz
U
0.00 Sec
b126
Brake release current Set range: 0~200% of inverter
rated current
U
(rated
current)
A
b127
Braking freq. setting Set range: 0 to 400Hz
U
0.00 Hz
B130
Deceleration overvoltage
suppression enable
00Disabled
01Enabled
02Enabled with accel.
U
00
B131
Decel. overvolt. suppress
level
DC bus voltage of suppression.
Range is:
200V class330 to 395
400V class660 to 790
U
380
/760
V
b132
Decel. overvolt. suppress
const.
Accel. rate when b130=02.
Set range: 0.10 ~ 30.00 sec.
U
1.00 sec
B133
Decel. overvolt. suppress
proportional gain
Proportional gain when b130=01.
Range is: 0.00 to 5.00
9
0.20
B134
Decel. overvolt. suppress
integral time
Integration time when b130=01.
Range is: 0.00 to 150.0
9
1.0 sec
b145
GS input mode Two option codes:
00No trip (Hardware shutoff
only)
01Trip
U
00 -
b150
Display ex.operator
connected
When an external operator is
connected via RS-422 port, the
built-in display is locked and shows
only one "d" parameter configured
in:
d001 ~ d030
U
001
b160
1st parameter of Dual
Monitor
Set any two "d" parameters in b160
and b161, then they can be
monitored in d050. The two
parameters are switched by
up/down keys.
Set range: d001 ~ d030
U
001
b161
2nd parameter of Dual
Monitor
U
002
b163
Frequency set in monitoring Two option codes:
00Freq. set disabled
01Freq. set enabled
9
00 -
C19
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
b164
Automatic return to the
initial display
10 min. after the last key
operation, display returns to the
initial parameter set by b038. Two
option codes:
00Disable
01Enable
9
00 -
b165
Ex. operator com. loss action Five option codes:
00Trip
01Trip after deceleration to a
stop
02Ignore
03Coasting (FRS)
04Decelerates to a stop
9
02 -
b171
Inverter mode selection Three option codes:
00No function
01Std. IM (Induction Motor)
03PM(Permanent Magnet
Motor)
U
00 -
b180
Initialization trigger
(*)
This is to perform initialization by
parameter input with b084, b085
and b094. Two option codes:
00Initialization disable
01Perform initialization
U
00 -
b190
Password Settings A
0000(Invalid Password)
0001-FFFF(Password)
U
0000 -
b191
Password authentication A 0000-FFFF
U
0000 -
b192
Password Settings B 0000(Invalid Password)
0001-FFFF(Password)
U
0000 -
b193
Password authentication B 0000-FFFF
U
0000 -
C20
Intelligent Terminal Functions
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
C001
Input [1] function Select input terminal [1] function,
68 options (see next section)
U
00
[FW]
C002
Input [2] function Select input terminal [2] function,
68 options (see next section)
U
01
[RV]
C003
Input [3] function
[GS1 assignable]
Select input terminal [3] function,
68 options (see next section)
U
02
[CF1]
C004
Input [4] function
[GS2 assignable]
Select input terminal [4] function,
68 options (see next section)
U
03
[CF2]
C005
Input [5] function
[PTC assignable]
Select input terminal [5] function,
68 options (see next section)
U
09
[2CH]
C006
Input [6] function Select input terminal [6] function,
68 options (see next section)
U
18
[RS]
C007
Input [7] function Select input terminal [7] function,
68 options (see next section)
U
13
[USP]
C011
Input [1] active state Select logic conversion, two option
codes:
00normally open [NO]
01normally closed [NC]
U
00
C012
Input [2] active state
U
00
C013
Input [3] active state
U
00
C014
Input [4] active state
U
00
C015
Input [5] active state
U
00
C016
Input [6] active state
U
00
C017
Input [7] active state
U
00
C021
Output [11] function
[EDM assignable]
48 programmable functions
available for logic (discrete)
outputs
(see next section)
U
01
[FA1]
C022
Output [12] function
U
00
[RUN]
C026
Alarm relay function
48 programmable functions available
for logic (discrete) outputs
(see next section)
U
05
[AL]
C027
[EO] terminal selection
(Pulse/PWM output)
13 programmable functions:
00Output frequency (PWM)
01Output current (PWM)
02Output torque (PWM)
03Output frequency (Pulse train)
04Output voltage (PWM)
05Input power (PWM)
06Electronic thermal load ratio
(PWM)
07LAD frequency (PWM)
08Output current (Pulse train)
10Heat sink temperature (PWM)
12General output (PWM)
15Pulse train input monitor
16Option(PWM)
U
07
C21
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
C028
[AM] terminal selection
(Analog voltage output
0...10V)
11 programmable functions:
00Output frequency
01Output current
02Output torque
04Output voltage
05Input power
06Electronic thermal load ratio
07LAD frequency
10Heat sink temperature
11Output torque (with code)
13General output
16Option
U
07
[LAD]
C030
Digital current monitor
reference value
Current with digital current
monitor output at 1,440Hz
Range is 20%~200% of rated
current
9
Rated
current
A
C031
Output [11] active state Select logic conversion, two option
codes:
00normally open [NO]
01normally closed [NC]
U
00
C032
Output [12] active state
U
00 -
C036
Alarm relay active state
U
01
C038
Output mode of low
current detection
Two option codes:
00During acceleration,
deceleration and constant speed
01During constant speed only
U
01
C039
Low current detection
level
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
U
INV rated
current
A
C040
Output mode of overload
warning
Two option codes:
00During accel., decel. and
constant speed
01During constant speed only
U
01
C041
Overload warning level Sets the overload warning signal
level between 0% and 200% (from 0
to two time the rated current of the
inverter)
U
Rated
current
x 1.15
A
C241
Overload warning level,
2
nd
motor
Sets the overload warning signal
level between 0% and 200% (from 0
to two time the rated current of the
inverter)
U
Rated
current
x 1.15
A
C042
Frequency arrival setting
for acceleration
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
U
0.0 Hz
C043
Frequency arrival setting
for deceleration
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
U
0.0 Hz
C044
PID deviation level Sets the allowable PID loop error
magnitude (absolute value), SP-PV,
range is 0.0 to 100%
U
3.0 %
C045
Frequency arrival setting
2 for acceleration
Set range is 0.0 to 400.0 Hz
U
0.00 Hz
C046
Frequency arrival setting
2 for deceleration
Set range is 0.0 to 400.0 Hz
U
0.00 Hz
C22
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
C047
Pulse train input/output
scale conversion
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in × (C047)
Set range is 0.01 to 99.99
9
1.00
C052
PID FBV output
high limit
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0 to
100%
U
100.0 %
C053
PID FBV output
low limit
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
U
0.0 %
C054
Over-torque/under-torque
selection
Two option codes:
00Over-torque
01Under-torque
U
00 -
C055
Over/under-torque level
(Forward powering mode)
Set range is 0 to 200%
U
100. %
C056
Over/under-torque level
(Reverse regen. mode)
Set range is 0 to 200%
U
100. %
C057
Over/under-torque level
(Reverse powering mode)
Set range is 0 to 200%
U
100. %
C058
Over/under-torque level
(Forward regen. mode)
Set range is 0 to 200%
U
100. %
C059
Signal output mode of
Over/under-torque
Two option codes:
00During accel., decel. and
constant speed
01During constant speed only
U
01 -
C061
Electronic thermal
warning level
Set range is 0 to 100%
Setting 0 means disabled.
U
90 %
C063
Zero speed detection level Set range is 0.0 to 100.0Hz
U
0.00 Hz
C064
Heat sink overheat
warning
Set range is 0 to 110 °C
U
100.
°C
C071
Communication speed Eight option codes:
032,400 bps
044,800 bps
059,600 bps
0619,200 bps
0738,400 bps
0857,600 bps
0976,800 bps
10115,200 bps
U
05 baud
C072
Modbus address Set the address of the inverter on
the network. Range is 1 to 247
U
1.
C074
Communication parity Three option codes:
00No parity
01Even parity
02Odd parity
U
00
C075
Communication stop bit Two option codes:
11 bit
22 bit
U
1 bit
C23
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
C076
Communication error
select
Selects inverter response to
communications error.
Five options:
00Trip
01Decelerate to a stop and trip
02Disable
03Free run stop (coasting)
04Decelerates to a stop
U
02
C077
Communication error
time-out
Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 sec
0.0 = disabled
U
0.00 sec.
C078
Communication wait time Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms
U
0. msec.
C081
O input span calibration Scale factor between the external
frequency command on terminals
L–O (voltage input) and the
frequency output,
range is 0.0 to 200%
9
100.0 %
C082
OI input span calibration Scale factor between the external
frequency command on terminals
L–OI (voltage input) and the
frequency output,
range is 0.0 to 200%
9
100.0 %
C085
Thermistor input (PTC)
span calibration
Scale factor of PTC input.
Range is 0.0 to 200%
9
100.0 %
C091
Debug mode enable * Displays debug parameters.
Two option codes:
00Disable
01Enable <Do not set>
(for factory use)
9
00
C096
Communication selection
00Modbus-RTU
01 EzCOM
02 EzCOM<administrator>
U
00
C098
EzCOM start adr. of
master
01-08
U
01
C099
EzCOM end adr. of
master
01-08
U
01
C100
EzCOM starting trigger
00 Input terminal
01 Always
U
00
C101
Up/Down memory mode
selection
Controls speed setpoint for the
inverter after power cycle.
Two option codes:
00Clear last frequency (return to
default frequency F001)
01Keep last frequency adjusted
by UP/DWN
U
00
C24
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
C102
Reset selection Determines response to Reset
input [RS].
Four option codes:
00Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01Cancel trip state at signal
OFF transition, stops inverter
if in Run Mode
02Cancel trip state at input ON
transition, no effect if in Run
Mode
03Clear the memories only
related to trip status
U
00
C103
Restart mode after reset Determines the restart mode after
reset is given, three option codes:
00Start with 0 Hz
01Start with freq. matching
02Start with active freq.
matching
U
00 -
C104
UP/DWN clear mode Freq. set value when UDC signal is
given to the input terminal, two
option codes:
000 Hz
01Original setting (in the
EEPROM memory at power
on)
U
00 -
C105
EO gain adjustment Set range is 50 to 200%
9
100. %
C106
AM gain adjustment Set range is 50 to 200%
9
100. %
C109
AM bias adjustment Set range is 0 to 100%
9
0. %
C111
Overload warning level 2 Sets the overload warning signal
level between 0% and 200% (from 0
to two time the rated current of the
inverter)
9
Rated
current
x 1.15
A
C130
Output [11] on delay Set range is 0.0 to 100.0 sec.
U
0.0 Sec.
C131
Output [11] off delay
U
0.0 Sec.
C132
Output [12] on delay Set range is 0.0 to 100.0 sec.
U
0.0 Sec.
C133
Output [12] off delay
U
0.0 Sec.
C140
Relay output on delay Set range is 0.0 to 100.0 sec.
U
0.0 Sec.
C141
Relay output off delay
U
0.0 Sec.
C142
Logic output 1 operand A
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
U
00
C143
Logic output 1 operand B
U
00
C144
Logic output 1 operator Applies a logic function to calculate
[LOG] output state,
Three options:
00[LOG] = A AND B
01[LOG] = A OR B
02[LOG] = A XOR B
U
00
C145
Logic output 2 operand A
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
U
00
C146
Logic output 2 operand B
U
00
C25
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
C147
Logic output 2 operator Applies a logic function to calculate
[LOG] output state,
Three options:
00[LOG] = A AND B
01[LOG] = A OR B
02[LOG] = A XOR B
U
00
C148
Logic output 3 operand A
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
U
00
C149
Logic output 3 operand B
U
01
C150
Logic output 3 operator Applies a logic function to calculate
[LOG] output state,
Three options:
00[LOG] = A AND B
01[LOG] = A OR B
02[LOG] = A XOR B
U
00
C160
Input [1] response time Sets response time of each input
terminal, set range:
0 (x 2 [ms]) to 200 (x 2 [ms])
(0 to 400 [ms])
U
1.
C161
Input [2] response time
U
1.
C162
Input [3] response time
U
1.
C163
Input [4] response time
U
1.
C164
Input [5] response time
U
1.
C165
Input [6] response time
U
1.
C166
Input [7] response time
U
1.
C169
Multistage speed/position
determination time
Set range is 0. to 200. (x 10ms)
U
0. ms
Motor Constants Functions
“H” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
H001
Auto-tuning selection Three option codes:
00Disabled
01Enabled with motor stop
02Enabled with motor rotation
U
00 -
H002
Motor constant selection Four option codes:
00Hitachi standard motor
02Auto tuned data
U
00 -
H202
Motor constant selection,
2
nd
motor
U
00 -
H003
Motor capacity Eleven selections:
0.1/0.2/0.4/0.75/1.5/2.2/3.7/
5.5/7.5/11/15/18.5
U
Specified by
the capacity
of each
inverter
model
kW
H203
Motor capacity,
2
nd
motor
U
kW
H004
Motor poles setting Four selections:
2 / 4 / 6 / 8 / 10
U
4 poles
H204
Motor poles setting,
2
nd
motor
U
4 poles
C26
“H” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
H005
Motor speed response
constant
Set range is 1 to 1000
9
100. -
H205
Motor speed response
constant, 2
nd
motor
9
100. -
H006
Motor stabilization
constant
Motor constant (factory set),
range is 0 to 255
9
100.
H206
Motor stabilization
constant, 2
nd
motor
9
100.
H020
Motor constant R1
(Hitachi motor)
0.001~65.535 ohms
U
Specified by
the capacity
of each
inverter mode
Ohm
H220
Motor constant R1,
2
nd
motor (Hitachi motor)
U
Ohm
H021
Motor constant R2
(Hitachi motor)
0.001~65.535 ohms
U
Ohm
H221
Motor constant R2,
2
nd
motor (Hitachi motor)
U
Ohm
H022
Motor constant L
(Hitachi motor)
0.01~655.35mH
U
mH
H222
Motor constant L,
2
nd
motor (Hitachi motor)
U
mH
H023
Motor constant I0
(Hitachi motor)
0.01~655.35A
U
A
H223
Motor constant I0,
2
nd
motor (Hitachi motor)
U
A
H024
Motor constant J
(Hitachi motor)
0.001~9999 kgm
2
U
kgm
2
H224
Motor constant J,
2
nd
motor (Hitachi motor)
U
kgm
2
H030
Motor constant R1
(Auto tuned data)
0.001~65.535 ohms
U
Specified by
the capacity
of each
inverter mode
ohm
H230
Motor constant R1,
2
nd
motor (Auto tuned data)
U
ohm
H031
Motor constant R2
(Auto tuned data)
0.001~65.535 ohms
U
ohm
H231
Motor constant R2,
2
nd
motor (Auto tuned data)
U
ohm
H032
Motor constant L
(Auto tuned data)
0.01~655.35mH
U
mH
H232
Motor constant L,
2
nd
motor (Auto tuned data)
U
mH
H033
Motor constant I0
(Auto tuned data)
0.01~655.35A
U
A
H233
Motor constant I0,
2
nd
motor (Auto tuned data)
U
A
H034
Motor constant J
(Auto tuned data)
0.001~9999 kgm
2
U
kgm
2
H234
Motor constant J,
2
nd
motor (Auto tuned data)
U
kgm
2
H050
Slip compensation P gain
for V/f control with FB
0.00-10.00
U
0.2 Times
H051
Slip compensation I gain
for V/f control with FB
0.-1000.
U
2. (s)
Expansion Card Functions
C27
“P” parameters will be appeared when the expansion option is connected.
“P” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
P001
Reaction when option card
error occurs
Two option codes:
00…Inverter trips
01…Ignores the error (Inverter
continues operation)
U
00
-
P003
[EA] terminal selection Three option codes:
00…Speed reference (incl. PID)
01…For control with encoder
feedback
02…Extended terminal for EzSQ
U
00
-
P004
Pulse train input mode
selection for feedback
Four option codes:
00…Single-phase pulse [EA]
01…2-phase pulse (90°
difference) 1 ([EA] and [EB])
02…2-phase pulse (90°
difference) 2 ([EA] and [EB])
03…Single-phase pulse [EA] and
direction signal [EB]
U
00
-
P011
Encoder pulse setting Sets the pulse number (ppr) of
the encoder, set range is 32~1024
pulses
U
512.
-
P012
Simple positioning selection Two option codes:
00…simple positioning
deactivated
01…simple positioning activated
U
00
-
p015
Creep Speed Set range is start frequency
(b082) ~10.00 Hz
U
5.00
Hz
P026
Over-speed error detection
level
Set range is 0~150%
U
115.0
%
P027
Speed deviation error
detection level
Set range is 0~120 Hz
U
10.00
Hz
P031
P033
Torque command input
selection
Six option codes:
00…Analog voltage input [O]
01…Analog current input [OI]
03…Operator, 06…Option
U
00
-
P034
Torque command level input Set range is 0~200%
9
0.
%
p036
Torque bias mode selection Five option codes:
00…No bias
01…Operator
U
00
-
p037
Torque bias value setting Range is –200~200%
9
0.
%
p038
Torque bias polar selection Two option codes:
00…According to the sign
01…According to the rotation
direction
05…Option
U
00
-
p039
Speed limit of Torque control
(Forward rotation)
Set range is 0.00~120.00Hz
9
0.00
Hz
p040
Speed limit of Torque control
(Forward rotation)
Set range is 0.00~120.00Hz
9
0.00
Hz
p041
Speed / Torque control
switching time
Set range is 0 to 1000 ms
U
0.
ms
C28
“P” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
P044
Communication watchdog
timer
(
for option
)
Set range is 0.00 to 99.99s
U
1.00
s
P045
Inverter action on
communication error
(for option)
00 (tripping),
01 (tripping after decelerating
and stopping the motor),
02 (ignoring errors),
03 (stopping the motor after
free-running),
04 (decelerating and stopping the
motor)
U
00
-
P046
DeviceNet polled I/O:
Output instance number
0-20
U
1
-
P048
Inverter action on
communication idle mode
00 (tripping),
01 (tripping after decelerating
and
stopping the motor),
02 (ignoring errors),
03 (stopping the motor after
free-running),
04 (decelerating and stopping the
motor)
U
00
-
P049
Motor poles setting for RPM 0/2/4/6/8/10/12/14/16/18/20/22/24/
26/28/
30/32/34/36/38/40/42/44/46/48
U
0
Poles
p055
Pulse train input frequency
scale setting
Sets the pulse numbers at max.
frequency, set range is 1.0~32.0
kHz
U
25.0
kHz
p056
Pulse train input frequency
filter time constant setting
Set range is 0.01~2.00 sec.
U
0.10
sec
p057
Pulse train input bias
setting
Set range is –100~100 %
U
0.
%
p058
Limitation of the pulse train
input setting
Set range is 0~100 %
U
100.
%
P060
Multistage position 0
P073 to P072
(Displayed higher 4-digits only)
9
0
Pulses
P061
Multistage position 1
9
0
Pulses
P062
Multistage position 2
9
0
Pulses
P063
Multistage position 3
9
0
Pulses
P064
Multistage position 4
9
0
Pulses
P065
Multistage position 5
9
0
Pulses
P066
Multistage position 6
9
0
Pulses
P067
Multistage position 7
9
0
Pulses
P068
Homing mode selection
00…Low speed mode
01…High speed mode
9
00
-
P069
Homing direction
00…Forward rotation side
01…Reverse rotation side
9
01
-
P070
Low speed homing freq. 0 to 10Hz
9
5.00
Hz
P071
High speed homing freq. 0 to 400Hz
9
5.00
Hz
P072
Position range (Forward)
0 to +268435455(Higher 4-digits
displayed)
9
+26843
5455
Pulses
C29
“P” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
P073
Position range (Reverse)
–268435455 to 0(Higher 4-digits
displayed)
9
-268435
455
Pulses
P075
Positioning mode selection
00…With limitation
01…No limitation (shorter route)
P004 is to be set 00 or 01
U
00
-
P077
Encoder disconnection
timeout
0.0 to 10.0 s
9
1.0
s
p100
~
P131
EzSQ user parameter
U(00) ~ U(31)
Each set range is 0~65535
9
0.
-
P140
EzCOM number of data 1 to 5
9
5
-
P141
EzCOM destination 1 adderss 1 to 247
9
1
-
P142
EzCOM destination 1 register 0000 to FFFF
9
0000
-
P143
EzCOM source 1 register 0000 to FFFF
9
0000
-
P144
EzCOM destination 2 adderss 1 to 247
9
2
-
P145
EzCOM destination 2 register 0000 to FFFF
9
0000
-
P146
EzCOM source 2 register 0000 to FFFF
9
0000
-
P147
EzCOM destination 3 adderss 1 to 247
9
3
-
P148
EzCOM destination 3 register 0000 to FFFF
9
0000
-
P149
EzCOM source 3 register 0000 to FFFF
9
0000
-
P150
EzCOM destination 4 adderss 1 to 247
9
4
-
P151
EzCOM destination 4 register 0000 to FFFF
9
0000
-
P152
EzCOM source 4 register 0000 to FFFF
9
0000
-
P153
EzCOM destination 5 adderss 1 to 247
9
5
-
P154
EzCOM destination 5 register 0000 to FFFF
9
0000
-
P155
EzCOM source 5 register 0000 to FFFF
9
0000
-
P160
Option I/F command register
to write 1
0000 to FFFF
9
0000
-
P161
Option I/F command register
to write 2
0000 to FFFF
9
0000
-
P162
Option I/F command register
to write 3
0000 to FFFF
9
0000
-
P163
Option I/F command register
to write 4
0000 to FFFF
9
0000
-
P164
Option I/F command register
to write 5
0000 to FFFF
9
0000
-
P165
Option I/F command register
to write 6
0000 to FFFF
9
0000
-
P166
Option I/F command register
to write 7
0000 to FFFF
9
0000
-
P167
Option I/F command register
to write 8
0000 to FFFF
9
0000
-
P168
Option I/F command register
to write 9
0000 to FFFF
9
0000
-
P169
Option I/F command register
to write 10
0000 to FFFF
9
0000
-
P170
Option I/F command register
to read 1
0000 to FFFF
9
0000
-
P171
Option I/F command register
to read 2
0000 to FFFF
9
0000
-
P172
Option I/F command register
to read 3
0000 to FFFF
9
0000
-
C30
“P” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
P173
Option I/F command register
to read 4
0000 to FFFF
9
0000
-
P174
Option I/F command register
to read 5
0000 to FFFF
9
0000
-
P175
Option I/F command register
to read 6
0000 to FFFF
9
0000
-
P176
Option I/F command register
to read 7
0000 to FFFF
9
0000
-
P177
Option I/F command register
to read 8
0000 to FFFF
9
0000
-
P178
Option I/F command register
to read 9
0000 to FFFF
9
0000
-
P179
Option I/F command register
to read 10
0000 to FFFF
9
0000
-
P180
Profibus Node address 0 to 125
U
0.
-
P181
Profibus Clear Node address
00
01
U
00
-
P182
Profibus Map selection
00
01
U
00
-
D1
CE-EMC
D
Installation
Guidelines
In This Appendix… page
- CE-EMC Installation Guidelines ...................................................... 2
- Hitachi EMC Recommendations ..................................................... 6
D2
CE-EMC Installation Guidelines
You are required to satisfy the EMC directive (2004/108/EC) when using an WJ200 inverter
in an EU country.
To satisfy the EMC directive and to comply with standard, you need to use a dedicated EMC
filter suitable for each model, and follow the guidelines in this section. Following table shows
the compliance condition for reference.
Table 1. Condition for the compliance
Model Cat. Carrier f Motor cable
All WJ200 series C1 2kHz 20m (Shielded)
Table 2. Applicable EMC filter
Input class Inverter model Filter model (Schaffner)
1-ph. 200V class
WJ200-001SFE
FS24828-8-07
WJ200-002SFE
WJ200-004SFE
WJ200-007SFE
FS24828-27-07
WJ200-015SFE
WJ200-022SFE
3-ph. 200V class
WJ200-001LFU
FS24829-8-07
WJ200-002LFU
WJ200-004LFU
WJ200-007LFU
WJ200-015LFU
FS24829-16-07
WJ200-022LFU
WJ200-037LFU FS24829-25-07
WJ200-055LFU
FS24829-50-07
WJ200-075LFU
WJ200-110LFU FS24829-70-07
WJ200-150LFU FS24829-75-07
3-ph. 400V class
WJ200-004HFE
FS24830-6-07
WJ200-007HFE
WJ200-015HFE
FS24830-12-07
WJ200-022HFE
WJ200-030HFE
WJ200-040HFE FS24830-15-07
WJ200-055HFE
FS24830-29-07
WJ200-075HFE
WJ200-110HFE
FS24830-48-07
WJ200-150HFE
WJ200-110L and 150H needs to be installed in a metal cabinet and add ferrite core
at the input cable to meet category C1. Unless otherwise category C2.
Important notes
1. Input choke or other equipment is required if necessary to comply with EMC
directive from the harmonic distortion point of view (IEC 61000-3-2 and 4).
2. If the motor cable length exceeds 20m, use output choke to avoid unexpected
problem due to the leakage current from the motor cable (such as malfunction of
the thermal relay, vibration of the motor, etc..).
D3
3. As user you must ensure that the HF (high frequency) impedance between
adjustable frequency inverter, filter, and ground is as small as possible.
Ensure that the connections are metallic and have the largest possible contact
areas (zinc-plated mounting plates).
4. Avoid conductor loops that act like antennas, especially loops that encompass large
areas.
Avoid unnecessary conductor loops.
Avoid parallel arrangement of low-level signal wiring and power-carrying or
noise-prone conductors.
5. Use shielded wiring for the motor cable and all analog and digital control lines.
Allow the effective shield area of these lines to remain as large as possible; i.e.,
do not strip away the shield (screen) further away from the cable end than
absolutely necessary.
With integrated systems (for example, when the adjustable frequency inverter
is communicating with some type of supervisory controller or host computer in
the same control cabinet and they are connected at the same ground +
PE-potential), connect the shields of the control lines to ground + PE (protective
earth) at both ends. With distributed systems (for example the communicating
supervisory controller or host computer is not in the same control cabinet and
there is a distance between the systems), we recommend connecting the shield
of the control lines only at the end connecting to the adjustable frequency
inverter. If possible, route the other end of the control lines directly to the cable
entry section of the supervisory controller or host computer. The shield
conductor of the motor cables always must connected to ground + PE at both
ends.
To achieve a large area contact between shield and ground + PE-potential, use
a PG screw with a metallic shell, or use a metallic mounting clip.
Use only cable with braided, tinned copper mesh shield (type “CY”) with 85%
coverage.
The shielding continuity should not be broken at any point in the cable. If the
use of reactors, contactors, terminals, or safety switches in the motor output is
necessary, the unshielded section should be kept as short as possible.
Some motors have a rubber gasket between terminal box and motor housing.
Very often, the terminal boxes, and particularly the threads for the metal PG
screw connections, are painted. Make sure there is always a good metallic
connection between the shielding of the motor cable, the metal PG screw
connection, the terminal box, and the motor housing. If necessary, carefully
remove paint between conducting surfaces.
6. Take measures to minimize interference that is frequently coupled in through
installation cables.
Separate interfering cables with 0.25m minimum from cables susceptible to
interference. A particularly critical point is laying parallel cables over longer
distances. If two cables intersect (one crosses over the other), the interference is
smallest if they intersect at an angle of 90°. Cables susceptible to interference
should therefore only intersect motor cables, intermediate circuit cables, or the
wiring of a rheostat at right angles and never be laid parallel to them over
longer distances.
7. Minimize the distance between an interference source and an interference sink
(interference- threatened device), thereby decreasing the effect of the emitted
interference on the interference sink.
You should use only interference-free devices and maintain a minimum
distance of 0.25 m from the adjustable frequency inverter.
D4
8. Follow safety measures in the filter installation.
If using external EMC filter, ensure that the ground terminal (PE) of the filter
is properly connected to the ground terminal of the adjustable frequency
inverter. An HF ground connection via metal contact between the housings of
the filter and the adjustable frequency inverter, or solely via cable shield, is not
permitted as a protective conductor connection. The filter must be solidly and
permanently connected with the ground potential so as to preclude the danger
of electric shock upon touching the filter if a fault occurs.
To achieve a protective ground connection for the filter:
Ground the filter with a conductor of at least 10 mm
2
cross-sectional area.
Connect a second grounding conductor, using a separate grounding terminal
parallel to the protective conductor. (The cross section of each single protective
conductor terminal must be sized for the required nominal load.)
D5
Installation for WJ200 series (example of SFE models)
Model LFx (3-ph. 200V class) and HFx (3-ph. 400V class) are the same concept for the
installation.
*) Both earth portions of the shielded cable must be connected to the earth point by
cable clamps.
Input choke or equipment to reduce harmonic current is necessary for CE marking
(IEC 61000-3-2 and IEC61000-3-4) from the harmonic current point of view, even
conducted emission and radiated emission passed without the input choke.
Shielded cable
Power supply
1-ph. 200V
M
U,V,W
Metal plate (earth)
Earth line is co
heatsink of the inverter
nnected to the
(
or PE terminal for bi
gg
er models
)
The filter is a footprint type, so it is located
between the inverter and the metal plate.
Remove the insulation material coating of the
earth contact portions so to obtain good
g
roundin
g
condition.
PE
EMC filter
(Foot-print)
Cable clamp *
Metal plate (earth)
L1,N
Cable clamp *
D6
Hitachi EMC Recommendations
WARNING: This equipment should be installed, adjusted, and serviced by qualified
personal familiar with construction and operation of the equipment and the hazards
involved. Failure to observe this precaution could result in bodily injury.
Use the following checklist to ensure the inverter is within proper operating ranges
and conditions.
1. The power supply to WJ200 inverters must meet these specifications:
Voltage fluctuation ±10% or less
Voltage imbalance ±3% or less
Frequency variation ±4% or less
Voltage distortion THD = 10% or less
2. Installation measure:
Use a filter designed for WJ200 inverter. Refer to the instruction of the
applicable external EMC filter.
3. Wiring:
Shielded wire (screened cable) is required for motor wiring, and the length must
be 20 meter or less.
If the motor cable length exceeds the value shown above, use output choke to
avoid unexpected problem due to the leakage current from the motor cable.
The carrier frequency setting must be 2 kHz to satisfy EMC requirements.
Separate the power input and motor wiring from the signal/process circuit
wiring.
4. Environmental conditions—when using a filter, follow these guidelines:
Ambient temperature: –10 to 50 °C (Derating is required when the ambient
temperature exceeds 40 °C)
Humidity: 20 to 90% RH (non-condensing)
Vibration: 5.9 m/sec2 (0.6 G) 10 ~ 55Hz
Location: 1000 meters or less altitude, indoors (no corrosive gas or dust)
E1
E
Safety
(ISO13849-1)
In This Appendix… page
- Introduction ...................................................................................... 2
- How it works ..................................................................................... 2
- installation ........................................................................................ 2
- Components to be combined .......................................................... 3
- Periodical check .............................................................................. 3
- Precautions ...................................................................................... 3
E2
Introduction
The Gate Suppress function can be utilized to perform a safe stop according to the
EN60204-1, stop category 0 (Uncontrolled stop by power removal). It is designed to
meet the requirements of the ISO13849-1, PL=d only in a system in which EDM signal
is monitored by an “external device monitor”. (Otherwise PL of drive downgraded to
PL=c.)
How it works
Removing the currents from both terminals GS1 and GS2 disables the drive output, i.e.
the power supply to the motor is cut by stopping the switching of the output transistors
in a safe way. EDM output is activated when GS1 and GS2 are given to the drive.
Always use both inputs to disable the drive. If for any reason only one channel is
opened, the drive output is stopped but the EDM output is not activated. In this case
the Safe Disable input wiring must be checked.
Installation
When the Gate Suppress function is utilized, connect the drive to a safety certified
interrupting device utilizing EDM output signal to reconfirm both safety inputs GS1
and GS2. Follow the wiring instructions in the user manual chapter 3.
Safety Related Part
PWR
ERR
G9SX-AD
EI
T2
ED
T1
FBPWR
ERR
G9SX-AD
EI
T2
ED
T1
FB
S14 S24
T31 T33
KM1
M
Inverter
with
Safety stop
function
Safety
Unit
(certificated
acc. to EN954-1
and ISO13849-1)
Safety
Output
EDM
Feedback)
input
GS2
GS1
EDM
CM2
Safety
Iput
Safety
Iput
Manual
Reset
E3
Components to be combined
Followings are the example of the safety devices to be combined.
Series Model Norms to comply reference certificate
GS9A 301 ISO13849-2 cat4, SIL3 06.06.2007
G9SX GS226-T15-RC IEC61508 SIL1-3 04.11.2004
NE1A SCPU01-V1 IEC61508 SIL3 27.09.2006
In combination with the safety device complying with the class complying PL=d,
PL=d of the inverter is to be achieved.
Periodical check
Since the drive stops even one of the GS1 or GS2 is interrupted, it is to be reconfirmed
that there is not faiure in the path of GS1 and GS2 periodically. Period of this
maintenance is once per year, and the method to make sure GS1 and GS2 in
combination with EDM signal is as described below.
Terminal Status
GS1 current OFF current ON current OFF current ON
GS2 current OFF current OFF current ON current ON
EDM conducted not conducted not conducted not conducted
(output) forbidden forbidden forbidden Allowed
Precautions
1. To assure, that the Safe Disable function appropriately fulfills the safety
requirements of the application, a throughout risk assessment for the whole safety
system has to be carried out.
2. If EDM signal is not utilized in the system as a reconfirmation of redundancy
between GS1 and GS2, PL of drive is downgraded to PL=c.
3. The Safe Disable function does not cut the power supply to the drive and does not
provide electrical isolation. Before any installation or maintenance work is done,
the drives power supply must be switched off.
4. The wiring distance for the Safe Disable inputs should be shorter than 30 m.
5. The time from opening the Safe Disable input until the drive output is switched off
is less than 10 ms.
6. When two or more inverters are connected to common GS1 and GS2 wiring, please
be sure to put the diode as instructed in page 4-14, otherwise the drive may start to
work even in the safety mode.